description: "This binding provides native support of Siemens Logo! PLC devices. Communication with Logo is done via Moka7 library. Currently only two devices are supported: 0BA7 (Logo! 7) and 0BA8 (Logo! 8). Additionally multiple devices are supported. Different families of Logo! devices should work also, but was not tested now due to lack of hardware."
source: https://github.com/openhab/openhab1-addons/blob/master/bundles/binding/org.openhab.binding.plclogo/README.md
since: 1x
install: manual
---
<!-- Attention authors: Do not edit directly. Please add your changes to the appropriate source repository -->
{% include base.html %}
# PLCLogo Binding
This binding provides native support of Siemens Logo! PLC devices. Communication with Logo is done via Moka7 library. Currently only two devices are supported: 0BA7 (Logo! 7) and 0BA8 (Logo! 8). Additionally multiple devices are supported. Different families of Logo! devices should work also, but was not tested now due to lack of hardware.
Binding works nicely at least 100ms polling rate.
# Binding Configuration
This binding can be configured in the file `services/plclogo.cfg`.
| Property | Default | Required | Description |
|----------|---------|:--------:|-------------|
| `<plcname>`.host | | Yes | IP address of the LOGO! PLC |
| `<plcname>`.remoteTSAP | | Yes | `TSAP` (in hex) of the **remote** LOGO! PLC, as configured by LogoSoft Comfort. Common used value is 0x0200. |
| `<plcname>`.localTSAP | | Yes | `TSAP` (in hex) to be used by the **local** instance. Common used value is 0x0300. |
| `refresh` | 5000 | No | polling interval, in milliseconds, to be used when querying the Logo! |
## Item Configuration
Follow blocks can be read from on both device types: `I`, `Q`, `M`, `AI`, `AQ` and `AM`. For Logo! 8 devices `NI`, `NQ`, `NAI` and `NAQ` are supported additionally. `Contact` items are used for digital inputs, `Switch` items for digital inputs/outputs and `Number` items for analog inputs/outputs.
Writing to the PLC can be done via `VB` (byte values) and `VW` (word values) for both device types. Use `Switch` items for writing of digital and `Number` of analog values.
The configuration pattern for Contact and Switch items is:
```
plclogo=”<instancename>:<memorylocation>.<maskbit>”
```
Configuration pattern of Number items is:
```
plclogo=”<instancename>:<memorylocation>”
```
## Examples
```
Switch ReadOutputQ13 {plclogo="plc:Q13"}
```
read value of output block `Q13` from Logo! device named 'plc'
```
Switch ReadWriteBinaryValue {plclogo="plc:VB0.0"} }
```
read/write binary input block mapped to `VB` address 0, bit 0
```
Number ReadWriteAnalogValue {plclogo="plc:VW5"}
```
read/write analog input block mapped to `VW` address 5