| readme.md | ||
readme.md
| id | label | title | type | description | logo | install |
|---|---|---|---|---|---|---|
| wolfsmartset | Wolf Smartset | Wolf Smartset - Bindings | binding | This binding communicates with the <www.wolf-smartset.de> API and provides values readonly. | images/addons/wolfsmartset.png | auto |
{% include base.html %}
Wolf Smartset Binding
This binding communicates with the <www.wolf-smartset.de> API and provides values readonly. Wolf systems are connected with official gateways (Wolf Link Home or Wolf Link Pro) Wolf SmartHome products
Supported Things
- Account (
thing-type:wolfsmartset:account)- holding the credentials to connect to the wolf-smartset online portal.
- System (
thing-type:wolfsmartset:system)- represents one wolf system connected to the wolf-smartset online portal.
- Unit (
thing-type:wolfsmartset:unit)- unit is a part of the system with values and parameter
Discovery
- System things (bridge) are discovered after Account Thing (bridge) is set up
- Unit things are discovered after System things are set up
Thing Configuration
Account (bridge)
The account Thing holds the credentials to connect to the wolf-smartset online portal.
| Parameter | Type | Defaut | Description |
|---|---|---|---|
| username | text | username to authenticate to <www.wolf-smartset.de> | |
| password | text | password to authenticate to <www.wolf-smartset.de> | |
| refreshIntervalStructure | integer | 10 | Specifies the refresh interval to refresh the Structure in minutes |
| refreshIntervalValues | integer | 15 | Specifies time in seconds to refresh values |
| discoveryEnabled | boolean | true | disable the Thing discovery |
System (bridge)
The system Thing represents one wolf system connected via a WOLF Link home or a WOLF Link pro to the wolf-smartset online portal. You have access to your own or to shared systems.
| Parameter | Type | Defaut | Description |
|---|---|---|---|
| systemId | integer | System ID assigned to the system by WolfSmartset |
Unit
A system is divided into different units. In the wolf-smartset portal, the system has an "Expert" section, each submenu item within the "Expert" section has multiple tabs. Each of these tabs is treated as one unit.
| Parameter | Type | Defaut | Description |
|---|---|---|---|
| unitId | integer | The BundleId assigned to the unit by WolfSmartset |
Tested WOLF-Devices
| WOLF Equipment | openHAB Version | Used gateway |
|---|---|---|
| CSZ (CGB and SM1) | 3.1 | WOLF Link Pro |
| CGB-2 | 3.1 | WOLF Link home |
Channels
| channel | type | description |
|---|---|---|
| number | Number | a generic number |
| contact | Contact | a generic contact |
| temperature | Number:Temperature | a generic temperature |
| string | String | a generic String |
| datetime | DateTime | a generic DateTime |
Full Example
Things
Bridge wolfsmartset:account:account "Wolf Smartset Account" [ username="User", password="Password" ] {
Bridge system 32122305166 "WolfSmartset System CSZ" [ systemId="32122305166" ] {
Thing unitId uinit0 "CSZ Heizgerät" [ unitId="unit0" ] {
}
}
}
You need to use the corrosponding systemId and unitId returned by the discovery.
Items
"Number CSZHeizgerat_Raumtemperatur "Raumtemperatur" { channel="wolfsmartset:unit:account:32122305166:uinit0:1000900000"}
Number CSZHeizgerat_Flamme "Flamme" { channel="wolfsmartset:unit:account:32122305166:uinit0:1000900001"}
Number CSZHeizgerat_AnalogeFernbedienung "Analoge Fernbedienung" { channel="wolfsmartset:unit:account:32122305166:uinit0:1000900002"}
Number CSZHeizgerat_Raumsolltemperatur "Raumsolltemperatur" { channel="wolfsmartset:unit:account:32122305166:uinit0:1000900003"}
Number CSZHeizgerat_AusgangA1 "Ausgang A1" { channel="wolfsmartset:unit:account:32122305166:uinit0:1000900004"}
String CSZHeizgerat_ZeitprogrammdirekterHeizkreis "Zeitprogramm direkter Heizkreis" { channel="wolfsmartset:unit:account:32122305166:uinit0:1000900005"}
Number CSZHeizgerat_Ventil1 "Ventil 1" { channel="wolfsmartset:unit:account:32122305166:uinit0:1000900006"}
Number CSZHeizgerat_Ventil2 "Ventil 2" { channel="wolfsmartset:unit:account:32122305166:uinit0:1000900007"}
Number CSZHeizgerat_WiSoUmschaltung "Wi/So Umschaltung" { channel="wolfsmartset:unit:account:32122305166:uinit0:1000900008"}
Number CSZHeizgerat_Tagtemperatur "Tagtemperatur" { channel="wolfsmartset:unit:account:32122305166:uinit0:1000900009"}
Number CSZHeizgerat_PWMPumpe "PWM Pumpe" { channel="wolfsmartset:unit:account:32122305166:uinit0:10009000010"}
Number CSZHeizgerat_Speichersolltemperatur "Speichersolltemperatur" { channel="wolfsmartset:unit:account:32122305166:uinit0:10009000011"}
Number CSZHeizgerat_Heizkurve "Heizkurve" { channel="wolfsmartset:unit:account:32122305166:uinit0:10009000012"}
Number CSZHeizgerat_Raumeinfluss "Raumeinfluss" { channel="wolfsmartset:unit:account:32122305166:uinit0:10009000013"}
Number CSZHeizgerat_TWVorlauf "TW-Vorlauf" { channel="wolfsmartset:unit:account:32122305166:uinit0:10009000014"}
Number CSZHeizgerat_Spartemperatur "Spartemperatur" { channel="wolfsmartset:unit:account:32122305166:uinit0:10009000015"}
Number CSZHeizgerat_Geblase "Gebläse" { channel="wolfsmartset:unit:account:32122305166:uinit0:10009000016"}
Number CSZHeizgerat_Vorlaufsolltemperatur "Vorlaufsolltemperatur" { channel="wolfsmartset:unit:account:32122305166:uinit0:10009000017"}
Group CSZHeizgerat "CSZ Heizgerät" { channel="wolfsmartset:unit:account:32122305166:uinit0:10009000018"}
Number CSZHeizgerat_ECOABS "ECO/ABS" { channel="wolfsmartset:unit:account:32122305166:uinit0:10009000019"}
Number CSZHeizgerat_Netzbetriebstunden "Netzbetriebstunden" { channel="wolfsmartset:unit:account:32122305166:uinit0:10009000020"}
Number CSZHeizgerat_TWAbgas "TW-Abgas" { channel="wolfsmartset:unit:account:32122305166:uinit0:10009000021"}
Number CSZHeizgerat_HGStatus "HG Status" { channel="wolfsmartset:unit:account:32122305166:uinit0:10009000022"}
Number CSZHeizgerat_EingangE1 "Eingang E1" { channel="wolfsmartset:unit:account:32122305166:uinit0:10009000023"}"
Supported Heating-Devices
All devices able to be connected to <www.wolf-smartset.de>
Related Documentation from WOLF
| Heating system | WOLF Link home | WOLF Link pro |
|---|---|---|
| Gas condensing boiler CGB-2, CGW-2, CGS-2 | Y | Y |
| Oil condensing boiler TOB | Y | Y |
| MGK-2 gas condensing boiler | Y | Y |
| split air/water heat pump BWL-1S | Y | Y |
| Oil condensing boiler COB | Y | |
| gas condensing boiler MGK | Y | |
| Gas condensing boilers CGB, CGW, CGS, FGB | Y | |
| Gas condensing boilers CGG-2, CGU-2 | Y | |
| Boiler controls R2, R3, R21 | Y | |
| Monobloc heat pumps BWW-1, BWL-1, BWS-1 | Y | |
| mixer module MM, MM-2 | O | Y |
| cascade module KM, KM-2 | O | Y |
| solar modules SM1, SM1-2, SM-2, SM2-2 | O | Y |
| Comfort apartment ventilation CWL Excellent | O | Y |
Air handling units KG Top, CKL Pool* |
Y | |
Air handling units CKL, CFL, CRL* |
Y | |
| Combined heat and power units | Y |
Note:
O) possible in connection with a WOLF Link home compatible heater, full functionality only for devices with current software version.
* Modbus interface required in the device,
Special programming cannot be mapped.