openhab-docs/_addons_bindings/zwave/doc/eurotronic/temphumidity_0_0.md

9.7 KiB
Raw Permalink Blame History

layout title
documentation Eurotronic Temperature & Humidity Sensor Z-Wave Plus - ZWave

{% include base.html %}

Eurotronic Temperature & Humidity Sensor Z-Wave Plus Temperature & Humidity Sensor Z-Wave Plus

This describes the Z-Wave device Eurotronic Temperature & Humidity Sensor Z-Wave Plus, manufactured by Eurotronics with the thing type UID of eurotronic_temphumidity_00_000.

The device is in the category of Battery, defining Batteries, Energy Storages.

Eurotronic Temperature & Humidity Sensor Z-Wave Plus product image

The Eurotronic Temperature & Humidity Sensor Z-Wave Plus supports routing. This allows the device to communicate using other routing enabled devices as intermediate routers. This device is unable to participate in the routing of data from other devices.

The Eurotronic Temperature & Humidity Sensor Z-Wave Plus does not permanently listen for messages sent from the controller - it will periodically wake up automatically to check if the controller has messages to send, but will sleep most of the time to conserve battery life. Refer to the Wakeup Information section below for further information.

Overview

The Temperature & Humidity Sensor Z-Wave Plus is a temperature and humidity sensor for living and working rooms that is compatible with the Z-Wave wireless standard.

Inclusion Information

Press button three times within 1 second

Exclusion Information

Press button three times within 1 second

Wakeup Information

The Eurotronic Temperature & Humidity Sensor Z-Wave Plus does not permanently listen for messages sent from the controller - it will periodically wake up automatically to check if the controller has messages to send, but will sleep most of the time to conserve battery life. The wakeup period can be configured in the user interface - it is advisable not to make this too short as it will impact battery life - a reasonable compromise is 1 hour.

The wakeup period does not impact the devices ability to report events or sensor data. The device can be manually woken with a button press on the device as described below - note that triggering a device to send an event is not the same as a wakeup notification, and this will not allow the controller to communicate with the device.

Press button once

General Usage Information

Holding button for 10 seconds resets to factory default settngs.

Channels

The following table summarises the channels available for the Eurotronic Temperature & Humidity Sensor Z-Wave Plus -:

Channel Name Channel ID Channel Type Category Item Type
Sensor (relative humidity) sensor_relhumidity sensor_relhumidity Humidity Number
Sensor (temperature) sensor_temperature sensor_temperature Temperature Number:Temperature
Sensor (dew point) sensor_dewpoint sensor_dewpoint Temperature Number
Battery Level battery-level system.battery_level Battery Number

Sensor (relative humidity)

Indicates the current relative humidity.

The sensor_relhumidity channel is of type sensor_relhumidity and supports the Number item and is in the Humidity category. This is a read only channel so will only be updated following state changes from the device.

Sensor (temperature)

Indicates the current temperature.

The sensor_temperature channel is of type sensor_temperature and supports the Number:Temperature item and is in the Temperature category.

Sensor (dew point)

Indicates the dewpoint.

The sensor_dewpoint channel is of type sensor_dewpoint and supports the Number item and is in the Temperature category. This is a read only channel so will only be updated following state changes from the device.

Battery Level

Represents the battery level as a percentage (0-100%). Bindings for things supporting battery level in a different format (e.g. 4 levels) should convert to a percentage to provide a consistent battery level reading.

The system.battery-level channel is of type system.battery-level and supports the Number item and is in the Battery category. This channel provides the battery level as a percentage and also reflects the low battery warning state. If the battery state is in low battery warning state, this will read 0%.

Device Configuration

The following table provides a summary of the 5 configuration parameters available in the Eurotronic Temperature & Humidity Sensor Z-Wave Plus. Detailed information on each parameter can be found in the sections below.

Param Name Description
1 Temperature Reporting Temperature Change on Reporting
2 Humidity Reporting Humidity Change on Reporting
3 Temperature Unit Temperature Unit
4 Temperature Resolution Temperature Resolution
5 Humidity Resolution Humidity Resolution
Wakeup Interval Sets the interval at which the device will accept commands from the controller
Wakeup Node Sets the node ID of the device to receive the wakeup notifications

Parameter 1: Temperature Reporting

Temperature Change on Reporting 0x00 No on change reporting (only time-based reports)

0x01 0x32 report if temperature changed by delta = 0,1°C…5,0°C Values in the range 0 to 32 may be set.

The manufacturer defined default value is 5.

This parameter has the configuration ID config_1_1 and is of type INTEGER.

Parameter 2: Humidity Reporting

Humidity Change on Reporting 0x00 No on change reporting (only time-based reports).

0x01-0x0A report if humidity changed by delta = 1% …10% Values in the range 0 to 10 may be set.

The manufacturer defined default value is 5.

This parameter has the configuration ID config_2_1 and is of type INTEGER.

Parameter 3: Temperature Unit

Temperature Unit

Values in the range 0 to 1 may be set.

The manufacturer defined default value is 0.

This parameter has the configuration ID config_3_1 and is of type INTEGER.

Parameter 4: Temperature Resolution

Temperature Resolution

Values in the range 0 to 2 may be set.

The manufacturer defined default value is 1.

This parameter has the configuration ID config_4_1 and is of type INTEGER.

Parameter 5: Humidity Resolution

Humidity Resolution

Values in the range 0 to 2 may be set.

The manufacturer defined default value is 0.

This parameter has the configuration ID config_5_1 and is of type INTEGER.

Wakeup Interval

The wakeup interval sets the period at which the device will listen for messages from the controller. This is required for battery devices that sleep most of the time in order to conserve battery life. The device will wake up at this interval and send a message to the controller to tell it that it can accept messages - after a few seconds, it will go back to sleep if there is no further communications.

This setting is defined in seconds. It is advisable not to set this interval too short or it could impact battery life. A period of 1 hour (3600 seconds) is suitable in most instances.

Note that this setting does not affect the devices ability to send sensor data, or notification events.

This parameter has the configuration ID wakeup_interval and is of type INTEGER.

Wakeup Node

When sleeping devices wake up, they send a notification to a listening device. Normally, this device is the network controller, and normally the controller will set this automatically to its own address. In the event that the network contains multiple controllers, it may be necessary to configure this to a node that is not the main controller. This is an advanced setting and should not be changed without a full understanding of the impact.

This parameter has the configuration ID wakeup_node and is of type INTEGER.

Association Groups

Association groups allow the device to send unsolicited reports to the controller, or other devices in the network. Using association groups can allow you to eliminate polling, providing instant feedback of a device state change without unnecessary network traffic.

The Eurotronic Temperature & Humidity Sensor Z-Wave Plus supports 2 association groups.

Group 1: Lifeline

The Lifeline association group reports device status to a hub and is not designed to control other devices directly. When using the Lineline group with a hub, in most cases, only the lifeline group will need to be configured and normally the hub will perform this automatically during the device initialisation.

Association group 1 supports 1 node.

Group 2: Temperature

Association group 2 supports 5 nodes.

Technical Information

Endpoints

Endpoint 0

Command Class Comment
COMMAND_CLASS_NO_OPERATION_V1
COMMAND_CLASS_SENSOR_MULTILEVEL_V5
COMMAND_CLASS_TRANSPORT_SERVICE_V1
COMMAND_CLASS_ASSOCIATION_GRP_INFO_V1
COMMAND_CLASS_DEVICE_RESET_LOCALLY_V1
COMMAND_CLASS_ZWAVEPLUS_INFO_V1
COMMAND_CLASS_SUPERVISION_V1
COMMAND_CLASS_CONFIGURATION_V1
COMMAND_CLASS_MANUFACTURER_SPECIFIC_V1
COMMAND_CLASS_POWERLEVEL_V1
COMMAND_CLASS_FIRMWARE_UPDATE_MD_V1
COMMAND_CLASS_BATTERY_V1
COMMAND_CLASS_WAKE_UP_V2
COMMAND_CLASS_ASSOCIATION_V2
COMMAND_CLASS_VERSION_V2
COMMAND_CLASS_SECURITY_V1
COMMAND_CLASS_SECURITY_2_V1

Did you spot an error in the above definition or want to improve the content? You can contribute to the database here.