Markdown
---
|
|
title: KNX
|
|
description: Instructions on how to integrate KNX components with Home Assistant.
|
|
featured: true
|
|
ha_category:
|
|
- Binary sensor
|
|
- Button
|
|
- Climate
|
|
- Cover
|
|
- Date
|
|
- Fan
|
|
- Hub
|
|
- Light
|
|
- Notifications
|
|
- Number
|
|
- Scene
|
|
- Select
|
|
- Sensor
|
|
- Switch
|
|
- Text
|
|
- Time
|
|
- Weather
|
|
ha_release: 0.24
|
|
ha_iot_class: Local Push
|
|
ha_codeowners:
|
|
- '@Julius2342'
|
|
- '@farmio'
|
|
- '@marvin-w'
|
|
ha_domain: knx
|
|
ha_platforms:
|
|
- binary_sensor
|
|
- button
|
|
- climate
|
|
- cover
|
|
- date
|
|
- datetime
|
|
- diagnostics
|
|
- fan
|
|
- light
|
|
- notify
|
|
- number
|
|
- scene
|
|
- select
|
|
- sensor
|
|
- switch
|
|
- text
|
|
- time
|
|
- weather
|
|
ha_config_flow: true
|
|
ha_integration_type: hub
|
|
ha_quality_scale: silver
|
|
---
|
|
|
|
The [KNX](https://www.knx.org) integration connects Home Assistant to your KNX installation, allowing you to control KNX devices, act on telegrams and forward state changes from other integrations entities to your KNX bus.
|
|
|
|
This integration requires a local KNX/IP interface or router to establish the connection between Home Assistant and your KNX bus.
|
|
|
|
There is currently support for the following device types within Home Assistant:
|
|
|
|
- [Binary sensor](#binary-sensor)
|
|
- [Button](#button)
|
|
- [Climate](#climate)
|
|
- [Cover](#cover)
|
|
- [Date](#date)
|
|
- [Fan](#fan)
|
|
- [Light](#light)
|
|
- [Notify](#notify)
|
|
- [Number](#number)
|
|
- [Scene](#scene)
|
|
- [Select](#select)
|
|
- [Sensor](#sensor)
|
|
- [Switch](#switch)
|
|
- [Text](#text)
|
|
- [Time](#time)
|
|
- [Weather](#weather)
|
|
|
|
{% include integrations/config_flow.md %}
|
|
|
|
### KNX Connection
|
|
|
|
Select the connection type to your KNX bus. The integration supports the following connection methods:
|
|
|
|
- 'Automatic' performs a gateway scan on start, to find a KNX IP interface. It will connect via a tunnel. This option is not available when a gateway scan at setup initiation was not successful.
|
|
- 'Tunneling' will connect to a specific KNX IP interface over a tunnel.
|
|
- 'Routing' will use Multicast to communicate with KNX IP routers.
|
|
|
|
For more information about KNX connection types see [Connection](#connection).
|
|
|
|
### Tunneling specific settings
|
|
|
|
You can select a specific tunnel device if multiple were found during the setup. In case no device was discovered, you can configure connection information manually.
|
|
|
|
{% configuration_basic %}
|
|
KNX tunneling type:
|
|
description: "`UDP`, `TCP` or `Secure Tunneling`"
|
|
Host:
|
|
description: "IP address or hostname of the KNX/IP tunneling device."
|
|
Port:
|
|
description: "Port used by the KNX/IP tunneling device."
|
|
Route back / NAT mode:
|
|
description: "Enable if your KNXnet/IP tunneling server is behind NAT. Only applies for UDP connections."
|
|
Local IP interface:
|
|
description: "Local IP or interface name used for the connection from Home Assistant. Leave blank to use auto-discovery."
|
|
{% endconfiguration_basic %}
|
|
|
|
#### Tunnel endpoint
|
|
|
|
Select the tunnel endpoint used for the connection. This step is only available for `TCP` or `Secure Tunneling` connection types.
|
|
|
|
### Routing specific settings
|
|
|
|
{% configuration_basic %}
|
|
Individual address:
|
|
description: "KNX individual address to be used by Home Assistant to send telegrams. This shall not be used by any other device in your installation."
|
|
KNX IP Secure Routing:
|
|
description: "Select if your installation uses encrypted communication according to the KNX IP Secure standard. This setting requires compatible devices and configuration. You'll be prompted for credentials in the next step."
|
|
Multicast group:
|
|
description: "Multicast group used by your installation. Default is `224.0.23.12`"
|
|
Multicast port:
|
|
description: "Multicast port used by your installation. Default is `3671`"
|
|
Local IP interface:
|
|
description: "Local IP or interface name used for the connection from Home Assistant. Leave blank to use auto-discovery."
|
|
{% endconfiguration_basic %}
|
|
|
|
### KNX IP Secure specific settings
|
|
|
|
See [Connection](#connection) on how to get the files or keys needed for this configuration step.
|
|
|
|
## Reconfiguration
|
|
|
|
You can change your KNX connection configuration at any time through the integration settings. This is useful when you need to update the Keyring file or switch to a different connection type.
|
|
|
|
1. Go to {% my integrations icon title="**Settings** > **Devices & services**" %}.
|
|
2. Select **KNX**.
|
|
3. Click the three-dot {% icon "mdi:dots-vertical" %} menu and then select **Reconfigure**.
|
|
|
|
### Configure KNX interface
|
|
|
|
Reconfigure your connection settings. See above for more information.
|
|
|
|
### Import KNX Keyring
|
|
|
|
Provide a new keyring file to be used by the integration. See [KNX Secure](#knx-secure) on how to get this file.
|
|
|
|
{% include integrations/option_flow.md %}
|
|
|
|
{% configuration_basic %}
|
|
State updater:
|
|
description: "Sets the default behavior for periodically reading state addresses from the KNX Bus."
|
|
Rate limit:
|
|
description: "Maximum outgoing telegrams per second. `0` to disable limit - which is recommended."
|
|
Telegram history limit:
|
|
description: "Number of Telegrams to keep in memory for the KNX panels group monitor."
|
|
{% endconfiguration_basic %}
|
|
|
|
## Basic configuration
|
|
|
|
In order to make use of the various platforms offered by the KNX integration, you will need to set them up via the KNX panel or add the corresponding configuration yaml to your {% term "`configuration.yaml`" %}. See [Splitting up the configuration](/docs/configuration/splitting_configuration/) if you like to arrange YAML parts in dedicated files.
|
|
{% include integrations/restart_ha_after_config_inclusion.md %}
|
|
|
|
```yaml
|
|
knx:
|
|
# configure platforms directly in configuration.yaml
|
|
binary_sensor:
|
|
- name: "My first binary sensor"
|
|
state_address: "1/2/3"
|
|
# etc...
|
|
# or outsource platform configuration to separate files
|
|
sensor: !include knx_sensor.yaml
|
|
```
|
|
|
|
Please see the dedicated platform sections below about how to configure them correctly.
|
|
|
|
### Group addresses
|
|
|
|
Group addresses are configured as strings or integers in the format "1/2/3" for 3-level GA-structure, "1/2" for 2-level GA-structure or "1" for free GA-structure.
|
|
|
|
The HA KNX integration uses configured `state_address` or `*_state_address` to update the state of a function. These addresses are read by GroupValueRead requests on startup and when there was no incoming telegram for one hour (default `sync_state`).
|
|
|
|
It is possible to configure passive/listening group addresses for all functions of every KNX platform (except `expose` and `notify`). This allows having multiple group addresses to update the state of its function (e.g., the brightness of a light). When group addresses are configured as a list of strings, the first item is the active sending or state-reading address and the rest is registered as passive addresses. This schema behaves like in ETS configuration where the first is the "sending" address and others are just for updating the group object.
|
|
|
|
If your KNX device provides active state group objects it is advised to use `*_state_address` instead of passive addresses as it reduces configuration complexity and avoids wrong states (e.g., when channels are logically locked).
|
|
|
|
```yaml
|
|
knx:
|
|
switch:
|
|
- name: "Switch without passive addresses"
|
|
address: "1/1/1" # this is the address that will be sent to
|
|
state_address: "8/8/8" # this is the address GroupValueRead requests are sent to
|
|
- name: "Switch with passive addresses"
|
|
address:
|
|
- "1/1/1" # this is the address that will be sent to
|
|
- "1/1/2" # this and following are passive addresses
|
|
- "1/1/3"
|
|
state_address:
|
|
- "8/8/8" # this is the address GroupValueRead requests are sent to
|
|
- "8/8/2" # this and following are passive addresses
|
|
- "8/8/3"
|
|
```
|
|
|
|
## Connection
|
|
|
|
Connection parameters are configured during integration setup and can be modified later in the integrations settings.
|
|
|
|
### KNX Secure
|
|
|
|
The KNX integration supports both IP Secure and Data Secure.
|
|
|
|
#### IP Secure
|
|
|
|
IP Secure credentials can be provided in two ways:
|
|
|
|
1. Using a `.knxkeys` file: This file can be exported from ETS and imported into the integration settings.
|
|
2. Manual configuration: If you are not using Data Secure, you can manually input the required IP Secure credentials in the integration settings.
|
|
|
|
#### Data Secure
|
|
|
|
Data Secure credentials are always sourced from a `.knxkeys` file. You can import or update the Keyring file from the integrations settings.
|
|
|
|
{% important %}
|
|
|
|
Assign all secured group addresses that Home Assistant will use to either the interface's tunnel endpoint or a dummy device in ETS before exporting the Keyring file.
|
|
|
|
{% endimportant %}
|
|
|
|
When updating secure groups, ensure all participating devices, routers, and couplers applications are updated as well. After making changes, load the updated Keyring file into Home Assistant.
|
|
|
|
### Tunneling
|
|
|
|
Tunneling uses a KNX IP Interface to connect to the KNX bus. Most KNX IP Routers also support tunneling connections. This is the recommended connection type and is also used when selecting an "Automatic" connection in the integration setup.
|
|
|
|
For modern interfaces (supporting TCP or IP Secure) you can select a specific tunnel endpoint to be used. Make sure that Home Assistant is the only client connecting to this tunnel endpoint.
|
|
In ETS it is recommended to connect the group addresses you want to use to the tunnel endpoint that Home Assistant uses. For secure group addresses, this is mandatory.
|
|
|
|
If you use KNX IP Secure tunneling or Data Secure, export the Keyring file from ETS and import it in the KNX integration settings.
|
|
|
|

|
|
|
|
{% note %}
|
|
|
|
If you want Home Assistant to use a specific individual address, you can change the address of the used tunnel endpoint in ETS.
|
|
|
|
{% endnote %}
|
|
|
|
{% details "Manual IP Secure tunneling credentials" %}
|
|
|
|
If you opt for manual configuration of IP Secure tunneling, you will need the following:
|
|
|
|
1. User-ID: Use a User-ID of 2 or higher. (IDs 0 and 1 are reserved).
|
|
The first tunnel endpoint in ETS will typically use User-ID `2`, the second `3`, and so on.
|
|
2. User password.
|
|
3. Device authentication code (optional).
|
|
|
|

|
|
|
|
The following screenshot will show how you can find the device authentication code in ETS.
|
|
|
|

|
|
|
|
{% enddetails %}
|
|
|
|
### Routing
|
|
|
|
Routing communicates with KNXnet/IP routers via IP Multicast.
|
|
|
|
When using routing:
|
|
|
|
1. Add a dummy device in ETS at the same topology level as your routers.
|
|
2. Assign this dummy device the same individual address configured in the KNX integration setup.
|
|
3. Connect all group addresses that Home Assistant will use to the dummy device.
|
|
This ensures routers and couplers maintain updated filter tables and enables the use of secure group addresses in Home Assistant.
|
|
4. If you use KNX IP Secure routing or Data Secure groups, export the Keyring file from ETS and import it in the KNX integration settings.
|
|
|
|

|
|
|
|
{% details "Manual IP Secure routing credentials" %}
|
|
|
|
If you opt for manual configuration of IP Secure routing, you will need the backbone key. This can be found in the ETS "Project Security" report.
|
|
|
|

|
|
|
|
{% enddetails %}
|
|
|
|
## Data updates
|
|
|
|
This integration uses the KNX/IP protocol to receive telegrams live as they appear on the bus. When the integration is loaded, it actively requests data needed to initialize the configured entities. See [Group Addresses](#group-addresses) for more details.
|
|
|
|
States of diagnostic entities of the "KNX Interface" device are {% term polling polled %} every 10 seconds.
|
|
|
|
## Triggers
|
|
|
|
The KNX integration provides its own trigger platform which can be used in automations.
|
|
|
|
### Telegram trigger
|
|
|
|
The `knx.telegram` trigger can be used to trigger automations on incoming or outgoing KNX telegrams.
|
|
|
|
{% note %}
|
|
This trigger is also provided as a device trigger by the `KNX Interface` device. It supports setting the options in the automation builder UI, but doesn't support setting a specific <abbr title="data point type">DPT</abbr> (`type`) to decode the payload as it always relies on project data.
|
|
{% endnote %}
|
|
|
|
{% configuration %}
|
|
destination:
|
|
description: A group address or a list of group addresses the trigger should listen on. If not set, or an empty list, the trigger will listen on all group addresses.
|
|
type: [string, list]
|
|
required: false
|
|
type:
|
|
description: If set, the payload will be decoded as given DPT in the trigger data. When not set, the DPT is sourced from project data. KNX sensor types are valid values [KNX Sensor](#sensor) (e.g., "2byte_float" or "percent").
|
|
type: [string, integer]
|
|
required: false
|
|
group_value_write:
|
|
description: If set to `false`, the trigger will not fire on GroupValueWrite telegrams.
|
|
type: boolean
|
|
default: true
|
|
required: false
|
|
group_value_response:
|
|
description: If set to `false`, the trigger will not fire on GroupValueResponse telegrams.
|
|
type: boolean
|
|
default: true
|
|
required: false
|
|
group_value_read:
|
|
description: If set to `false`, the trigger will not fire on GroupValueRead telegrams.
|
|
type: boolean
|
|
default: true
|
|
required: false
|
|
incoming:
|
|
description: If set to `false`, the trigger will not fire on incoming telegrams.
|
|
type: boolean
|
|
default: true
|
|
required: false
|
|
outgoing:
|
|
description: If set to `false`, the trigger will not fire on outgoing telegrams.
|
|
type: boolean
|
|
default: true
|
|
required: false
|
|
{% endconfiguration %}
|
|
|
|
#### Available trigger data
|
|
|
|
In addition to the [standard automation trigger data](/docs/automation/templating/#all), the `knx.telegram` trigger platform has additional trigger data available for use.
|
|
|
|
- `trigger.destination` Destination group address
|
|
- `trigger.destination_name` Destination group address name
|
|
- `trigger.direction` Telegram direction
|
|
- `trigger.dpt_main` Destination group address main datapoint type number
|
|
- `trigger.dpt_sub` Destination group address sub datapoint type number
|
|
- `trigger.dpt_name` DPT value type name - see Sensor value types
|
|
- `trigger.payload` Raw telegram payload. DPT 1, 2, and 3 yield integers 0..255; other DPT yield lists of integers 0..255
|
|
- `trigger.source` Source individual address
|
|
- `trigger.source_name` Source name
|
|
- `trigger.telegramtype` APCI type of telegram
|
|
- `trigger.timestamp` Timestamp
|
|
- `trigger.unit` Unit according to group address DPT
|
|
- `trigger.value` Decoded telegram payload according to DPT
|
|
|
|
| Template variable | Type | Project data required |
|
|
|----------------------------|-----------------------------|-----------------------|
|
|
| `trigger.destination` | string | no |
|
|
| `trigger.destination_name` | string | yes |
|
|
| `trigger.direction` | string | no |
|
|
| `trigger.dpt_main` | integer | yes |
|
|
| `trigger.dpt_sub` | integer | yes |
|
|
| `trigger.dpt_name` | string | yes |
|
|
| `trigger.payload` | integer or list of integers | no |
|
|
| `trigger.source` | string | no |
|
|
| `trigger.source_name` | string | yes |
|
|
| `trigger.telegramtype` | string | no |
|
|
| `trigger.timestamp` | timestamp | no |
|
|
| `trigger.unit` | string | yes |
|
|
| `trigger.value` | any | yes |
|
|
|
|
For values that require project data: if the information was not found, or if no project file was provided, data will be set to `null`.
|
|
|
|
#### Examples
|
|
|
|
Example automation configuration
|
|
|
|
{% raw %}
|
|
|
|
```yaml
|
|
- alias: "Single group address trigger"
|
|
triggers:
|
|
- trigger: knx.telegram
|
|
destination: 1/2/3
|
|
group_value_read: false
|
|
outgoing: false
|
|
conditions: "{{ trigger.value == 0 }}"
|
|
actions: []
|
|
```
|
|
|
|
{% endraw %}
|
|
|
|
Example trigger data
|
|
|
|
```yaml
|
|
variables:
|
|
triggers:
|
|
id: "0"
|
|
idx: "0"
|
|
alias: null
|
|
destination: 1/2/3
|
|
destination_name: Light office brightness
|
|
direction: Incoming
|
|
dpt_main: 5
|
|
dpt_sub: 1
|
|
dpt_name: percent
|
|
payload:
|
|
- 255
|
|
source: 1.0.51
|
|
source_name: Dimming actuator 1
|
|
telegramtype: GroupValueWrite
|
|
timestamp: "2024-01-09T10:38:28.447487+01:00"
|
|
unit: "%"
|
|
value: 100
|
|
context: null
|
|
```
|
|
|
|
## Events
|
|
|
|
{% tip %}
|
|
For automation triggers, it is recommended to use the [knx.telegram](#telegram-trigger) trigger instead of `knx_event`.
|
|
{% endtip %}
|
|
|
|
```yaml
|
|
knx:
|
|
event:
|
|
- address:
|
|
- "0/1/*"
|
|
- address:
|
|
- "1/2/*"
|
|
- "1/3/2-4"
|
|
type: "2byte_unsigned"
|
|
- address:
|
|
- "3/4/5"
|
|
type: "2byte_float"
|
|
```
|
|
|
|
{% configuration %}
|
|
address:
|
|
description: Defines a list of patterns for matching KNX group addresses. Telegrams with destination addresses matching one of the patterns are sent to the Home Assistant event bus as `knx_event`.
|
|
required: true
|
|
type: [list, string]
|
|
type:
|
|
description: Telegram payloads in `knx_event` events will be decoded using the configured type (DPT) for the addresses in the same block. The decoded value will be written to the event data `value` key. If not configured the `value` key will be `None` - the `data` key will still hold the raw payload (use this for DPT 1, 2, 3). All sensor types are valid types - see [KNX Sensor](#sensor) (e.g., "2byte_float" or "1byte_signed").
|
|
type: [string, integer]
|
|
required: false
|
|
{% endconfiguration %}
|
|
|
|
Every telegram that matches an address pattern with its destination field will be announced on the event bus as a `knx_event` event containing data attributes
|
|
|
|
- `data` contains the raw payload data (e.g., 1 or "[12, 55]").
|
|
- `destination` the KNX group address the telegram is sent to as string (e.g., "1/2/3").
|
|
- `direction` the direction of the telegram as string ("Incoming" / "Outgoing").
|
|
- `source` the KNX individual address of the sender as string (e.g., "1.2.3").
|
|
- `telegramtype` the APCI service of the telegram. "GroupValueWrite", "GroupValueRead" or "GroupValueResponse" generate a knx_event.
|
|
- `value` contains the decoded payload value if `type` is configured for the address. Will be `None` for "GroupValueRead" telegrams.
|
|
|
|
## Actions
|
|
|
|
In order to directly interact with the KNX bus, you can use the following actions:
|
|
|
|
### Send
|
|
|
|
```txt
|
|
Domain: knx
|
|
Action: send
|
|
Data: {"address": "1/0/15", "payload": 0, "type": "temperature"}
|
|
```
|
|
|
|
{% configuration %}
|
|
address:
|
|
description: KNX group address.
|
|
type: string
|
|
payload:
|
|
description: Payload to send to the bus. When `type` is not set, raw bytes are sent. Integers are then treated as DPT 1/2/3 payloads. For DPTs > 6 bits send a list. Each value represents 1 octet (0-255). Pad with 0 to DPT byte length.
|
|
type: [integer, list]
|
|
type:
|
|
description: If set, the payload will not be sent as raw bytes, but encoded as given DPT. KNX sensor types are valid values - see table in [KNX Sensor](#sensor).
|
|
type: [string, integer, float]
|
|
response:
|
|
description: If set to `true`, the telegram will be sent as a `GroupValueResponse` instead of a `GroupValueWrite`.
|
|
type: boolean
|
|
default: false
|
|
{% endconfiguration %}
|
|
|
|
{% raw %}
|
|
|
|
```yaml
|
|
# Example script to send a fixed value and the state of an entity
|
|
alias: "My Script"
|
|
sequence:
|
|
- action: knx.send
|
|
data:
|
|
address: 1/1/1
|
|
type: percent
|
|
payload: 50
|
|
response: false
|
|
- action: knx.send
|
|
data:
|
|
address: 1/1/1
|
|
payload: [128] # 50 % as 1-byte raw value
|
|
response: false
|
|
- action: knx.send
|
|
data:
|
|
address: 3/3/3
|
|
type: temperature
|
|
payload: "{{ states('sensor.dew_point') }}"
|
|
response: false
|
|
```
|
|
|
|
{% endraw %}
|
|
|
|
### Read
|
|
|
|
You can use the `homeassistant.update_entity` action call to issue GroupValueRead requests for all `*state_address` of an entity.
|
|
To manually send GroupValueRead requests, use the `knx.read` action. The response can be used in automations by the `knx.telegram` trigger and it will be processed in KNX entities.
|
|
|
|
```txt
|
|
Domain: knx
|
|
Action: read
|
|
Data: {"address": "1/0/15"}
|
|
```
|
|
|
|
{% configuration %}
|
|
address:
|
|
description: Group address(es) to send read request to. Lists will read multiple group addresses.
|
|
type: [string, list]
|
|
{% endconfiguration %}
|
|
|
|
```yaml
|
|
# Example automation to update a cover position after 10 seconds of movement initiation
|
|
automation:
|
|
- triggers:
|
|
- trigger: knx.telegram
|
|
# Cover move trigger
|
|
destination: "0/4/20"
|
|
actions:
|
|
- delay: 0:0:10
|
|
- action: knx.read
|
|
data:
|
|
# Cover position address
|
|
address: "0/4/21"
|
|
|
|
- triggers:
|
|
- trigger: homeassistant
|
|
event: start
|
|
actions:
|
|
# Register the group address to trigger a knx_event
|
|
- action: knx.event_register
|
|
data:
|
|
# Cover move trigger
|
|
address: "0/4/20"
|
|
```
|
|
|
|
### Register event
|
|
|
|
The `knx.event_register` action can be used to register (or unregister) group addresses to fire `knx_event` Events. Events for group addresses configured in the `event` key in {% term "`configuration.yaml`" %} cannot be unregistered. See [knx_event](#events)
|
|
|
|
{% configuration %}
|
|
address:
|
|
description: Group address that shall be added or removed.
|
|
required: true
|
|
type: [string, list]
|
|
remove:
|
|
description: If `true` the group address will be removed.
|
|
required: false
|
|
type: boolean
|
|
default: false
|
|
type:
|
|
description: If set, the payload will be decoded as given DPT in the event data `value` key. KNX sensor types are valid values [KNX Sensor](#sensor) (e.g., "2byte_float" or "1byte_signed").
|
|
type: [string, integer]
|
|
required: false
|
|
{% endconfiguration %}
|
|
|
|
### Register exposure
|
|
|
|
The `knx.exposure_register` action can be used to register (or unregister) exposures to the KNX bus. Exposures defined in {% term "`configuration.yaml`" %} can not be unregistered. Per address only one exposure can be registered. See [expose](#exposing-entity-states-entity-attributes-or-time-to-knx-bus)
|
|
|
|
{% configuration %}
|
|
remove:
|
|
description: In addition to the configuration variables of [expose](#exposing-entity-states-entity-attributes-or-time-to-knx-bus) `remove` set to `true` can be used to remove exposures. Only `address` is required for removal.
|
|
required: false
|
|
type: boolean
|
|
default: false
|
|
{% endconfiguration %}
|
|
|
|
## Exposing entity states, entity attributes or time to KNX bus
|
|
|
|
KNX integration is able to expose entity states or attributes to KNX bus. The integration will broadcast any change of the exposed value to the KNX bus and answer read requests to the specified group address.
|
|
It is also possible to expose the current time and date. These are sent to the bus every hour.
|
|
|
|
{% tip %}
|
|
Expose is only triggered on state changes. If you need periodical telegrams, use an automation with the `knx.send` action to send the value to the bus.
|
|
{% endtip %}
|
|
|
|
{% raw %}
|
|
|
|
```yaml
|
|
# Example configuration.yaml entry
|
|
knx:
|
|
expose:
|
|
# time and date exposures
|
|
- type: time
|
|
address: "0/0/1"
|
|
# entitiy exposures
|
|
- type: temperature
|
|
entity_id: sensor.owm_temperature
|
|
address: "0/0/2"
|
|
cooldown: 600
|
|
- type: string
|
|
address: "0/6/4"
|
|
entity_id: sensor.owm_weather
|
|
- type: binary
|
|
entity_id: binary_sensor.kitchen_window
|
|
address: "0/6/5"
|
|
- type: binary
|
|
entity_id: light.office
|
|
address: "0/3/0"
|
|
default: false
|
|
- type: percentU8
|
|
entity_id: light.office
|
|
attribute: brightness
|
|
default: 0
|
|
address: "0/3/1"
|
|
- type: percent
|
|
address: "1/1/1"
|
|
entity_id: cover.office
|
|
attribute: current_position
|
|
value_template: "{{ 100 - value }}" # invert the value
|
|
- type: percent
|
|
address: "2/2/2"
|
|
entity_id: media_player.kitchen
|
|
attribute: volume_level
|
|
value_template: "{{ value * 100 }}" # convert from 0..1 to percent
|
|
```
|
|
|
|
{% endraw %}
|
|
|
|
{% configuration %}
|
|
address:
|
|
description: Group address state or attribute updates will be sent to. GroupValueRead requests will be answered.
|
|
type: string
|
|
required: true
|
|
type:
|
|
description: Type of the exposed value. Either `binary`, `time` *DPT 10.001*, `date` *DPT 11.001*, `datetime` *DPT 19.001* or any supported type of [KNX Sensor](#sensor) (e.g., "temperature" or "humidity").
|
|
type: [string, integer]
|
|
required: true
|
|
entity_id:
|
|
description: Entity ID to be exposed. Not needed for types `time`, `date` and `datetime`.
|
|
type: string
|
|
required: false
|
|
attribute:
|
|
description: Attribute of the entity that shall be sent to the KNX bus. If not set (or `None`) the state will be sent.
|
|
For example for a light the state is either "on" or "off". With `attribute` you can expose its "brightness".
|
|
type: string
|
|
required: false
|
|
default:
|
|
description: Default value to send to the bus if the state or attribute value is `None`.
|
|
For example a light with state "off" has no brightness attribute so a default value of `0` could be used.
|
|
If not set (or `None`) no value would be sent to the bus and a GroupReadRequest to the address would return the last known value.
|
|
type: [boolean, string, integer, float]
|
|
default: None
|
|
required: false
|
|
value_template:
|
|
description: A template to process the value before sending it to the KNX bus. The template has access to the entity state or attribute value as `value`.
|
|
required: false
|
|
default: None
|
|
type: template
|
|
cooldown:
|
|
description: Minimum time in seconds between two sent telegrams. This can be used to avoid flooding the KNX bus when exposing frequently changing states. If the state changes multiple times within the cooldown period the most recent value will be sent.
|
|
type: float
|
|
default: 0
|
|
required: false
|
|
respond_to_read:
|
|
description: Respond to GroupValueRead telegrams received to the configured `address`.
|
|
required: false
|
|
type: boolean
|
|
default: true
|
|
{% endconfiguration %}
|
|
|
|
## Binary sensor
|
|
|
|
The KNX binary sensor platform allows you to monitor [KNX](https://www.knx.org/) binary sensors like window/door contacts, motion detectors, alarms, etc.
|
|
|
|
{% note %}
|
|
|
|
Binary sensors are read-only entities. To write to the KNX bus, configure a [KNX Switch entity](#switch) or use the [`knx.send` action](#send).
|
|
|
|
{% endnote %}
|
|
|
|
Binary sensor entities can be created from the frontend in the KNX panel or via YAML.
|
|
|
|
<a name="configuration-binary-sensor-yaml"></a>
|
|
{% details "Configuration of KNX binary sensor entities via YAML" %}
|
|
|
|
```yaml
|
|
knx:
|
|
binary_sensor:
|
|
- name: "Sensor 1"
|
|
state_address: "6/0/2"
|
|
```
|
|
|
|
{% configuration %}
|
|
state_address:
|
|
description: KNX group address of the binary sensor. *DPT 1*
|
|
required: true
|
|
type: [string, list]
|
|
name:
|
|
description: A name for this device used within Home Assistant.
|
|
required: false
|
|
type: string
|
|
sync_state:
|
|
description: Actively read the value from the bus. The maximum time interval (`<minutes>`) is 1440. The following values are valid
|
|
|
|
- `true` equivalent to "expire 60" (default)
|
|
|
|
- `false` no GroupValueRead telegrams will be sent to the bus
|
|
|
|
- `every <minutes>` to update it regularly every \<minutes\>
|
|
|
|
- `expire <minutes>` to read the state from the KNX bus when no telegram was received for \<minutes\>
|
|
|
|
- `<minutes>` equivalent to "expire \<minutes\>"
|
|
|
|
- `init` to just initialize the state on startup
|
|
|
|
required: false
|
|
type: [boolean, string, integer]
|
|
default: true
|
|
device_class:
|
|
description: Sets the [class of the device](/integrations/binary_sensor/), changing the device state and icon that is displayed on the frontend.
|
|
required: false
|
|
type: string
|
|
reset_after:
|
|
description: Reset back to "off" state after specified time in seconds.
|
|
required: false
|
|
type: float
|
|
invert:
|
|
description: Invert the telegrams payload before processing. This is applied before `context_timeout` or `reset_after` is evaluated.
|
|
required: false
|
|
type: boolean
|
|
default: false
|
|
ignore_internal_state:
|
|
description: Specifies if telegrams should ignore the internal state and always trigger a Home Assistant state update.
|
|
required: false
|
|
type: boolean
|
|
default: false
|
|
context_timeout:
|
|
description: The time in seconds between multiple identical telegram payloads would count towards an internal counter that can be used for automations. This setting defines the time window that a second telegram would count toward a single state change. So if you set this 3.0 you can take up to 3 seconds in order to trigger the second button press, and a single press would take 3 seconds to trigger a Home Assistant state update. If this is set, `ignore_internal_state` will be set to `true` internally. Maximum value is 10.0.
|
|
required: false
|
|
type: float
|
|
default: None
|
|
entity_category:
|
|
description: The [category](https://developers.home-assistant.io/docs/core/entity#generic-properties) of the entity.
|
|
required: false
|
|
type: string
|
|
default: None
|
|
{% endconfiguration %}
|
|
|
|
{% enddetails %}
|
|
|
|
### Automation example
|
|
|
|
Let's pretend you have configured a binary sensor with the name `Livingroom Switch` and you want to toggle a light when the button was pressed once and another light when the button was pressed twice.
|
|
`context_timeout` has to be configured in order for this to work and the switch would have to send the same payloads on each press (`on` - `on` within the time window).
|
|
|
|
```yaml
|
|
automation:
|
|
- triggers:
|
|
- trigger: numeric_state
|
|
entity_id: binary_sensor.livingroom_switch
|
|
attribute: counter
|
|
above: 0
|
|
below: 2
|
|
actions:
|
|
- action: light.toggle
|
|
entity_id: light.livingroom_ceiling_lamp
|
|
- triggers:
|
|
- trigger: numeric_state
|
|
entity_id: binary_sensor.livingroom_switch
|
|
attribute: counter
|
|
above: 1
|
|
below: 3
|
|
actions:
|
|
- action: light.toggle
|
|
target:
|
|
entity_id:
|
|
- light.livingroom_floor_lamp
|
|
```
|
|
|
|
## Button
|
|
|
|
The KNX button platform allows to send concurrent predefined values via the frontend or an action. When a user presses the button, the assigned generic raw payload is sent to the KNX bus.
|
|
|
|
{% tip %}
|
|
Telegrams received on the KNX bus for the group address of a button are not reflected in a new button state. Use the `knx.telegram` trigger if you want to automate on a specific payload received on a group address.
|
|
{% endtip %}
|
|
|
|
```yaml
|
|
# Example configuration.yaml entry
|
|
knx:
|
|
button:
|
|
- name: "DPT 1 - True button"
|
|
address: "0/0/1"
|
|
- name: "100% button"
|
|
address: "0/0/2"
|
|
payload: 0xFF
|
|
payload_length: 1
|
|
- name: "Temperature button"
|
|
address: "0/0/3"
|
|
value: 21.5
|
|
type: temperature
|
|
```
|
|
|
|
{% important %}
|
|
When `type` is used `value` is required, `payload` is invalid.
|
|
When `payload_length` is used `value` is invalid.
|
|
{% endimportant %}
|
|
|
|
{% configuration %}
|
|
name:
|
|
description: A name for this device used within Home Assistant.
|
|
required: false
|
|
type: string
|
|
address:
|
|
description: Group address to send to.
|
|
required: true
|
|
type: string
|
|
payload:
|
|
description: The raw payload that shall be sent.
|
|
required: false
|
|
type: integer
|
|
default: 1
|
|
payload_length:
|
|
description: The length of the payload data in the telegram. Use `0` for DPT 1, 2 or 3.
|
|
required: false
|
|
type: integer
|
|
default: 0
|
|
value:
|
|
description: The value that shall be sent encoded by `type`.
|
|
required: false
|
|
type: [integer, float, string]
|
|
type:
|
|
description: A type from the [value types table](/integrations/knx/#value-types) to encode the configured `value`.
|
|
required: false
|
|
type: [string, integer]
|
|
entity_category:
|
|
description: The [category](https://developers.home-assistant.io/docs/core/entity#generic-properties) of the entity.
|
|
required: false
|
|
type: string
|
|
default: None
|
|
{% endconfiguration %}
|
|
|
|
## Climate
|
|
|
|
The KNX climate platform is used as an interface to KNX thermostats and room controllers.
|
|
|
|
To use your KNX thermostats in your installation, add the following lines to your top level [KNX Integration](/integrations/knx) configuration key in {% term "`configuration.yaml`" %}:
|
|
|
|
```yaml
|
|
# Example configuration.yaml entry
|
|
knx:
|
|
climate:
|
|
- name: "Kitchen"
|
|
temperature_address: "5/1/1"
|
|
setpoint_shift_address: "5/1/2"
|
|
setpoint_shift_state_address: "5/1/3"
|
|
target_temperature_state_address: "5/1/4"
|
|
operation_mode_address: "5/1/5"
|
|
operation_mode_state_address: "5/1/6"
|
|
```
|
|
|
|
Alternatively, if your device has dedicated binary group addresses for frost/night/comfort mode:
|
|
|
|
```yaml
|
|
# Example configuration.yaml entry
|
|
knx:
|
|
climate:
|
|
- name: "Kitchen"
|
|
temperature_address: "5/1/1"
|
|
setpoint_shift_address: "5/1/2"
|
|
setpoint_shift_state_address: "5/1/3"
|
|
target_temperature_state_address: "5/1/4"
|
|
operation_mode_frost_protection_address: "5/1/5"
|
|
operation_mode_night_address: "5/1/6"
|
|
operation_mode_comfort_address: "5/1/7"
|
|
operation_mode_state_address: "5/1/8"
|
|
```
|
|
|
|
If your device doesn't support setpoint_shift calculations (i.e., if you don't provide a `setpoint_shift_address` value) please set the `min_temp` and `max_temp`
|
|
attributes of the climate device to avoid issues with exceeding valid temperature values in the frontend. Please do also make sure to add the `target_temperature_address` to the configuration in this case.:
|
|
|
|
```yaml
|
|
# Example configuration.yaml entry
|
|
knx:
|
|
climate:
|
|
- name: "Kitchen"
|
|
temperature_address: "5/1/2"
|
|
target_temperature_address: "5/1/4"
|
|
target_temperature_state_address: "5/1/1"
|
|
operation_mode_frost_protection_address: "5/1/5"
|
|
operation_mode_night_address: "5/1/6"
|
|
operation_mode_comfort_address: "5/1/7"
|
|
operation_mode_state_address: "5/1/8"
|
|
operation_mode_standby_address: "5/1/9"
|
|
min_temp: 7.0
|
|
max_temp: 32.0
|
|
```
|
|
|
|
`setpoint_shift_mode` allows the two following DPTs to be used:
|
|
|
|
- DPT6010 (for 1 byte signed integer with scale factor)
|
|
- DPT9002 (for 2 byte float)
|
|
|
|
Example:
|
|
|
|
```yaml
|
|
# Example configuration.yaml entry
|
|
knx:
|
|
climate:
|
|
- name: "Kitchen"
|
|
temperature_address: "5/1/1"
|
|
setpoint_shift_address: "5/1/2"
|
|
setpoint_shift_state_address: "5/1/3"
|
|
setpoint_shift_mode: "DPT9002"
|
|
target_temperature_state_address: "5/1/4"
|
|
operation_mode_address: "5/1/5"
|
|
operation_mode_state_address: "5/1/6"
|
|
```
|
|
|
|
`operation_mode_frost_protection_address` / `operation_mode_night_address` / `operation_mode_comfort_address` / `operation_mode_standby_address` are not necessary if `operation_mode_address` is specified.
|
|
|
|
The following values are valid for the `heat_cool_address` and the `heat_cool_state_address`:
|
|
|
|
- `0` (cooling)
|
|
- `1` (heating)
|
|
|
|
Supported HVAC modes for your KNX thermostats are found automatically. This can be overridden by using the `controller_modes` configuration variable. The following values are valid controller modes:
|
|
|
|
- `off`
|
|
- `auto`
|
|
- `heat`
|
|
- `cool`
|
|
- `fan_only`
|
|
- `dehumidification`
|
|
|
|
Supported preset modes for your KNX thermostats are found automatically. This can be overridden by using the `operation_modes` configuration variable. The following values are valid operation modes:
|
|
|
|
- `auto`
|
|
- `comfort`
|
|
- `standby`
|
|
- `economy`
|
|
- `building_protection`
|
|
|
|
{% configuration %}
|
|
name:
|
|
description: A name for this device used within Home Assistant.
|
|
required: false
|
|
default: KNX Climate
|
|
type: string
|
|
temperature_address:
|
|
description: KNX group address for reading current room temperature from KNX bus. *DPT 9.001*
|
|
required: true
|
|
type: [string, list]
|
|
temperature_step:
|
|
description: Defines the step size in Kelvin for each step of setpoint_shift (scale factor). For non setpoint-shift configurations this is used to set the step of temperature sliders in UI.
|
|
required: false
|
|
type: float
|
|
default: 0.1
|
|
target_temperature_address:
|
|
description: KNX group address for setting target temperature. *DPT 9.001*
|
|
required: false
|
|
type: [string, list]
|
|
target_temperature_state_address:
|
|
description: KNX group address for reading current target temperature from KNX bus. *DPT 9.001*
|
|
required: true
|
|
type: [string, list]
|
|
setpoint_shift_address:
|
|
description: KNX address for setpoint_shift. *DPT 6.010 or DPT 9.002 based on setpoint_shift_mode*
|
|
required: false
|
|
type: [string, list]
|
|
setpoint_shift_state_address:
|
|
description: KNX address for reading setpoint_shift. *DPT 6.010 or DPT 9.002 based on setpoint_shift_mode*
|
|
required: false
|
|
type: [string, list]
|
|
setpoint_shift_mode:
|
|
description: Defines the internal device DPT used. Either 'DPT6010', 'DPT9002' or None. When `None` or omitted the DPT is auto-assigned from the first incoming telegram.
|
|
required: false
|
|
type: string
|
|
default: None
|
|
setpoint_shift_min:
|
|
description: Minimum value of setpoint shift.
|
|
required: false
|
|
default: -6
|
|
type: float
|
|
setpoint_shift_max:
|
|
description: Maximum value of setpoint shift.
|
|
required: false
|
|
default: 6
|
|
type: float
|
|
active_state_address:
|
|
description: KNX address for reading current activity. `0` is idle, `1` is active. *DPT 1*
|
|
required: false
|
|
type: [string, list]
|
|
command_value_state_address:
|
|
description: KNX address for reading current command value in percent. `0` sets the climate entity to idle if `active_state_address` is not set. *DPT 5.001*
|
|
required: false
|
|
type: [string, list]
|
|
humidity_state_address:
|
|
description: KNX address for reading current humidity. *DPT 9.007*
|
|
required: false
|
|
type: [string, list]
|
|
operation_mode_address:
|
|
description: KNX address for setting operation mode (auto / building protection / economy / standby / comfort). *DPT 20.102*
|
|
required: false
|
|
type: [string, list]
|
|
operation_mode_state_address:
|
|
description: KNX address for reading operation mode. *DPT 20.102*
|
|
required: false
|
|
type: [string, list]
|
|
controller_status_address:
|
|
description: KNX address for HVAC controller status (in accordance with KNX AN 097/07 rev 3).
|
|
required: false
|
|
type: [string, list]
|
|
controller_status_state_address:
|
|
description: KNX address for reading HVAC controller status.
|
|
required: false
|
|
type: [string, list]
|
|
controller_mode_address:
|
|
description: KNX address for setting HVAC controller modes. *DPT 20.105*
|
|
required: false
|
|
type: [string, list]
|
|
controller_mode_state_address:
|
|
description: KNX address for reading HVAC control mode. *DPT 20.105*
|
|
required: false
|
|
type: [string, list]
|
|
heat_cool_address:
|
|
description: KNX address for switching between heat/cool mode. *DPT 1.100*
|
|
required: false
|
|
type: [string, list]
|
|
heat_cool_state_address:
|
|
description: KNX address for reading heat/cool mode. *DPT 1.100*
|
|
required: false
|
|
type: [string, list]
|
|
operation_mode_frost_protection_address:
|
|
description: KNX address for switching on/off frost/heat protection mode. *DPT 1*
|
|
required: false
|
|
type: [string, list]
|
|
operation_mode_night_address:
|
|
description: KNX address for switching on/off economy mode. *DPT 1*
|
|
required: false
|
|
type: [string, list]
|
|
operation_mode_comfort_address:
|
|
description: KNX address for switching on/off comfort mode. *DPT 1*
|
|
required: false
|
|
type: [string, list]
|
|
operation_mode_standby_address:
|
|
description: KNX address for switching on/off standby mode. *DPT 1*
|
|
required: false
|
|
type: [string, list]
|
|
operation_modes:
|
|
description: Overrides the supported operation modes. Provide the supported `preset_modes` value for your device.
|
|
required: false
|
|
type: list
|
|
controller_modes:
|
|
description: Overrides the supported controller modes. Provide the supported `hvac_modes` value for your device.
|
|
required: false
|
|
type: list
|
|
default_controller_mode:
|
|
description: Overrides the default controller mode. Any Home Assistant `hvac_mode` can be configured. This can, for example, be set to "cool" for cooling-only devices.
|
|
required: false
|
|
default: "heat"
|
|
type: string
|
|
on_off_address:
|
|
description: KNX address for switching the climate device on/off. *DPT 1*
|
|
required: false
|
|
type: [string, list]
|
|
on_off_invert:
|
|
description: Value for switching the climate device on/off is inverted.
|
|
required: false
|
|
default: false
|
|
type: boolean
|
|
on_off_state_address:
|
|
description: KNX address for gathering the current state (on/off) of the climate device. *DPT 1*
|
|
required: false
|
|
type: [string, list]
|
|
min_temp:
|
|
description: Override the minimum temperature.
|
|
required: false
|
|
type: float
|
|
max_temp:
|
|
description: Override the maximum temperature.
|
|
required: false
|
|
type: float
|
|
fan_speed_address:
|
|
description: KNX group address for setting the percentage or step of the fan. *DPT 5.001* or *DPT 5.010*
|
|
required: false
|
|
type: [string, list]
|
|
fan_speed_state_address:
|
|
description: KNX group address for retrieving the percentage or step of the fan. *DPT 5.001* or *DPT 5.010*
|
|
required: false
|
|
type: [string, list]
|
|
fan_max_step:
|
|
description: The maximum amount of steps for the fan.
|
|
required: false
|
|
type: integer
|
|
default: 3
|
|
fan_speed_mode:
|
|
description: Fan speed group address data type. `percent` for *DPT 5.001* and `step` for *DPT 5.010*.
|
|
required: false
|
|
type: string
|
|
default: percent
|
|
fan_zero_mode:
|
|
description: The fan mode for the zero speed, either `off` or `auto`. This affects the fan modes displayed in the UI.
|
|
required: false
|
|
type: string
|
|
default: "off"
|
|
swing_address:
|
|
description: KNX address for turning the (vertical) swing on/off. *DPT 1*
|
|
required: false
|
|
type: [string, list]
|
|
swing_state_address:
|
|
description: KNX address for gathering the current state (on/off) of the (vertical) swing. *DPT 1*
|
|
required: false
|
|
type: [string, list]
|
|
swing_horizontal_address:
|
|
description: KNX address for turning the horizontal swing on/off. *DPT 1*
|
|
required: false
|
|
type: [string, list]
|
|
swing_horizontal_state_address:
|
|
description: KNX address for gathering the current state (on/off) of the horizontal swing. *DPT 1*
|
|
required: false
|
|
type: [string, list]
|
|
entity_category:
|
|
description: The [category](https://developers.home-assistant.io/docs/core/entity#generic-properties) of the entity.
|
|
required: false
|
|
type: string
|
|
default: None
|
|
{% endconfiguration %}
|
|
|
|
## Cover
|
|
|
|
The KNX cover platform is used as an interface to KNX covers.
|
|
|
|
{% note %}
|
|
Unlike most KNX devices, Home Assistant defines 0% as closed and 100% as fully open in regards to covers. The corresponding value inversion is done internally by the KNX integration.
|
|
|
|
Home Assistant will, by default, `close` a cover by moving it in the `DOWN` direction in the KNX nomenclature, and `open` a cover by moving it in the `UP` direction.
|
|
{% endnote %}
|
|
|
|
Cover entities can be created from the frontend in the KNX panel or via YAML.
|
|
|
|
<a name="configuration-cover-yaml"></a>
|
|
{% details "Configuration of KNX cover entities via YAML" %}
|
|
|
|
To use your KNX covers in your installation, add the following lines to your top level [KNX Integration](/integrations/knx) configuration key in your {% term "`configuration.yaml`" %}:
|
|
|
|
```yaml
|
|
# Example configuration.yaml entry
|
|
knx:
|
|
cover:
|
|
- name: "Kitchen shutter"
|
|
move_long_address: "3/0/0"
|
|
stop_address: "3/0/4"
|
|
position_address: "3/0/3"
|
|
position_state_address: "3/0/2"
|
|
travelling_time_down: 51
|
|
travelling_time_up: 61
|
|
- name: "Bedroom blinds"
|
|
move_long_address: "3/1/1"
|
|
move_short_address: "3/1/4"
|
|
position_address: "3/1/3"
|
|
position_state_address: "3/1/2"
|
|
angle_address: "3/1/5"
|
|
angle_state_address: "3/1/6"
|
|
travelling_time_down: 40
|
|
travelling_time_up: 40
|
|
```
|
|
|
|
{% configuration %}
|
|
name:
|
|
description: A name for this device used within Home Assistant.
|
|
required: false
|
|
default: KNX Cover
|
|
type: string
|
|
move_long_address:
|
|
description: KNX group address for moving the cover full up or down. *DPT 1*
|
|
required: false
|
|
type: [string, list]
|
|
move_short_address:
|
|
description: KNX group address for moving the cover stepwise up or down. Used by some covers also as the means to stop the cover. Stepwise moves are only mapped to tilt angle functions in Home Assistant, as no stepwise move of cover position is generally supported by the architecture. If tilt angle is not supported, prefer the use of a `stop_address`. *DPT 1*
|
|
required: false
|
|
type: [string, list]
|
|
stop_address:
|
|
description: KNX group address for stopping the current movement of the cover. *DPT 1*
|
|
required: false
|
|
type: [string, list]
|
|
position_address:
|
|
description: KNX group address for moving the cover to the dedicated position. *DPT 5.001*
|
|
required: false
|
|
type: [string, list]
|
|
position_state_address:
|
|
description: Separate KNX group address for requesting the current position of the cover. *DPT 5.001*
|
|
required: false
|
|
type: [string, list]
|
|
angle_address:
|
|
description: KNX group address for tilting the cover to the dedicated angle. *DPT 5.001*
|
|
required: false
|
|
type: [string, list]
|
|
angle_state_address:
|
|
description: Separate KNX group address for requesting the current tilt angle of the cover. *DPT 5.001*
|
|
required: false
|
|
type: [string, list]
|
|
travelling_time_down:
|
|
description: Time cover needs to travel down in seconds. Needed to calculate the intermediate positions of cover while traveling.
|
|
required: false
|
|
default: 25
|
|
type: integer
|
|
travelling_time_up:
|
|
description: Time cover needs to travel up in seconds. Needed to calculate the intermediate positions of cover while traveling.
|
|
required: false
|
|
default: 25
|
|
type: integer
|
|
invert_updown:
|
|
description: Set this to `true` to invert the up/down commands from/to your KNX actuator. Default is to consider `UP` (0) as opening of a cover and `DOWN` (1) as closing of a cover.
|
|
required: false
|
|
default: false
|
|
type: boolean
|
|
invert_position:
|
|
description: Set this to `true` if your actuator reports fully down position as 0% in KNX.
|
|
required: false
|
|
default: false
|
|
type: boolean
|
|
invert_angle:
|
|
description: Set this to `true` if your actuator reports fully closed tilt as 0% in KNX.
|
|
required: false
|
|
default: false
|
|
type: boolean
|
|
device_class:
|
|
description: Sets the [class of the device](/integrations/cover/), changing the device state and icon that is displayed on the frontend.
|
|
required: false
|
|
type: string
|
|
entity_category:
|
|
description: The [category](https://developers.home-assistant.io/docs/core/entity#generic-properties) of the entity.
|
|
required: false
|
|
type: string
|
|
default: None
|
|
{% endconfiguration %}
|
|
|
|
{% enddetails %}
|
|
|
|
## Date
|
|
|
|
The KNX date platform allows to send date values to the KNX bus and update its state from received telegrams. It can optionally respond to read requests from the KNX bus.
|
|
|
|
{% note %}
|
|
Date entities without a `state_address` will restore their last known state after Home Assistant was restarted.
|
|
|
|
Dates that have a `state_address` configured request their current state from the KNX bus.
|
|
{% endnote %}
|
|
|
|
{% note %}
|
|
DPT 11.001 covers the range 1990 to 2089. Year values outside of this range are not allowed.
|
|
{% endnote %}
|
|
|
|
```yaml
|
|
# Example configuration.yaml entry
|
|
knx:
|
|
date:
|
|
- name: "Date"
|
|
address: "0/0/2"
|
|
state_address: "0/0/2"
|
|
```
|
|
|
|
{% configuration %}
|
|
name:
|
|
description: A name for this device used within Home Assistant.
|
|
required: false
|
|
type: string
|
|
address:
|
|
description: The group address to which new values will be sent. *DPT 11.001*
|
|
required: true
|
|
type: [string, list]
|
|
state_address:
|
|
description: Group address for retrieving the state from the KNX bus. *DPT 11.001*
|
|
required: false
|
|
type: [string, list]
|
|
respond_to_read:
|
|
description: If `true`, the entity will respond to GroupValueRead telegrams received on the configured `address` by sending a GroupValueResponse to the same `address`. This is typically used when Home Assistant acts as the state provider for the KNX bus. In such cases, only `address` is configured, and `state_address` is not set. Read-requests to passive or state addresses don't trigger responses.
|
|
required: false
|
|
type: boolean
|
|
default: false
|
|
sync_state:
|
|
description: Actively read the value from the bus. The maximum time interval (`<minutes>`) is 1440. The following values are valid
|
|
|
|
- `true` equivalent to "expire 60" (default)
|
|
|
|
- `false` no GroupValueRead telegrams will be sent to the bus
|
|
|
|
- `every <minutes>` to update it regularly every \<minutes\>
|
|
|
|
- `expire <minutes>` to read the state from the KNX bus when no telegram was received for \<minutes\>
|
|
|
|
- `<minutes>` equivalent to "expire \<minutes\>"
|
|
|
|
- `init` to just initialize the state on startup
|
|
|
|
required: false
|
|
type: [boolean, string, integer]
|
|
default: true
|
|
entity_category:
|
|
description: The [category](https://developers.home-assistant.io/docs/core/entity#generic-properties) of the entity.
|
|
required: false
|
|
type: string
|
|
default: None
|
|
{% endconfiguration %}
|
|
|
|
## DateTime
|
|
|
|
The KNX datetime platform allows to send datetime values to the KNX bus and update its state from received telegrams. It can optionally respond to read requests from the KNX bus.
|
|
|
|
{% note %}
|
|
Date entities without a `state_address` will restore their last known state after Home Assistant was restarted.
|
|
|
|
DateTimes that have a `state_address` configured request their current state from the KNX bus.
|
|
{% endnote %}
|
|
|
|
{% note %}
|
|
System timezone is used as DPT 19.001 doesn't provide timezone information.
|
|
Year values outside of the range 1900 to 2155 are invalid.
|
|
{% endnote %}
|
|
|
|
```yaml
|
|
# Example configuration.yaml entry
|
|
knx:
|
|
datetime:
|
|
- name: "DateTime"
|
|
address: "0/0/3"
|
|
state_address: "0/0/4"
|
|
```
|
|
|
|
{% configuration %}
|
|
name:
|
|
description: A name for this device used within Home Assistant.
|
|
required: false
|
|
type: string
|
|
address:
|
|
description: The group address to which new values will be sent. *DPT 19.001*
|
|
required: true
|
|
type: [string, list]
|
|
state_address:
|
|
description: Group address for retrieving the state from the KNX bus. *DPT 19.001*
|
|
required: false
|
|
type: [string, list]
|
|
respond_to_read:
|
|
description: If `true`, the entity will respond to GroupValueRead telegrams received on the configured `address` by sending a GroupValueResponse to the same `address`. This is typically used when Home Assistant acts as the state provider for the KNX bus. In such cases, only `address` is configured, and `state_address` is not set. Read-requests to passive or state addresses don't trigger responses.
|
|
required: false
|
|
type: boolean
|
|
default: false
|
|
sync_state:
|
|
description: Actively read the value from the bus. The maximum time interval (`<minutes>`) is 1440. The following values are valid
|
|
|
|
- `true` equivalent to "expire 60" (default)
|
|
|
|
- `false` no GroupValueRead telegrams will be sent to the bus
|
|
|
|
- `every <minutes>` to update it regularly every \<minutes\>
|
|
|
|
- `expire <minutes>` to read the state from the KNX bus when no telegram was received for \<minutes\>
|
|
|
|
- `<minutes>` equivalent to "expire \<minutes\>"
|
|
|
|
- `init` to just initialize the state on startup
|
|
|
|
required: false
|
|
type: [boolean, string, integer]
|
|
default: true
|
|
entity_category:
|
|
description: The [category](https://developers.home-assistant.io/docs/core/entity#generic-properties) of the entity.
|
|
required: false
|
|
type: string
|
|
default: None
|
|
{% endconfiguration %}
|
|
|
|
## Fan
|
|
|
|
The KNX fan integration is used to control KNX fans. Following control types are supported:
|
|
|
|
- Percentage controlled: Fans that set the percentage directly from 0-100%.
|
|
- Step controlled: Fans which have a fixed amount of steps to set. The integration will convert percentage to step automatically. The `max_step` attribute is set to the number of steps of the fan, not counting the `off`-step. Example: A fan supports the steps 0 to 3. To use this fan the `max_step` attribute has to be set to `3`. The integration will convert the percentage `66 %` to the step `2` when sending data to KNX.
|
|
|
|
To use your KNX fan in your installation, add the following lines to your top-level [KNX Integration](/integrations/knx) configuration key in your {% term "`configuration.yaml`" %}:
|
|
|
|
```yaml
|
|
# Example configuration.yaml entry
|
|
knx:
|
|
fan:
|
|
- name: "Ceiling fan"
|
|
address: "9/0/1"
|
|
state_address: "9/0/2"
|
|
```
|
|
|
|
{% configuration %}
|
|
name:
|
|
description: A name for this device used within Home Assistant.
|
|
required: false
|
|
type: string
|
|
address:
|
|
description: KNX group address for setting the percentage or step of the fan. *DPT 5.001* or *DPT 5.010*
|
|
required: true
|
|
type: [string, list]
|
|
state_address:
|
|
description: KNX group address for retrieving the percentage or step of the fan. *DPT 5.001* or *DPT 5.010*
|
|
required: false
|
|
type: [string, list]
|
|
oscillation_address:
|
|
description: KNX group address for switching the fan oscillation on or off. *DPT 1*
|
|
required: false
|
|
type: [string, list]
|
|
oscillation_state_address:
|
|
description: KNX group address for retrieving the state of the fan oscillation. *DPT 1*
|
|
required: false
|
|
type: [string, list]
|
|
max_step:
|
|
description: The maximum amount of steps for a step-controlled fan. If set, the integration will convert percentages to steps automatically.
|
|
required: false
|
|
type: integer
|
|
entity_category:
|
|
description: The [category](https://developers.home-assistant.io/docs/core/entity#generic-properties) of the entity.
|
|
required: false
|
|
type: string
|
|
default: None
|
|
{% endconfiguration %}
|
|
|
|
## Light
|
|
|
|
The KNX light integration is used as an interface to control KNX actuators for lighting applications such as:
|
|
|
|
- Switching actuators
|
|
- Dimming actuators
|
|
- LED controllers
|
|
- DALI gateways
|
|
|
|
Light entities can be created from the frontend in the KNX panel or via YAML.
|
|
|
|
<a name="configuration-light-yaml"></a>
|
|
{% details "Configuration of KNX light entities via YAML" %}
|
|
|
|
{% configuration %}
|
|
address:
|
|
description: KNX group address for switching the light on and off. *DPT 1.001*
|
|
required: true
|
|
type: [string, list]
|
|
state_address:
|
|
description: KNX group address for retrieving the switch state of the light. *DPT 1.001*
|
|
required: false
|
|
type: [string, list]
|
|
name:
|
|
description: A name for this device used within Home Assistant.
|
|
required: false
|
|
type: string
|
|
brightness_address:
|
|
description: KNX group address for setting the brightness of the light in percent (absolute dimming). *DPT 5.001*
|
|
required: false
|
|
type: [string, list]
|
|
brightness_state_address:
|
|
description: KNX group address for retrieving the brightness of the light in percent. *DPT 5.001*
|
|
required: false
|
|
type: [string, list]
|
|
color_address:
|
|
description: KNX group address for setting the RGB color of the light. *DPT 232.600*
|
|
required: false
|
|
type: [string, list]
|
|
color_state_address:
|
|
description: KNX group address for retrieving the RGB color of the light. *DPT 232.600*
|
|
required: false
|
|
type: [string, list]
|
|
rgbw_address:
|
|
description: KNX group address for setting the RGBW color of the light. *DPT 251.600*
|
|
required: false
|
|
type: [string, list]
|
|
rgbw_state_address:
|
|
description: KNX group address for retrieving the RGBW color of the light. *DPT 251.600*
|
|
required: false
|
|
type: [string, list]
|
|
hue_address:
|
|
description: KNX group address for setting the hue of the light color in degrees. *DPT 5.003*
|
|
required: false
|
|
type: [string, list]
|
|
hue_state_address:
|
|
description: KNX group address for retrieving the hue of the light color in degrees. *DPT 5.003*
|
|
required: false
|
|
type: [string, list]
|
|
saturation_address:
|
|
description: KNX group address for setting the saturation of the light color in percent. *DPT 5.001*
|
|
required: false
|
|
type: [string, list]
|
|
saturation_state_address:
|
|
description: KNX group address for retrieving the saturation of the light color in percent. *DPT 5.001*
|
|
required: false
|
|
type: [string, list]
|
|
xyy_address:
|
|
description: KNX group address for setting the xyY color of the light. *DPT 242.600*
|
|
required: false
|
|
type: [string, list]
|
|
xyy_state_address:
|
|
description: KNX group address for retrieving the xyY color of the light. *DPT 242.600*
|
|
required: false
|
|
type: [string, list]
|
|
individual_colors:
|
|
description: Used when the actuator only supports individual group addresses for colors. When `individual_colors` is used the root `address` key may be omitted.
|
|
required: false
|
|
type: map
|
|
keys:
|
|
red:
|
|
description: Group addresses for the red component.
|
|
type: map
|
|
required: true
|
|
keys:
|
|
address:
|
|
description: KNX group address to switch the red component. *DPT 1.001*
|
|
type: [string, list]
|
|
required: false
|
|
state_address:
|
|
description: KNX group address for the state of the red component. *DPT 1.001*
|
|
type: [string, list]
|
|
required: false
|
|
brightness_address:
|
|
description: KNX group address to set the brightness of the red component. *DPT 5.001*
|
|
type: [string, list]
|
|
required: true
|
|
brightness_state_address:
|
|
description: KNX group address for the current brightness of the red component. *DPT 5.001*
|
|
type: [string, list]
|
|
required: false
|
|
green:
|
|
description: Group addresses for the green component. Same keys available as for red component above.
|
|
type: map
|
|
required: true
|
|
blue:
|
|
description: Group addresses for the blue component. Same keys available as for red component above.
|
|
type: map
|
|
required: true
|
|
white:
|
|
description: Group addresses for the white component. Same keys available as for red component above.
|
|
type: map
|
|
required: false
|
|
color_temperature_address:
|
|
description: KNX group address for setting the color temperature of the light. *DPT 5.001, 7.600 or 9 based on color_temperature_mode*
|
|
required: false
|
|
type: [string, list]
|
|
color_temperature_state_address:
|
|
description: KNX group address for retrieving the color temperature of the light. *DPT 5.001, 7.600 or 9 based on color_temperature_mode*
|
|
required: false
|
|
type: [string, list]
|
|
color_temperature_mode:
|
|
description: Color temperature group address data type. `absolute` for color temperature in Kelvin (2 byte unsigned integer). *color_temperature_address -> DPT 7.600*. `absolute_float` for color temperature represented in 2 byte float. *color_temperature_address -> DPT 9*. `relative` color temperature in percent cold white (0% warmest; 100% coldest). *color_temperature_address -> DPT 5.001*
|
|
required: false
|
|
type: string
|
|
default: absolute
|
|
min_kelvin:
|
|
description: Warmest possible color temperature in Kelvin. Used in combination with `color_temperature_address`.
|
|
required: false
|
|
type: integer
|
|
default: 2700
|
|
max_kelvin:
|
|
description: Coldest possible color temperature in Kelvin. Used in combination with `color_temperature_address`.
|
|
required: false
|
|
type: integer
|
|
default: 6000
|
|
entity_category:
|
|
description: The [category](https://developers.home-assistant.io/docs/core/entity#generic-properties) of the entity.
|
|
required: false
|
|
type: string
|
|
default: None
|
|
{% endconfiguration %}
|
|
|
|
Many KNX devices can change their state internally without a message to the switch address on the KNX bus, e.g., if you configure a scene or a timer on a channel. The optional `state_address` can be used to inform Home Assistant about these state changes. If a KNX message is seen on the bus addressed to the given `state_address` (in most cases from the light actuator), it will overwrite the state of the object.
|
|
|
|
For switching/light actuators that are only controlled by a single group address and don't have dedicated state group objects you can set `state_address` to the same value as `address` if it is readable from the bus.
|
|
|
|
### YAML configuration examples
|
|
|
|
```yaml
|
|
knx:
|
|
light:
|
|
# dimmable light
|
|
# color mode: brightness
|
|
- name: "Dimmable light"
|
|
address: "1/0/9"
|
|
state_address: "1/1/9"
|
|
brightness_address: "1/2/9"
|
|
brightness_state_address: "1/3/9"
|
|
# XYY light
|
|
# color mode: xy
|
|
- name: "XYY light"
|
|
address: "1/0/9"
|
|
state_address: "1/1/9"
|
|
brightness_address: "1/2/9" # optional - if not set brightness will be sent over the xyy data point
|
|
brightness_state_address: "1/3/9"
|
|
xyy_address: "1/4/9"
|
|
xyy_state_address: "1/5/9"
|
|
# HS light
|
|
# color mode: hs
|
|
- name: "HS light"
|
|
address: "1/0/9"
|
|
state_address: "1/1/9"
|
|
brightness_address: "1/2/9" # required for HS
|
|
brightness_state_address: "1/3/9"
|
|
hue_address: "1/4/8"
|
|
hue_state_address: "1/5/8" # required for HS
|
|
saturation_address: "1/4/9"
|
|
saturation_state_address: "1/5/9" # required for HS
|
|
# RGB light
|
|
# color mode: rgb
|
|
- name: "RGB light"
|
|
address: "1/0/9"
|
|
state_address: "1/1/9"
|
|
brightness_address: "1/2/9" # optional for RGB lights
|
|
brightness_state_address: "1/3/9"
|
|
color_address: "1/4/9"
|
|
color_state_address: "1/5/9"
|
|
# RGBW light
|
|
# color mode: rgbw
|
|
- name: "RGBW light"
|
|
address: "0/4/83"
|
|
state_address: "0/4/84"
|
|
brightness_address: "0/4/85" # optional for RGBW lights
|
|
brightness_state_address: "0/4/86"
|
|
rgbw_address: "0/4/87"
|
|
rgbw_state_address: "0/4/88"
|
|
# RGB(W) individual object light
|
|
# color mode: rgb / rgbw
|
|
- name: "RGBW individual light"
|
|
address: "1/0/9" # optional for individual color lights
|
|
individual_colors:
|
|
red:
|
|
brightness_address: "0/4/61"
|
|
brightness_state_address: "0/5/61"
|
|
green:
|
|
brightness_address: "0/4/62"
|
|
brightness_state_address: "0/5/62"
|
|
blue:
|
|
brightness_address: "0/4/63"
|
|
brightness_state_address: "0/5/63"
|
|
white:
|
|
brightness_address: "0/4/64"
|
|
brightness_state_address: "0/5/64"
|
|
# tunable white light
|
|
# color mode: color_temp
|
|
- name: "TW light"
|
|
address: "1/0/21"
|
|
state_address: "1/1/21"
|
|
brightness_address: "1/2/21"
|
|
brightness_state_address: "1/3/21"
|
|
color_temperature_address: "1/4/21"
|
|
color_temperature_state_address: "1/5/21"
|
|
color_temperature_mode: absolute
|
|
min_kelvin: 2550
|
|
max_kelvin: 6200
|
|
# actuator without dedicated state group object
|
|
# color mode: onoff
|
|
- name: "Simple light"
|
|
address: "1/0/5"
|
|
state_address: "1/0/5"
|
|
```
|
|
|
|
{% enddetails %}
|
|
|
|
## Notify
|
|
|
|
The KNX notify platform allows you to send notifications to [KNX](https://www.knx.org/) devices as DPT16 strings.
|
|
|
|
```yaml
|
|
knx:
|
|
notify:
|
|
- name: "Alarm"
|
|
address: "5/1/10"
|
|
```
|
|
|
|
{% configuration %}
|
|
address:
|
|
description: KNX group address the notification will be sent to. *DPT 16*
|
|
required: true
|
|
type: [string, list]
|
|
name:
|
|
description: A name for this device used within Home Assistant.
|
|
required: false
|
|
type: string
|
|
type:
|
|
description: A DPT identifier representing a text value ("string" or "latin_1" - see [KNX Sensor](#sensor)) used to encode the notification.
|
|
required: false
|
|
default: "latin_1"
|
|
type: string
|
|
entity_category:
|
|
description: The [category](https://developers.home-assistant.io/docs/core/entity#generic-properties) of the entity.
|
|
required: false
|
|
type: string
|
|
default: None
|
|
{% endconfiguration %}
|
|
|
|
### Example action
|
|
|
|
```yaml
|
|
action: notify.send_message
|
|
data:
|
|
message: "Hello from HA!"
|
|
entity_id: notify.alarm
|
|
```
|
|
|
|
## Number
|
|
|
|
The KNX number platform allows to send generic numeric values to the KNX bus and update its state from received telegrams. It can optionally respond to read requests from the KNX bus.
|
|
|
|
{% note %}
|
|
Number entities without a `state_address` will restore their last known state after Home Assistant was restarted.
|
|
|
|
Numbers that have a `state_address` configured request their current state from the KNX bus.
|
|
{% endnote %}
|
|
|
|
```yaml
|
|
# Example configuration.yaml entry
|
|
knx:
|
|
number:
|
|
- name: "Duration"
|
|
address: "0/0/1"
|
|
type: time_period_sec
|
|
- name: "Volume"
|
|
address: "0/0/2"
|
|
state_address: "0/0/3"
|
|
type: percent
|
|
- name: "Temperature threshold"
|
|
address: "0/0/4"
|
|
respond_to_read: true
|
|
type: temperature
|
|
min: 20
|
|
max: 24.5
|
|
step: 0.1
|
|
mode: slider
|
|
```
|
|
|
|
{% configuration %}
|
|
name:
|
|
description: A name for this device used within Home Assistant.
|
|
required: false
|
|
type: string
|
|
address:
|
|
description: The group address to which new values will be sent.
|
|
required: true
|
|
type: [string, list]
|
|
state_address:
|
|
description: Group address for retrieving the state from the KNX bus.
|
|
required: false
|
|
type: [string, list]
|
|
type:
|
|
description: Any supported type of [KNX Sensor](#sensor) representing a numeric value (e.g., "percent" or "temperature").
|
|
required: true
|
|
type: [string, integer]
|
|
respond_to_read:
|
|
description: If `true`, the entity will respond to GroupValueRead telegrams received on the configured `address` by sending a GroupValueResponse to the same `address`. This is typically used when Home Assistant acts as the state provider for the KNX bus. In such cases, only `address` is configured, and `state_address` is not set. Read-requests to passive or state addresses don't trigger responses.
|
|
required: false
|
|
type: boolean
|
|
default: false
|
|
min:
|
|
description: Minimum value that can be sent. Defaults to the `type` DPT minimum value.
|
|
required: false
|
|
type: float
|
|
max:
|
|
description: Maximum value that can be sent. Defaults to the `type` DPT maximum value.
|
|
required: false
|
|
type: float
|
|
step:
|
|
description: Step value. Defaults to the step size defined for the DPT in the KNX specifications.
|
|
required: false
|
|
type: float
|
|
mode:
|
|
description: Specifies the mode used in the UI. `auto`, `box` or `slider` are valid.
|
|
required: false
|
|
type: string
|
|
default: auto
|
|
entity_category:
|
|
description: The [category](https://developers.home-assistant.io/docs/core/entity#generic-properties) of the entity.
|
|
required: false
|
|
type: string
|
|
default: None
|
|
{% endconfiguration %}
|
|
|
|
## Scene
|
|
|
|
The KNX scenes platform allows you to trigger [KNX](https://www.knx.org/) scenes. These entities are write-only.
|
|
|
|
```yaml
|
|
# Example configuration.yaml entry
|
|
knx:
|
|
scene:
|
|
- name: "Romantic"
|
|
address: 8/8/8
|
|
scene_number: 23
|
|
```
|
|
|
|
{% configuration %}
|
|
address:
|
|
description: KNX group address for the scene. *DPT 17.001*
|
|
required: true
|
|
type: [string, list]
|
|
scene_number:
|
|
description: KNX scene number to be activated (range 1..64 ).
|
|
required: true
|
|
type: integer
|
|
name:
|
|
description: A name for this device used within Home Assistant.
|
|
required: false
|
|
type: string
|
|
entity_category:
|
|
description: The [category](https://developers.home-assistant.io/docs/core/entity#generic-properties) of the entity.
|
|
required: false
|
|
type: string
|
|
default: None
|
|
{% endconfiguration %}
|
|
|
|
## Select
|
|
|
|
The KNX select platform allows the user to define a list of values that can be selected via the frontend and can be used within conditions of automation. When a user selects a new item, the assigned generic raw payload is sent to the KNX bus. A received telegram updates the state of the select entity. It can optionally respond to read requests from the KNX bus.
|
|
|
|
{% note %}
|
|
Select entities without a `state_address` will restore their last known state after Home Assistant was restarted.
|
|
|
|
Selects that have a `state_address` configured request their current state from the KNX bus.
|
|
{% endnote %}
|
|
|
|
```yaml
|
|
# Example configuration.yaml entry
|
|
knx:
|
|
select:
|
|
- name: "DPT 2 selector"
|
|
address: "0/0/1"
|
|
payload_length: 0
|
|
options:
|
|
- option: "No control"
|
|
payload: 0
|
|
- option: "Control On"
|
|
payload: 0b10
|
|
- option: "Control Off"
|
|
payload: 0b11
|
|
- name: "DHWMode"
|
|
address: "0/0/2"
|
|
state_address: "0/0/3"
|
|
payload_length: 1
|
|
options:
|
|
- option: "Auto"
|
|
payload: 0
|
|
- option: "LegioProtect"
|
|
payload: 1
|
|
- option: "Normal"
|
|
payload: 2
|
|
- option: "Reduced"
|
|
payload: 3
|
|
- option: "Off/FrostProtect"
|
|
payload: 4
|
|
```
|
|
|
|
{% configuration %}
|
|
name:
|
|
description: A name for this device used within Home Assistant.
|
|
required: false
|
|
type: string
|
|
address:
|
|
description: The group address to which new values will be sent.
|
|
required: true
|
|
type: [string, list]
|
|
state_address:
|
|
description: Group address for retrieving the state from the KNX bus.
|
|
required: false
|
|
type: [string, list]
|
|
payload_length:
|
|
description: The length of the payload expected for the DPT. Use `0` for DPT 1, 2 or 3.
|
|
required: true
|
|
type: integer
|
|
options:
|
|
description: List of options to choose from. Each `option` and `payload` have to be unique.
|
|
type: list
|
|
required: true
|
|
keys:
|
|
option:
|
|
description: The name of the option used to trigger the assigned `payload`.
|
|
required: true
|
|
type: string
|
|
payload:
|
|
description: The raw payload assigned to the `option`.
|
|
required: true
|
|
type: integer
|
|
respond_to_read:
|
|
description: If `true`, the entity will respond to GroupValueRead telegrams received on the configured `address` by sending a GroupValueResponse to the same `address`. This is typically used when Home Assistant acts as the state provider for the KNX bus. In such cases, only `address` is configured, and `state_address` is not set. Read-requests to passive or state addresses don't trigger responses.
|
|
required: false
|
|
type: boolean
|
|
default: false
|
|
sync_state:
|
|
description: Actively read the value from the bus. The maximum time interval (`<minutes>`) is 1440. The following values are valid
|
|
|
|
- `true` equivalent to "expire 60" (default)
|
|
|
|
- `false` no GroupValueRead telegrams will be sent to the bus
|
|
|
|
- `every <minutes>` to update it regularly every \<minutes\>
|
|
|
|
- `expire <minutes>` to read the state from the KNX bus when no telegram was received for \<minutes\>
|
|
|
|
- `<minutes>` equivalent to "expire \<minutes\>"
|
|
|
|
- `init` to just initialize the state on startup
|
|
|
|
required: false
|
|
type: [boolean, string, integer]
|
|
default: true
|
|
entity_category:
|
|
description: The [category](https://developers.home-assistant.io/docs/core/entity#generic-properties) of the entity.
|
|
required: false
|
|
type: string
|
|
default: None
|
|
{% endconfiguration %}
|
|
|
|
## Sensor
|
|
|
|
The KNX sensor platform allows you to monitor [KNX](https://www.knx.org/) sensors.
|
|
|
|
{% note %}
|
|
|
|
Sensors are read-only entities. To write to the KNX bus, configure a [KNX Number entity](#number) or use the [`knx.send` action](#send).
|
|
|
|
{% endnote %}
|
|
|
|
```yaml
|
|
# Example configuration.yaml entry
|
|
knx:
|
|
sensor:
|
|
- name: "Heating Valve 1"
|
|
state_address: "2/0/0"
|
|
type: percent
|
|
```
|
|
|
|
In order to actively read the sensor data from the bus every 30 minutes you can add the following lines to your {% term "`configuration.yaml`" %}:
|
|
|
|
```yaml
|
|
# Example configuration.yaml entry
|
|
knx:
|
|
sensor:
|
|
- name: "Heating Valve 1"
|
|
state_address: "2/0/0"
|
|
type: percent
|
|
sync_state: every 30
|
|
```
|
|
|
|
{% configuration %}
|
|
state_address:
|
|
description: KNX group address of the sensor.
|
|
required: true
|
|
type: [string, list]
|
|
type:
|
|
description: A type from the [value types table](/integrations/knx/#value-types) below must be defined. The DPT of the group address should match the expected KNX DPT to be parsed correctly.
|
|
required: true
|
|
type: [string, integer]
|
|
name:
|
|
description: A name for this device used within Home Assistant.
|
|
required: false
|
|
type: string
|
|
sync_state:
|
|
description: Actively read the value from the bus. The maximum time interval (`<minutes>`) is 1440. The following values are valid
|
|
|
|
- `true` equivalent to "expire 60" (default)
|
|
|
|
- `false` no GroupValueRead telegrams will be sent to the bus
|
|
|
|
- `every <minutes>` to update it regularly every \<minutes\>
|
|
|
|
- `expire <minutes>` to read the state from the KNX bus when no telegram was received for \<minutes\>
|
|
|
|
- `<minutes>` equivalent to "expire \<minutes\>"
|
|
|
|
- `init` to just initialize the state on startup
|
|
|
|
required: false
|
|
type: [boolean, string, integer]
|
|
default: true
|
|
always_callback:
|
|
description: Defines if telegrams with equal payload as the previously received telegram should trigger a state update within Home Assistant.
|
|
required: false
|
|
type: boolean
|
|
default: false
|
|
state_class:
|
|
description: Sets the [state_class](https://developers.home-assistant.io/docs/core/entity/sensor#available-state-classes) of the sensor.
|
|
required: false
|
|
type: string
|
|
entity_category:
|
|
description: The [category](https://developers.home-assistant.io/docs/core/entity#generic-properties) of the entity.
|
|
required: false
|
|
type: string
|
|
default: None
|
|
device_class:
|
|
description: Overrides the [class of the device](/integrations/sensor/), changing the device state and icon that is displayed on the frontend.
|
|
required: false
|
|
type: string
|
|
{% endconfiguration %}
|
|
|
|
### Value types
|
|
|
|
| KNX DPT | type | size in byte | range | unit |
|
|
| ------: | ----------------------------- | -----------: | :------------------------: | -------------- |
|
|
| 5 | 1byte_unsigned | 1 | 0 ... 255 | |
|
|
| 5.001 | percent | 1 | 0 ... 100 | % |
|
|
| 5.003 | angle | 1 | 0 ... 360 | ° |
|
|
| 5.004 | percentU8 | 1 | 0 ... 255 | % |
|
|
| 5.005 | decimal_factor | 1 | 0 ... 255 | |
|
|
| 5.006 | tariff | 1 | 0 ... 254 | |
|
|
| 5.010 | pulse | 1 | 0 ... 255 | counter pulses |
|
|
| 6 | 1byte_signed | 1 | -128 ... 127 | |
|
|
| 6.001 | percentV8 | 1 | -128 ... 127 | % |
|
|
| 6.010 | counter_pulses | 1 | -128 ... 127 | counter pulses |
|
|
| 7 | 2byte_unsigned | 2 | 0 ... 65535 | |
|
|
| 7.001 | pulse_2byte | 2 | 0 ... 65535 | pulses |
|
|
| 7.002 | time_period_msec | 2 | 0 ... 65535 | ms |
|
|
| 7.003 | time_period_10msec | 2 | 0 ... 65535 | ms |
|
|
| 7.004 | time_period_100msec | 2 | 0 ... 65535 | ms |
|
|
| 7.005 | time_period_sec | 2 | 0 ... 65535 | s |
|
|
| 7.006 | time_period_min | 2 | 0 ... 65535 | min |
|
|
| 7.007 | time_period_hrs | 2 | 0 ... 65535 | h |
|
|
| 7.011 | length_mm | 2 | 0 ... 65535 | mm |
|
|
| 7.012 | current | 2 | 0 ... 65535 | mA |
|
|
| 7.013 | brightness | 2 | 0 ... 65535 | lx |
|
|
| 7.600 | color_temperature | 2 | 0 ... 65535 | K |
|
|
| 8 | 2byte_signed | 2 | -32768 ... 32767 | |
|
|
| 8.001 | pulse_2byte_signed | 2 | -32768 ... 32767 | pulses |
|
|
| 8.002 | delta_time_ms | 2 | -32768 ... 32767 | ms |
|
|
| 8.003 | delta_time_10ms | 2 | -32768 ... 32767 | ms |
|
|
| 8.004 | delta_time_100ms | 2 | -32768 ... 32767 | ms |
|
|
| 8.005 | delta_time_sec | 2 | -32768 ... 32767 | s |
|
|
| 8.006 | delta_time_min | 2 | -32768 ... 32767 | min |
|
|
| 8.007 | delta_time_hrs | 2 | -32768 ... 32767 | h |
|
|
| 8.010 | percentV16 | 2 | -32768 ... 32767 | % |
|
|
| 8.011 | rotation_angle | 2 | -32768 ... 32767 | ° |
|
|
| 8.012 | length_m | 2 | -32768 ... 32767 | m |
|
|
| 9 | 2byte_float | 2 | -671088.64 ... 670760.96 | |
|
|
| 9.001 | temperature | 2 | -273 ... 670760 | °C |
|
|
| 9.002 | temperature_difference_2byte | 2 | -670760 ... 670760 | K |
|
|
| 9.003 | temperature_a | 2 | -670760 ... 670760 | K/h |
|
|
| 9.004 | illuminance | 2 | 0 ... 670760 | lx |
|
|
| 9.005 | wind_speed_ms | 2 | 0 ... 670760 | m/s |
|
|
| 9.006 | pressure_2byte | 2 | 0 ... 670760 | Pa |
|
|
| 9.007 | humidity | 2 | 0 ... 670760 | % |
|
|
| 9.008 | ppm | 2 | -671088.64 ... 670760.96 | ppm |
|
|
| 9.009 | air_flow | 2 | -671088.64 ... 670760.96 | m³/h |
|
|
| 9.010 | time_1 | 2 | -670760 ... 670760 | s |
|
|
| 9.011 | time_2 | 2 | -670760 ... 670760 | ms |
|
|
| 9.020 | voltage | 2 | -671088.64 ... 670760.96 | mV |
|
|
| 9.021 | curr | 2 | -671088.64 ... 670760.96 | mA |
|
|
| 9.022 | power_density | 2 | -671088.64 ... 670760.96 | W/m² |
|
|
| 9.023 | kelvin_per_percent | 2 | -671088.64 ... 670760.96 | K/% |
|
|
| 9.024 | power_2byte | 2 | -671088.64 ... 670760.96 | kW |
|
|
| 9.025 | volume_flow | 2 | -671088.64 ... 670760.96 | l/h |
|
|
| 9.026 | rain_amount | 2 | -671088.64 ... 670760.96 | l/m² |
|
|
| 9.027 | temperature_f | 2 | -459.6 ... 670760 | °F |
|
|
| 9.028 | wind_speed_kmh | 2 | 0 ... 670760 | km/h |
|
|
| 9.029 | absolute_humidity | 2 | 0 ... 670760 | g/m³ |
|
|
| 9.030 | concentration_ugm3 | 2 | 0 ... 670760 | μg/m³ |
|
|
| 9.? | enthalpy | 2 | -671088.64 ... 670760.96 | H |
|
|
| 12 | 4byte_unsigned | 4 | 0 ... 4294967295 | |
|
|
| 12.001 | pulse_4_ucount | 4 | 0 ... 4294967295 | counter pulses |
|
|
| 12.100 | long_time_period_sec | 4 | 0 ... 4294967295 | s |
|
|
| 12.101 | long_time_period_min | 4 | 0 ... 4294967295 | min |
|
|
| 12.102 | long_time_period_hrs | 4 | 0 ... 4294967295 | h |
|
|
| 12.1200 | volume_liquid_litre | 4 | 0 ... 4294967295 | l |
|
|
| 12.1201 | volume_m3 | 4 | 0 ... 4294967295 | m³ |
|
|
| 13 | 4byte_signed | 4 | -2147483648 ... 2147483647 | |
|
|
| 13.001 | pulse_4byte | 4 | -2147483648 ... 2147483647 | counter pulses |
|
|
| 13.002 | flow_rate_m3h | 4 | -2147483648 ... 2147483647 | m³/h |
|
|
| 13.010 | active_energy | 4 | -2147483648 ... 2147483647 | Wh |
|
|
| 13.011 | apparant_energy | 4 | -2147483648 ... 2147483647 | VAh |
|
|
| 13.012 | reactive_energy | 4 | -2147483648 ... 2147483647 | VARh |
|
|
| 13.013 | active_energy_kwh | 4 | -2147483648 ... 2147483647 | kWh |
|
|
| 13.014 | apparant_energy_kvah | 4 | -2147483648 ... 2147483647 | kVAh |
|
|
| 13.015 | reactive_energy_kvarh | 4 | -2147483648 ... 2147483647 | kVARh |
|
|
| 13.016 | active_energy_mwh | 4 | -2147483648 ... 2147483647 | MWh |
|
|
| 13.100 | long_delta_timesec | 4 | -2147483648 ... 2147483647 | s |
|
|
| 14 | 4byte_float | 4 | | |
|
|
| 14.000 | acceleration | 4 | | m/s² |
|
|
| 14.001 | acceleration_angular | 4 | | rad/s² |
|
|
| 14.002 | activation_energy | 4 | | J/mol |
|
|
| 14.003 | activity | 4 | | s⁻¹ |
|
|
| 14.004 | mol | 4 | | mol |
|
|
| 14.005 | amplitude | 4 | | |
|
|
| 14.006 | angle_rad | 4 | | rad |
|
|
| 14.007 | angle_deg | 4 | | ° |
|
|
| 14.008 | angular_momentum | 4 | | J s |
|
|
| 14.009 | angular_velocity | 4 | | rad/s |
|
|
| 14.010 | area | 4 | | m² |
|
|
| 14.011 | capacitance | 4 | | F |
|
|
| 14.012 | charge_density_surface | 4 | | C/m² |
|
|
| 14.013 | charge_density_volume | 4 | | C/m³ |
|
|
| 14.014 | compressibility | 4 | | m²/N |
|
|
| 14.015 | conductance | 4 | | S |
|
|
| 14.016 | electrical_conductivity | 4 | | S/m |
|
|
| 14.017 | density | 4 | | kg/m³ |
|
|
| 14.018 | electric_charge | 4 | | C |
|
|
| 14.019 | electric_current | 4 | | A |
|
|
| 14.020 | electric_current_density | 4 | | A/m² |
|
|
| 14.021 | electric_dipole_moment | 4 | | C m |
|
|
| 14.022 | electric_displacement | 4 | | C/m² |
|
|
| 14.023 | electric_field_strength | 4 | | V/m |
|
|
| 14.024 | electric_flux | 4 | | c |
|
|
| 14.025 | electric_flux_density | 4 | | C/m² |
|
|
| 14.026 | electric_polarization | 4 | | C/m² |
|
|
| 14.027 | electric_potential | 4 | | V |
|
|
| 14.028 | electric_potential_difference | 4 | | V |
|
|
| 14.029 | electromagnetic_moment | 4 | | A m² |
|
|
| 14.030 | electromotive_force | 4 | | V |
|
|
| 14.031 | energy | 4 | | J |
|
|
| 14.032 | force | 4 | | N |
|
|
| 14.033 | frequency | 4 | | Hz |
|
|
| 14.034 | angular_frequency | 4 | | rad/s |
|
|
| 14.035 | heatcapacity | 4 | | J/K |
|
|
| 14.036 | heatflowrate | 4 | | W |
|
|
| 14.037 | heat_quantity | 4 | | J |
|
|
| 14.038 | impedance | 4 | | Ω |
|
|
| 14.039 | length | 4 | | m |
|
|
| 14.040 | light_quantity | 4 | | lm s |
|
|
| 14.041 | luminance | 4 | | cd/m² |
|
|
| 14.042 | luminous_flux | 4 | | lm |
|
|
| 14.043 | luminous_intensity | 4 | | cd |
|
|
| 14.044 | magnetic_field_strength | 4 | | A/m |
|
|
| 14.045 | magnetic_flux | 4 | | Wb |
|
|
| 14.046 | magnetic_flux_density | 4 | | T |
|
|
| 14.047 | magnetic_moment | 4 | | A m² |
|
|
| 14.048 | magnetic_polarization | 4 | | T |
|
|
| 14.049 | magnetization | 4 | | A/m |
|
|
| 14.050 | magnetomotive_force | 4 | | A |
|
|
| 14.051 | mass | 4 | | kg |
|
|
| 14.052 | mass_flux | 4 | | kg/s |
|
|
| 14.053 | momentum | 4 | | N/s |
|
|
| 14.054 | phaseanglerad | 4 | | rad |
|
|
| 14.055 | phaseangledeg | 4 | | ° |
|
|
| 14.056 | power | 4 | | W |
|
|
| 14.057 | powerfactor | 4 | | |
|
|
| 14.058 | pressure | 4 | | Pa |
|
|
| 14.059 | reactance | 4 | | Ω |
|
|
| 14.060 | resistance | 4 | | Ω |
|
|
| 14.061 | resistivity | 4 | | Ωm |
|
|
| 14.062 | self_inductance | 4 | | H |
|
|
| 14.063 | solid_angle | 4 | | sr |
|
|
| 14.064 | sound_intensity | 4 | | W/m² |
|
|
| 14.065 | speed | 4 | | m/s |
|
|
| 14.066 | stress | 4 | | Pa |
|
|
| 14.067 | surface_tension | 4 | | N/m |
|
|
| 14.068 | common_temperature | 4 | | °C |
|
|
| 14.069 | absolute_temperature | 4 | | K |
|
|
| 14.070 | temperature_difference | 4 | | K |
|
|
| 14.071 | thermal_capacity | 4 | | J/K |
|
|
| 14.072 | thermal_conductivity | 4 | | W/mK |
|
|
| 14.073 | thermoelectric_power | 4 | | V/K |
|
|
| 14.074 | time_seconds | 4 | | s |
|
|
| 14.075 | torque | 4 | | Nm |
|
|
| 14.076 | volume | 4 | | m³ |
|
|
| 14.077 | volume_flux | 4 | | m³/s |
|
|
| 14.078 | weight | 4 | | N |
|
|
| 14.079 | work | 4 | | J |
|
|
| 14.080 | apparent_power | 4 | | VA |
|
|
| 16.000 | string | 14 | ASCII | |
|
|
| 16.001 | latin_1 | 14 | ISO 8859-1 / Latin-1 | |
|
|
| 17.001 | scene_number | 1 | 1 ... 64 | |
|
|
| 29 | 8byte_signed | 8 | ±9223372036854775807 | |
|
|
| 29.010 | active_energy_8byte | 8 | ±9223372036854775807 | Wh |
|
|
| 29.011 | apparant_energy_8byte | 8 | ±9223372036854775807 | VAh |
|
|
| 29.012 | reactive_energy_8byte | 8 | ±9223372036854775807 | VARh |
|
|
|
|
### More examples
|
|
|
|
```yaml
|
|
# Example configuration.yaml entry
|
|
knx:
|
|
sensor:
|
|
- name: "Heating Valve 1"
|
|
state_address: "2/0/0"
|
|
sync_state: init
|
|
type: percent
|
|
- name: "Kitchen Temperature"
|
|
state_address: "6/2/1"
|
|
sync_state: every 60
|
|
type: temperature
|
|
state_class: measurement
|
|
```
|
|
|
|
## Switch
|
|
|
|
The KNX switch platform is used as an interface to switching actuators.
|
|
|
|
Switch entities can be created from the frontend in the KNX panel or via YAML.
|
|
|
|
Switch entities without a `state_address` will restore their last known state after Home Assistant was restarted.
|
|
Switches that have a `state_address` configured request their current state from the KNX bus.
|
|
|
|
<a name="configuration-switch-yaml"></a>
|
|
{% details "Configuration of KNX switch entities via YAML" %}
|
|
|
|
```yaml
|
|
knx:
|
|
switch:
|
|
- name: "Kitchen coffee maker"
|
|
address: "1/1/6"
|
|
```
|
|
|
|
{% configuration %}
|
|
address:
|
|
description: KNX group address for switching the switch on/off. *DPT 1*
|
|
required: true
|
|
type: [string, list]
|
|
name:
|
|
description: A name for this device used within Home Assistant.
|
|
required: false
|
|
default: KNX Switch
|
|
type: string
|
|
state_address:
|
|
description: Separate KNX group address for retrieving the switch state. *DPT 1*
|
|
required: false
|
|
type: [string, list]
|
|
invert:
|
|
description: Invert the telegrams payload before processing or sending.
|
|
required: false
|
|
type: boolean
|
|
default: false
|
|
respond_to_read:
|
|
description: If `true`, the entity will respond to GroupValueRead telegrams received on the configured `address` by sending a GroupValueResponse to the same `address`. This is typically used when Home Assistant acts as the state provider for the KNX bus. In such cases, only `address` is configured, and `state_address` is not set. Read-requests to passive or state addresses don't trigger responses.
|
|
required: false
|
|
type: boolean
|
|
default: false
|
|
entity_category:
|
|
description: The [category](https://developers.home-assistant.io/docs/core/entity#generic-properties) of the entity.
|
|
required: false
|
|
type: string
|
|
default: None
|
|
device_class:
|
|
description: Sets the [class of the device](/integrations/switch/), changing the device state and icon that is displayed on the frontend.
|
|
required: false
|
|
type: string
|
|
{% endconfiguration %}
|
|
|
|
The optional `state_address` can be used to inform Home Assistant about state changes not triggered by a telegram to the `address` e.g., if you configure a timer on a channel. If a KNX message is seen on the bus addressed to the given state address, this will overwrite the state of the switch object.
|
|
|
|
{% enddetails %}
|
|
|
|
## Text
|
|
|
|
The KNX text platform allows to send text values to the KNX bus and update its state from received telegrams. It can optionally respond to read requests from the KNX bus.
|
|
|
|
{% note %}
|
|
Text entities without a `state_address` will restore their last known state after Home Assistant was restarted.
|
|
|
|
Texts that have a `state_address` configured request their current state from the KNX bus.
|
|
{% endnote %}
|
|
|
|
```yaml
|
|
# Example configuration.yaml entry
|
|
knx:
|
|
text:
|
|
- name: "Info"
|
|
address: "0/0/1"
|
|
- name: "ASCII Info"
|
|
address: "0/0/2"
|
|
state_address: "0/0/3"
|
|
type: string
|
|
- name: "Greeting"
|
|
address: "0/0/4"
|
|
respond_to_read: true
|
|
```
|
|
|
|
{% configuration %}
|
|
name:
|
|
description: A name for this device used within Home Assistant.
|
|
required: false
|
|
type: string
|
|
address:
|
|
description: The group address to which new values will be sent.
|
|
required: true
|
|
type: [string, list]
|
|
state_address:
|
|
description: Group address for retrieving the state from the KNX bus.
|
|
required: false
|
|
type: [string, list]
|
|
type:
|
|
description: Either `latin_1` for DPT 16.001 or `string` for DPT 16.000 (ASCII).
|
|
required: false
|
|
type: [string, integer]
|
|
default: latin_1
|
|
respond_to_read:
|
|
description: If `true`, the entity will respond to GroupValueRead telegrams received on the configured `address` by sending a GroupValueResponse to the same `address`. This is typically used when Home Assistant acts as the state provider for the KNX bus. In such cases, only `address` is configured, and `state_address` is not set. Read-requests to passive or state addresses don't trigger responses.
|
|
required: false
|
|
type: boolean
|
|
default: false
|
|
mode:
|
|
description: Specifies the mode used in the UI. `text` or `password` are valid.
|
|
required: false
|
|
type: string
|
|
default: text
|
|
entity_category:
|
|
description: The [category](https://developers.home-assistant.io/docs/core/entity#generic-properties) of the entity.
|
|
required: false
|
|
type: string
|
|
default: None
|
|
{% endconfiguration %}
|
|
|
|
## Time
|
|
|
|
The KNX time platform allows to send time values to the KNX bus and update its state from received telegrams. It can optionally respond to read requests from the KNX bus.
|
|
|
|
{% note %}
|
|
Time entities without a `state_address` will restore their last known state after Home Assistant was restarted.
|
|
|
|
Times that have a `state_address` configured request their current state from the KNX bus.
|
|
{% endnote %}
|
|
|
|
{% note %}
|
|
The `day` field of the time telegram will always be set to 0 (`no day`).
|
|
{% endnote %}
|
|
|
|
```yaml
|
|
# Example configuration.yaml entry
|
|
knx:
|
|
time:
|
|
- name: "Time"
|
|
address: "0/0/2"
|
|
state_address: "0/0/2"
|
|
```
|
|
|
|
{% configuration %}
|
|
name:
|
|
description: A name for this device used within Home Assistant.
|
|
required: false
|
|
type: string
|
|
address:
|
|
description: The group address to which new values will be sent. *DPT 10.001*
|
|
required: true
|
|
type: [string, list]
|
|
state_address:
|
|
description: Group address for retrieving the state from the KNX bus. *DPT 10.001*
|
|
required: false
|
|
type: [string, list]
|
|
respond_to_read:
|
|
description: If `true`, the entity will respond to GroupValueRead telegrams received on the configured `address` by sending a GroupValueResponse to the same `address`. This is typically used when Home Assistant acts as the state provider for the KNX bus. In such cases, only `address` is configured, and `state_address` is not set. Read-requests to passive or state addresses don't trigger responses.
|
|
required: false
|
|
type: boolean
|
|
default: false
|
|
sync_state:
|
|
description: Actively read the value from the bus. The maximum time interval (`<minutes>`) is 1440. The following values are valid
|
|
|
|
- `true` equivalent to "expire 60" (default)
|
|
|
|
- `false` no GroupValueRead telegrams will be sent to the bus
|
|
|
|
- `every <minutes>` to update it regularly every \<minutes\>
|
|
|
|
- `expire <minutes>` to read the state from the KNX bus when no telegram was received for \<minutes\>
|
|
|
|
- `<minutes>` equivalent to "expire \<minutes\>"
|
|
|
|
- `init` to just initialize the state on startup
|
|
|
|
required: false
|
|
type: [boolean, string, integer]
|
|
default: true
|
|
entity_category:
|
|
description: The [category](https://developers.home-assistant.io/docs/core/entity#generic-properties) of the entity.
|
|
required: false
|
|
type: string
|
|
default: None
|
|
{% endconfiguration %}
|
|
|
|
## Weather
|
|
|
|
The KNX weather platform is used as an interface to KNX weather stations.
|
|
|
|
To use your KNX weather station in your installation, add the following lines to your top-level [KNX Integration](/integrations/knx) configuration key in your {% term "`configuration.yaml`" %}:
|
|
|
|
```yaml
|
|
# Example configuration.yaml entry
|
|
knx:
|
|
weather:
|
|
- name: "Home"
|
|
address_temperature: "7/0/0"
|
|
address_brightness_south: "7/0/1"
|
|
address_brightness_west: "7/0/2"
|
|
address_brightness_east: "7/0/3"
|
|
address_brightness_north: "7/0/11"
|
|
address_wind_speed: "7/0/4"
|
|
address_rain_alarm: "7/0/5"
|
|
address_frost_alarm: "7/0/6"
|
|
address_wind_alarm: "7/0/7"
|
|
address_day_night: "7/0/8"
|
|
address_air_pressure: "7/0/9"
|
|
address_humidity: "7/0/10"
|
|
sync_state: true
|
|
```
|
|
|
|
{% configuration %}
|
|
name:
|
|
description: A name for this device used within Home Assistant.
|
|
required: false
|
|
default: KNX Weather
|
|
type: string
|
|
address_temperature:
|
|
description: KNX group address for reading current outside temperature from KNX bus. *DPT 9.001*
|
|
required: true
|
|
type: [string, list]
|
|
address_brightness_south:
|
|
description: KNX group address for reading current brightness to south coordinate from KNX bus. *DPT 9.004*
|
|
required: false
|
|
type: [string, list]
|
|
address_brightness_west:
|
|
description: KNX group address for reading current brightness to west coordinate from KNX bus. *DPT 9.004*
|
|
required: false
|
|
type: [string, list]
|
|
address_brightness_east:
|
|
description: KNX group address for reading current brightness to east coordinate from KNX bus. *DPT 9.004*
|
|
required: false
|
|
type: [string, list]
|
|
address_brightness_north:
|
|
description: KNX group address for reading current brightness to north coordinate from KNX bus. *DPT 9.004*
|
|
required: false
|
|
type: [string, list]
|
|
address_wind_bearing:
|
|
description: KNX group address for reading current wind bearing from KNX bus. *DPT 5.003*
|
|
required: false
|
|
type: [string, list]
|
|
address_wind_speed:
|
|
description: KNX group address for reading current wind speed from KNX bus. *DPT 9.005*
|
|
required: false
|
|
type: [string, list]
|
|
address_rain_alarm:
|
|
description: KNX group address for reading if rain alarm is on/off.
|
|
required: false
|
|
type: [string, list]
|
|
address_frost_alarm:
|
|
description: KNX group address for reading if frost alarm is on/off.
|
|
required: false
|
|
type: [string, list]
|
|
address_wind_alarm:
|
|
description: KNX group address for reading if wind alarm is on/off.
|
|
required: false
|
|
type: [string, list]
|
|
address_day_night:
|
|
description: KNX group address for reading if it's day/night.
|
|
required: false
|
|
type: [string, list]
|
|
address_air_pressure:
|
|
description: KNX address reading current air pressure. *DPT 9.006 or 14.058*
|
|
required: false
|
|
type: [string, list]
|
|
address_humidity:
|
|
description: KNX address for reading current humidity. *DPT 9.007*
|
|
required: false
|
|
type: [string, list]
|
|
sync_state:
|
|
description: Actively read the value from the bus. The maximum time interval (`<minutes>`) is 1440. The following values are valid
|
|
|
|
- `true` equivalent to "expire 60" (default)
|
|
|
|
- `false` no GroupValueRead telegrams will be sent to the bus
|
|
|
|
- `every <minutes>` to update it regularly every \<minutes\>
|
|
|
|
- `expire <minutes>` to read the state from the KNX bus when no telegram was received for \<minutes\>
|
|
|
|
- `<minutes>` equivalent to "expire \<minutes\>"
|
|
|
|
- `init` to just initialize the state on startup
|
|
|
|
required: false
|
|
type: [boolean, string, integer]
|
|
default: true
|
|
entity_category:
|
|
description: The [category](https://developers.home-assistant.io/docs/core/entity#generic-properties) of the entity.
|
|
required: false
|
|
type: string
|
|
default: None
|
|
{% endconfiguration %}
|
|
|
|
## Known limitations
|
|
|
|
- The integration aims to be compatible with a wide variety of KNX devices from different manufacturers and eras. However, there are some devices that use non-standard <abbr title="data point type">DPT</abbr> or use telegrams in a proprietary way. In these cases, you might not be able to configure {% term entities %} directly through this integration. However, you may still use [Template entities](/integrations/template/) with the [KNX telegram trigger](#telegram-trigger) to work around this.
|
|
|
|
- USB bus interfaces are not directly supported by the underlying [`xknx` library](https://github.com/XKNX/xknx). However, you could try to run a software KNX router such as `Calimero` or `knxd` alongside Home Assistant to serve as a USB to IP bridge. For best reliability, using a certified KNX IP interface or router is recommended.
|
|
|
|
## Troubleshooting / Common issues
|
|
|
|
### Logs for the KNX integration
|
|
|
|
The [`xknx` library](https://github.com/XKNX/xknx) is used for KNX communication. It provides various logging handlers for monitoring and debug purposes.
|
|
Add the following lines to your Home Assistant {% term "`configuration.yaml`" %} to activate them:
|
|
|
|
```yaml
|
|
logger:
|
|
default: warning
|
|
logs:
|
|
# For most debugging needs `xnx.log` and `xknx.telegram` are a good choice.
|
|
xknx: info # sets the level of all loggers
|
|
# Loggers for different layers of KNX communication
|
|
xknx.log: debug # provides general information (connection, etc.)
|
|
xknx.telegram: debug # logs telegrams before they are being processed or sent
|
|
xknx.cemi: debug # logs incoming and outgoing CEMI frames
|
|
xknx.data_secure: debug # logs Data Secure relevant information
|
|
xknx.ip_secure: debug # logs IP Secure relevant information
|
|
xknx.knx: debug # logs incoming and outgoing KNX/IP frames
|
|
xknx.raw_socket: warning # logs incoming UDP/TCP frames in raw hex format at socket level
|
|
# Loggers for xknx internals
|
|
xknx.ga_dpt: warning # logs when payloads can't be decoded with given project file information
|
|
xknx.state_updater: warning # provides information about the state updater
|
|
```
|
|
|
|
You can use the `logger.set_level` action to change the log level of a handler on a running instance.
|
|
{% my developer_call_service badge service="logger.set_level" %}
|
|
|
|
### Group address can not be read
|
|
|
|
Every `*_state_address` is read on startup sequentially if not configured differently. If you see the following errors in your log, a group address could not be read by a GroupValueRead request from Home Assistant in time.
|
|
|
|
```log
|
|
> Could not sync group address '1/2/3' (Entity name - Feature)
|
|
> Error: KNX bus did not respond in time (2.0 secs) to GroupValueRead request for: '1/2/3'
|
|
```
|
|
|
|
#### No group object (GO) assigned to the group address (GA) has the Read-Flag set in ETS
|
|
|
|
- Enable the read flag for *one* GO assigned to the GA. Use the one most likely to hold the current state (e.g., for a light entity's `brightness_state_address` the according GO of the dimming actuator).
|
|
|
|
#### Response telegrams are not passing a line coupler, router or other filter in the installation
|
|
|
|
- Assign the group addresses used by Home Assistant to the used interface in ETS if your interface application supports that. ETS will generate filter tables that are applied to your line couplers after updating their application.
|
|
- If your interface application doesn't support that, use a dummy device in ETS for Home Assistant. These can be found in the ETS online catalog. Assign it to the line your interface connects Home Assistant to and link its group objects to the group addresses you are using in Home Assistant.
|
|
|
|
#### Unresponsive system
|
|
|
|
- The timeout for logging the errors (2 seconds) is started when the GroupValueRead request is scheduled to be sent. On systems experiencing high loads sending can be delayed (e.g., Raspberry Pi running lots of integrations at startup).
|
|
Incoming response telegrams are always processed, so no information gets lost.
|
|
|
|
### Duplicate entities
|
|
|
|
If you find following error in your log you seem to have a duplicated entity in your configuration.
|
|
|
|
```log
|
|
Platform knx does not generate unique IDs. ID 1/2/3 already exists - ignoring platform.name
|
|
```
|
|
|
|
The `unique_id` for KNX entities is generated based on required configuration values.
|
|
|
|
- binary_sensor: `state_address`
|
|
- climate: `temperature_address` `target_temperature_state_address` `target_temperature_address` `setpoint_shift_address`
|
|
- cover: `move_long_address` `position_address`
|
|
- fan: `address`
|
|
- light: `address` or all combined `brightness_address` if only `individual_colors` is used
|
|
- notify: `address`
|
|
- scene: `address` and `scene_number`
|
|
- sensor: `state_address`
|
|
- switch: `address`
|
|
- weather: `address_temperature`
|
|
|
|
There can not be multiple entities on the same platform sharing these exact group addresses, even if they differ in other configuration.
|
|
|
|
## Removing the integration
|
|
|
|
This integration can be removed by following these steps:
|
|
|
|
{% include integrations/remove_device_service.md %}
|
|
|
|
In addition, remove `knx:` from your {% term "`configuration.yaml`" %}.
|
|
|
|
{% warning %}
|
|
|
|
Removing the integration will delete an uploaded keyring file, ETS project information, telegram history, and all entity configuration done via the UI panel.
|
|
|
|
{% endwarning %}
|