APC UPSD Input Plugin
This plugin gathers data from one or more apcupsd daemon over the NIS network protocol. To query a server, the daemon must be running and be accessible.
Introduced in: Telegraf v1.12.0 Tags: hardware, server OS support: all
Global configuration options
Plugins support additional global and plugin configuration settings for tasks such as modifying metrics, tags, and fields, creating aliases, and configuring plugin ordering. See CONFIGURATION.md for more details.
Configuration
# Monitor APC UPSes connected to apcupsd
[[inputs.apcupsd]]
# A list of running apcupsd server to connect to.
# If not provided will default to tcp://127.0.0.1:3551
servers = ["tcp://127.0.0.1:3551"]
## Timeout for dialing server.
timeout = "5s"
Metrics
- apcupsd
- tags:
- serial
- ups_name
- status (string representing the set status_flags)
- model
- fields:
- status_flags (status-bits)
- input_voltage
- load_percent
- battery_charge_percent
- time_left_ns
- output_voltage
- internal_temp
- battery_voltage
- input_frequency
- time_on_battery_ns
- cumulative_time_on_battery_ns
- nominal_input_voltage
- nominal_battery_voltage
- nominal_power
- firmware
- battery_date
- last_transfer
- number_transfers
- tags:
Example Output
apcupsd,serial=AS1231515,status=ONLINE,ups_name=name1 time_on_battery=0,load_percent=9.7,time_left_minutes=98,output_voltage=230.4,internal_temp=32.4,battery_voltage=27.4,input_frequency=50.2,input_voltage=230.4,battery_charge_percent=100,status_flags=8i 1490035922000000000