4512744 / 4512745 Z-Wave Touch Thermostat
This describes the Z-Wave device 4512744 / 4512745, manufactured by Namron with the thing type UID of namron_45127444512745_00_000
.
The device is in the category of HVAC, defining Air condition devices, Fans.
The 4512744 / 4512745 supports routing. This allows the device to communicate using other routing enabled devices as intermediate routers. This device is also able to participate in the routing of data between other devices in the mesh network.
Overview
Z-Wave 16A underfloor heating thermostat with a touch panel. Both internal and external temperature sensor supported. Available in white or black.
Inclusion Information
Under Home Interface, while the device is at OFF mode , press and hold up and down buttons at the same time for over 5 seconds to enter Settings Menu.
Short press move up and down button to select a settings item, then short press button F to enter selected item.
Select ZWAVE INFO on Home Interface to enter into Z-Wave network management interface, to include device as follows:
Method 1: Select “Add”, then short press button , the device will send out inclusion request, “Status” will show “Inclusion...”. If
there is no response from a gateway within 30 seconds, or inclusion failed, “Status” will show “Fail”. If included successfully,
“Status” will show “Inclusion OK” and device ID.
Method 2: Operate the gateway into inclusion mode, make sure the device is already removed from previous network, reset
power off the device, the device will be included to the gateway automatically
Exclusion Information
Select “Remove”, then short press button , the device will send out exclusion request, “Status” will show “Exclusion... If ”.
there is no response from a gateway within 30 seconds, or exclusion failed, “Status” will show “Fail”. If excluded successfully,
“Status” will show “Exclusion OK” and device ID will be showed as 0
General Usage Information
Channels
The following table summarises the channels available for the 4512744 / 4512745 -:
Channel Name | Channel ID | Channel Type | Category | Item Type |
---|---|---|---|---|
Sensor (temperature) | sensor_temperature | sensor_temperature | Temperature | Number:Temperature |
Electric meter (kWh) | meter_kwh | meter_kwh | Energy | Number |
Electric meter (watts) | meter_watts | meter_watts | Energy | Number |
Electric meter (volts) | meter_voltage | meter_voltage | Energy | Number |
Electric meter (amps) | meter_current | meter_current | Energy | Number |
Thermostat mode | thermostat_mode | thermostat_mode | Temperature | Number |
Operating State | thermostat_state | thermostat_state | Temperature | Number |
Setpoint (heating) | thermostat_setpoint | thermostat_setpoint | Heating | Number:Temperature |
Setpoint (dry air) | thermostat_setpoint | thermostat_setpoint | Heating | Number:Temperature |
Alarm (heat) | alarm_heat | alarm_heat | Fire | Switch |
Alarm (power) | alarm_power | alarm_power | Energy | Switch |
Clock Time Offset | time_offset | time_offset | Time | Number |
Sensor (temperature) 1 | sensor_temperature1 | sensor_temperature | Temperature | Number:Temperature |
Electric meter (kWh) 1 | meter_kwh1 | meter_kwh | Energy | Number |
Electric meter (watts) 1 | meter_watts1 | meter_watts | Energy | Number |
Electric meter (volts) 1 | meter_voltage1 | meter_voltage | Energy | Number |
Electric meter (amps) 1 | meter_current1 | meter_current | Energy | Number |
Thermostat mode 1 | thermostat_mode1 | thermostat_mode | Temperature | Number |
Operating State 1 | thermostat_state1 | thermostat_state | Temperature | Number |
Setpoint (heating) 1 | thermostat_setpoint1 | thermostat_setpoint | Heating | Number:Temperature |
Setpoint (dry air) 1 | thermostat_setpoint1 | thermostat_setpoint | Heating | Number:Temperature |
Sensor (temperature) 2 | sensor_temperature2 | sensor_temperature | Temperature | Number:Temperature |
Sensor (temperature)
Indicates the current temperature.
The sensor_temperature
channel is of type sensor_temperature
and supports the Number:Temperature
item and is in the Temperature
category.
Electric meter (kWh)
Indicates the energy consumption (kWh).
The meter_kwh
channel is of type meter_kwh
and supports the Number
item and is in the Energy
category. This is a read only channel so will only be updated following state changes from the device.
Electric meter (watts)
Indicates the instantaneous power consumption.
The meter_watts
channel is of type meter_watts
and supports the Number
item and is in the Energy
category. This is a read only channel so will only be updated following state changes from the device.
Electric meter (volts)
Indicates the instantaneous voltage.
The meter_voltage
channel is of type meter_voltage
and supports the Number
item and is in the Energy
category. This is a read only channel so will only be updated following state changes from the device.
Electric meter (amps)
Indicates the instantaneous current consumption.
The meter_current
channel is of type meter_current
and supports the Number
item and is in the Energy
category. This is a read only channel so will only be updated following state changes from the device.
Thermostat mode
Sets the thermostat.
The thermostat_mode
channel is of type thermostat_mode
and supports the Number
item and is in the Temperature
category.
The following state translation is provided for this channel to the Number
item type -:
Value | Label |
---|---|
0 | Off |
1 | Heat |
2 | Cool |
3 | Auto |
4 | Aux Heat |
5 | Resume |
6 | Fan Only |
7 | Furnace |
8 | Dry Air |
9 | Moist Air |
10 | Auto Changeover |
11 | Heat Economy |
12 | Cool Economy |
13 | Away |
Operating State
Sets the thermostat operating state.
The thermostat_state
channel is of type thermostat_state
and supports the Number
item and is in the Temperature
category.
The following state translation is provided for this channel to the Number
item type -:
Value | Label |
---|---|
0 | Idle |
1 | Heating |
2 | Cooling |
3 | Fan Only |
4 | Pending Heat |
5 | Pending Cool |
6 | Vent / Economiser |
Setpoint (heating)
Sets the thermostat setpoint.
The thermostat_setpoint
channel is of type thermostat_setpoint
and supports the Number:Temperature
item and is in the Heating
category.
Setpoint (dry air)
Sets the thermostat setpoint.
The thermostat_setpoint
channel is of type thermostat_setpoint
and supports the Number:Temperature
item and is in the Heating
category.
Alarm (heat)
Indicates if a heat alarm is triggered.
The alarm_heat
channel is of type alarm_heat
and supports the Switch
item and is in the Fire
category. This is a read only channel so will only be updated following state changes from the device.
The following state translation is provided for this channel to the Switch
item type -:
Value | Label |
---|---|
OFF | OK |
ON | Alarm |
Alarm (power)
Indicates if a power alarm is triggered.
The alarm_power
channel is of type alarm_power
and supports the Switch
item and is in the Energy
category. This is a read only channel so will only be updated following state changes from the device.
The following state translation is provided for this channel to the Switch
item type -:
Value | Label |
---|---|
OFF | OK |
ON | Alarm |
Clock Time Offset
Provides the current time difference for the devices time.
The time_offset
channel is of type time_offset
and supports the Number
item and is in the Time
category.
Sensor (temperature) 1
Indicates the current temperature.
The sensor_temperature1
channel is of type sensor_temperature
and supports the Number:Temperature
item and is in the Temperature
category.
Electric meter (kWh) 1
Indicates the energy consumption (kWh).
The meter_kwh1
channel is of type meter_kwh
and supports the Number
item and is in the Energy
category. This is a read only channel so will only be updated following state changes from the device.
Electric meter (watts) 1
Indicates the instantaneous power consumption.
The meter_watts1
channel is of type meter_watts
and supports the Number
item and is in the Energy
category. This is a read only channel so will only be updated following state changes from the device.
Electric meter (volts) 1
Indicates the instantaneous voltage.
The meter_voltage1
channel is of type meter_voltage
and supports the Number
item and is in the Energy
category. This is a read only channel so will only be updated following state changes from the device.
Electric meter (amps) 1
Indicates the instantaneous current consumption.
The meter_current1
channel is of type meter_current
and supports the Number
item and is in the Energy
category. This is a read only channel so will only be updated following state changes from the device.
Thermostat mode 1
Sets the thermostat.
The thermostat_mode1
channel is of type thermostat_mode
and supports the Number
item and is in the Temperature
category.
The following state translation is provided for this channel to the Number
item type -:
Value | Label |
---|---|
0 | Off |
1 | Heat |
2 | Cool |
3 | Auto |
4 | Aux Heat |
5 | Resume |
6 | Fan Only |
7 | Furnace |
8 | Dry Air |
9 | Moist Air |
10 | Auto Changeover |
11 | Heat Economy |
12 | Cool Economy |
13 | Away |
Operating State 1
Sets the thermostat operating state.
The thermostat_state1
channel is of type thermostat_state
and supports the Number
item and is in the Temperature
category.
The following state translation is provided for this channel to the Number
item type -:
Value | Label |
---|---|
0 | Idle |
1 | Heating |
2 | Cooling |
3 | Fan Only |
4 | Pending Heat |
5 | Pending Cool |
6 | Vent / Economiser |
Setpoint (heating) 1
Sets the thermostat setpoint.
The thermostat_setpoint1
channel is of type thermostat_setpoint
and supports the Number:Temperature
item and is in the Heating
category.
Setpoint (dry air) 1
Sets the thermostat setpoint.
The thermostat_setpoint1
channel is of type thermostat_setpoint
and supports the Number:Temperature
item and is in the Heating
category.
Sensor (temperature) 2
Indicates the current temperature.
The sensor_temperature2
channel is of type sensor_temperature
and supports the Number:Temperature
item and is in the Temperature
category.
Device Configuration
The following table provides a summary of the 23 configuration parameters available in the 4512744 / 4512745. Detailed information on each parameter can be found in the sections below.
Param | Name | Description |
---|---|---|
0 | Meter reports | Time interval value for periodic active report of Meter 60-2678400 (31 days) , unit is S |
2 | Overcurrent detection max value | Over current detection max. value, unit is A. When detected current is over this value, the device will turn off the relay and send NOTIFICATION CC. 0, disable over current detection 5-16, over current detection max. value |
3 | Vibration and buzzer level | Vibration level and buzzer level triggered by pressing buttons 0, disable vibration and buzzer 1, Low Level 2, High Level |
4 | Recover settings on power reset | Whether to recover to settings before power failure or power reset 0, use default settings 1, recover to settings before power failure or power reset |
6 | Floor temperature detection max value | Floor temperature detection max. value, unit is ℃ , when floor temperature sensor is higher than this value, the device will turn off the relay and send NOTIFICATION CC. 0, disable this function 1-35, the high temperature value |
7 | Temperature control hysteresis | Temperature control hysteresis value setting, setting range 0.5℃-5℃. 5 Monitor Set value range is 5-50, unit is 0.1℃ |
8 | Auto mode temperature schedule | Auto mode (Energy save mode) temperature schedule 0, use schedule set by user 1, use Energy_Save_Heating temperature set by THERMOSTAT_SETPOINT_SET |
9 | Floor temperature sensor | Select floor temperature sensor type 1, NTC/10K B(25/50°C)=3950 2, NTC/15K B(25/50°C)=3950 3, NTC/50K B(25/50°C)=3950 4, NTC/100K B(25/50°C)=3950 5, NTC/12K B(25/50°C)=3950 |
10 | Temperature control reference selection | Temperature control reference selection 1, room sensor 2, floor sensor 3, room+floor sensor |
11 | Room sensor temperature compensation | ROOM SENSOR temperature compensation setting -10~10, unit is 0.5℃ |
12 | Floor sensor temperature compensation | Floor sensor temperature compensation setting -10~10, unit is 0.5℃ |
13 | Duration of drying mode | Set how long the drying mode lasts 5~100, unit is minute |
14 | Mode after drying mode | Set the mode after the drying mode ends 0x00 = OFF 0x01 = Manual mode (comfort mode) 0x02 = Auto mode (energy save mode) 0x03 = Away mode |
16 | Report temperature relative change threshold | When to report temperature relative change threshold value actively, unit is 0.1℃ 0, disable to report 2-10, report when the threshold value is 2-10 |
17 | Time interval for periodic report of temperature | Time interval value for periodic report of temperature, humidity, unit is S 0, disable to report 30~28800, report when time interval value is 30~28800 |
18 | When to report power change | When to report power change absolute threshold, unit is W 0, disable to report 1~100, report when absolute threshold is 1~100 |
19 | Report current change | When to report current change absolute threshold, unit is 0.1A 0, disable to report 1~10, report when absolute threshold is 1~10 |
20 | Report voltage change | When to report voltage change absolute threshold, unit is 1 V 0, disable to report 1~10, report when absolute threshold is 1~10 |
21 | Meter reports | Time interval value for periodic active report of Meter 60-2678400 (31 days) , unit is S |
22 | OLED Display brightness | The OLED display brightness when operate the device. 0, low level 1, mid level 2, high level |
23 | Sensor to show in display | This parameter defines which sensor temperature will be displayed on Home page. 0x00: indoor air temperature 0x01: external temperature (floor temperature) |
24 | Time Zone | The time zone that the time parameters command adopts is UTC, the time zone need to be set: +12 ~ -12 |
27 | Display Auto-off | Enable or disable Display Auto Off function when the interface is standby interface. 0, disabled 1, enabled |
Parameter 0: Meter reports
Time interval value for periodic active report of Meter 60-2678400 (31 days) , unit is S This is an advanced parameter and will therefore not show in the user interface without entering advanced mode. Values in the range 60 to 2678400 may be set.
The manufacturer defined default value is 600
.
This parameter has the configuration ID config_0_4
and is of type INTEGER
.
Parameter 2: Overcurrent detection max value
Over current detection max. value, unit is A. When detected current is over this value, the device will turn off the relay and send NOTIFICATION CC. 0, disable over current detection 5-16, over current detection max. value This is an advanced parameter and will therefore not show in the user interface without entering advanced mode. Values in the range 0 to 16 may be set.
The manufacturer defined default value is 16
.
This parameter has the configuration ID config_2_1
and is of type INTEGER
.
Parameter 3: Vibration and buzzer level
Vibration level and buzzer level triggered by pressing buttons 0, disable vibration and buzzer 1, Low Level 2, High Level
The following option values may be configured, in addition to values in the range 1 to 2 -:
Value | Description |
---|---|
1 | Low |
2 | High |
The manufacturer defined default value is 1
(Low).
This parameter has the configuration ID config_3_1
and is of type INTEGER
.
Parameter 4: Recover settings on power reset
Whether to recover to settings before power failure or power reset 0, use default settings 1, recover to settings before power failure or power reset
The following option values may be configured, in addition to values in the range 0 to 1 -:
Value | Description |
---|---|
0 | Do not recover to settings |
1 | Recover to settings |
The manufacturer defined default value is 1
(Recover to settings).
This parameter has the configuration ID config_4_1
and is of type INTEGER
.
Parameter 6: Floor temperature detection max value
Floor temperature detection max. value, unit is ℃ , when floor temperature sensor is higher than this value, the device will turn off the relay and send NOTIFICATION CC. 0, disable this function 1-35, the high temperature value This is an advanced parameter and will therefore not show in the user interface without entering advanced mode. Values in the range 1 to 35 may be set.
The manufacturer defined default value is 27
.
This parameter has the configuration ID config_6_1
and is of type INTEGER
.
Parameter 7: Temperature control hysteresis
Temperature control hysteresis value setting, setting range 0.5℃-5℃. 5 Monitor Set value range is 5-50, unit is 0.1℃ This is an advanced parameter and will therefore not show in the user interface without entering advanced mode. Values in the range 5 to 50 may be set.
The manufacturer defined default value is 5
.
This parameter has the configuration ID config_7_1
and is of type INTEGER
.
Parameter 8: Auto mode temperature schedule
Auto mode (Energy save mode) temperature schedule 0, use schedule set by user 1, use Energy_Save_Heating temperature set by THERMOSTAT_SETPOINT_SET
The following option values may be configured, in addition to values in the range 0 to 1 -:
Value | Description |
---|---|
0 | Use schedule set by user |
1 | Use Energy_Save_Heating temperature set by THERMOSTAT_SETPOINT_SET |
The manufacturer defined default value is 0
(Use schedule set by user).
This parameter has the configuration ID config_8_1
and is of type INTEGER
.
Parameter 9: Floor temperature sensor
Select floor temperature sensor type 1, NTC/10K B(25/50°C)=3950 2, NTC/15K B(25/50°C)=3950 3, NTC/50K B(25/50°C)=3950 4, NTC/100K B(25/50°C)=3950 5, NTC/12K B(25/50°C)=3950
The following option values may be configured, in addition to values in the range 1 to 5 -:
Value | Description |
---|---|
1 | NTC/10K B(25/50°C)=3950 |
2 | NTC/15K B(25/50°C)=3950 |
3 | NTC/50K B(25/50°C)=3950 |
4 | NTC/100K B(25/50°C)=3950 |
5 | NTC/12K B(25/50°C)=3950 |
The manufacturer defined default value is 1
(NTC/10K B(25/50°C)=3950).
This parameter has the configuration ID config_9_1
and is of type INTEGER
.
Parameter 10: Temperature control reference selection
Temperature control reference selection 1, room sensor 2, floor sensor 3, room+floor sensor This is an advanced parameter and will therefore not show in the user interface without entering advanced mode. The following option values may be configured, in addition to values in the range 1 to 3 -:
Value | Description |
---|---|
1 | Room sensor only |
2 | Floor sensor only |
3 | Room + floor sensor |
The manufacturer defined default value is 1
(Room sensor only).
This parameter has the configuration ID config_10_1
and is of type INTEGER
.
Parameter 11: Room sensor temperature compensation
ROOM SENSOR temperature compensation setting -10~10, unit is 0.5℃ This is an advanced parameter and will therefore not show in the user interface without entering advanced mode. Values in the range -10 to 10 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_11_1
and is of type INTEGER
.
Parameter 12: Floor sensor temperature compensation
Floor sensor temperature compensation setting -10~10, unit is 0.5℃ This is an advanced parameter and will therefore not show in the user interface without entering advanced mode. Values in the range -10 to 10 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_12_1
and is of type INTEGER
.
Parameter 13: Duration of drying mode
Set how long the drying mode lasts 5~100, unit is minute
Values in the range 5 to 100 may be set.
The manufacturer defined default value is 30
.
This parameter has the configuration ID config_13_1
and is of type INTEGER
.
Parameter 14: Mode after drying mode
Set the mode after the drying mode ends 0x00 = OFF 0x01 = Manual mode (comfort mode) 0x02 = Auto mode (energy save mode) 0x03 = Away mode
The following option values may be configured, in addition to values in the range 0 to 3 -:
Value | Description |
---|---|
0 | Off |
1 | Manual (comfort mode) |
2 | Auto (energy saver) |
3 | Away mode |
The manufacturer defined default value is 2
(Auto (energy saver)).
This parameter has the configuration ID config_14_1
and is of type INTEGER
.
Parameter 16: Report temperature relative change threshold
When to report temperature relative change threshold value actively, unit is 0.1℃ 0, disable to report 2-10, report when the threshold value is 2-10 This is an advanced parameter and will therefore not show in the user interface without entering advanced mode. Values in the range 0 to 10 may be set.
The manufacturer defined default value is 2
.
This parameter has the configuration ID config_16_1
and is of type INTEGER
.
Parameter 17: Time interval for periodic report of temperature
Time interval value for periodic report of temperature, humidity, unit is S 0, disable to report 30~28800, report when time interval value is 30~28800
Values in the range 0 to 28800 may be set.
The manufacturer defined default value is 300
.
This parameter has the configuration ID config_17_1
and is of type INTEGER
.
Parameter 18: When to report power change
When to report power change absolute threshold, unit is W 0, disable to report 1~100, report when absolute threshold is 1~100 This is an advanced parameter and will therefore not show in the user interface without entering advanced mode. Values in the range 1 to 100 may be set.
The manufacturer defined default value is 5
.
This parameter has the configuration ID config_18_1
and is of type INTEGER
.
Parameter 19: Report current change
When to report current change absolute threshold, unit is 0.1A 0, disable to report 1~10, report when absolute threshold is 1~10 This is an advanced parameter and will therefore not show in the user interface without entering advanced mode. Values in the range 1 to 10 may be set.
The manufacturer defined default value is 10
.
This parameter has the configuration ID config_19_1
and is of type INTEGER
.
Parameter 20: Report voltage change
When to report voltage change absolute threshold, unit is 1 V 0, disable to report 1~10, report when absolute threshold is 1~10 This is an advanced parameter and will therefore not show in the user interface without entering advanced mode. Values in the range 1 to 10 may be set.
The manufacturer defined default value is 2
.
This parameter has the configuration ID config_20_1
and is of type INTEGER
.
Parameter 21: Meter reports
Time interval value for periodic active report of Meter 60-2678400 (31 days) , unit is S This is an advanced parameter and will therefore not show in the user interface without entering advanced mode. Values in the range 60 to 2678400 may be set.
The manufacturer defined default value is 600
.
This parameter has the configuration ID config_21_4
and is of type INTEGER
.
Parameter 22: OLED Display brightness
The OLED display brightness when operate the device. 0, low level 1, mid level 2, high level
The following option values may be configured, in addition to values in the range 0 to 2 -:
Value | Description |
---|---|
0 | Low level |
1 | Medium level |
2 | High level |
The manufacturer defined default value is 1
(Medium level).
This parameter has the configuration ID config_22_1
and is of type INTEGER
.
Parameter 23: Sensor to show in display
This parameter defines which sensor temperature will be displayed on Home page. 0x00: indoor air temperature 0x01: external temperature (floor temperature)
The following option values may be configured, in addition to values in the range 0 to 1 -:
Value | Description |
---|---|
0 | Indoor air temperature |
1 | Floor temperature |
The manufacturer defined default value is 0
(Indoor air temperature).
This parameter has the configuration ID config_23_1
and is of type INTEGER
.
Parameter 24: Time Zone
The time zone that the time parameters command adopts is UTC, the time zone need to be set: +12 ~ -12
Values in the range -12 to 12 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_24_1
and is of type INTEGER
.
Parameter 27: Display Auto-off
Enable or disable Display Auto Off function when the interface is standby interface. 0, disabled 1, enabled
The following option values may be configured, in addition to values in the range 0 to 1 -:
Value | Description |
---|---|
0 | Disabled |
1 | Enabled |
The manufacturer defined default value is 0
(Disabled).
This parameter has the configuration ID config_27_1
and is of type INTEGER
.
Association Groups
Association groups allow the device to send unsolicited reports to the controller, or other devices in the network. Using association groups can allow you to eliminate polling, providing instant feedback of a device state change without unnecessary network traffic.
The 4512744 / 4512745 supports 2 association groups.
Group 1: Lifeline
The Lifeline association group reports device status to a hub and is not designed to control other devices directly. When using the Lineline group with a hub, in most cases, only the lifeline group will need to be configured and normally the hub will perform this automatically during the device initialisation. 1.Send Command Class DEVICE_RESET_LOCALLY_NOTIFICATION to associated devices of this group when factory reset the device. 2.Send Command Class THERMOSTAT_SETPOINT_REPORT, THERMOSTAT_MODE_REPORT, THERMOSTAT_OPERATING_STATE_REPORT to associated devices of t
Association group 1 supports 5 nodes.
Group 2: Heat Set
Transfer Command Class THERMOSTAT_SETPOINT_SET THERMOSTAT_MODE_SET to control other temperature control devices when operation changes
Association group 2 supports 5 nodes.
Technical Information
Endpoints
Endpoint 0
Command Class | Comment |
---|---|
COMMAND_CLASS_NO_OPERATION_V1 | |
COMMAND_CLASS_BASIC_V1 | |
COMMAND_CLASS_SENSOR_MULTILEVEL_V5 | |
COMMAND_CLASS_METER_V3 | |
COMMAND_CLASS_THERMOSTAT_MODE_V1 | |
COMMAND_CLASS_THERMOSTAT_OPERATING_STATE_V1 | |
COMMAND_CLASS_THERMOSTAT_SETPOINT_V1 | |
COMMAND_CLASS_TRANSPORT_SERVICE_V1 | |
COMMAND_CLASS_ASSOCIATION_GRP_INFO_V1 | |
COMMAND_CLASS_DEVICE_RESET_LOCALLY_V1 | |
COMMAND_CLASS_ZWAVEPLUS_INFO_V1 | |
COMMAND_CLASS_MULTI_CHANNEL_V2 | |
COMMAND_CLASS_SUPERVISION_V1 | |
COMMAND_CLASS_CONFIGURATION_V1 | |
COMMAND_CLASS_ALARM_V8 | |
COMMAND_CLASS_MANUFACTURER_SPECIFIC_V1 | |
COMMAND_CLASS_POWERLEVEL_V1 | |
COMMAND_CLASS_FIRMWARE_UPDATE_MD_V1 | |
COMMAND_CLASS_ASSOCIATION_V2 | |
COMMAND_CLASS_VERSION_V2 | |
COMMAND_CLASS_TIME_PARAMETERS_V1 | |
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION_V3 | |
COMMAND_CLASS_SECURITY_V1 | |
COMMAND_CLASS_SECURITY_2_V1 |
Endpoint 1
Command Class | Comment |
---|---|
COMMAND_CLASS_BASIC_V1 | |
COMMAND_CLASS_SENSOR_MULTILEVEL_V5 | |
COMMAND_CLASS_METER_V3 | |
COMMAND_CLASS_THERMOSTAT_MODE_V1 | |
COMMAND_CLASS_THERMOSTAT_OPERATING_STATE_V1 | |
COMMAND_CLASS_THERMOSTAT_SETPOINT_V1 | |
COMMAND_CLASS_ASSOCIATION_GRP_INFO_V1 | |
COMMAND_CLASS_ZWAVEPLUS_INFO_V1 | |
COMMAND_CLASS_ASSOCIATION_V2 | |
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION_V3 | |
COMMAND_CLASS_SECURITY_V1 |
Endpoint 2
Command Class | Comment |
---|---|
COMMAND_CLASS_BASIC_V1 | |
COMMAND_CLASS_SENSOR_MULTILEVEL_V5 | |
COMMAND_CLASS_ASSOCIATION_GRP_INFO_V1 | |
COMMAND_CLASS_ZWAVEPLUS_INFO_V1 | |
COMMAND_CLASS_ASSOCIATION_V2 | |
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION_V3 | |
COMMAND_CLASS_SECURITY_V1 |