--- layout: documentation title: FGD212 - ZWave --- {% include base.html %} # FGD212 Dimmer 2 This describes the Z-Wave device *FGD212*, manufactured by *[Fibargroup](http://www.fibaro.com/)* with the thing type UID of ```fibaro_fgd212_03_005```. This version of the device is limited to firmware versions above 3.5 The device is in the category of *Wall Switch*, defining Any device attached to the wall that controls a binary status of something, for ex. a light switch. ![FGD212 product image](https://www.cd-jackson.com/zwave_device_uploads/787/787_default.jpg) The FGD212 supports routing. This allows the device to communicate using other routing enabled devices as intermediate routers. This device is also able to participate in the routing of data between other devices in the mesh network. ## Overview Remotely controlled light dimming module is designed to work with various types of light sources. It may be connected to two-wire or three-wire configuration so it can operate with or without neutral lead. FIBARO Dimmer 2 can switch or dim connected light source either through radio waves or through the wall switch connected directly to it. New FIBARO Dimmer 2 is equipped with an algorithm of smart light source detection which makes configuration easier and ensures high compatibility of the device. It may be used as a switch with nondimmable light sources (in 3-wire connection). **Main features of FIBARO Dimmer 2:** * Compatible with any Z-Wave or Z-Wave+ Controller * Controlled by FIBARO Home Center or any other Z-Wave controller * Advanced microprocessor control, • Implemented algorithm of smart light source detection * Auto-adjustment of the appropriate control mode to connected load * Active power and energy metering functionality * Soft start function, • Memory of the last lighting level settings * Works with various types of switches – momentary, toggle, three-way, etc * Active element: semiconductor electronic switch * To be installed in wall switch boxes of dimensions allowing for installation, conforming to provisions of applicable regulations * FGD-212 is an extension unit. ### Inclusion Information 1. Place the Dimmer 2 within the direct range of your Z-Wave controller. 2. Identify switch no. 1 (turns the light on) or the B-button (located on the device’s housing). 3. Set the main controller in (security/non-security) add mode (see the controller’s manual). 4. Quickly, three times press switch no. 1 or the B-button. 5. Wait for the adding process to end. 6. Successful adding will be confirmed by the Z-Wave controller’s message. ### Exclusion Information 1. Place the Dimmer 2 within the direct range of your Z-Wave controller. 2. Identify switch no. 1 (turns the light on) or the B-button (located on the device’s housing). 3. Set the main controller in remove mode (see the controller’s manual). 4. Quickly, three times press switch no. 1 or the B-button. 5. Wait for the removing process to end. 6. Successful removing will be confirmed by the Z-Wave controller’s message. 7. Dimmer 2 will start the calibration process. ## Channels The following table summarises the channels available for the FGD212 -: | Channel | Channel Id | Category | Item Type | |---------|------------|----------|-----------| | Scene Number | scene_number | | Number | | Sensor (power) | sensor_power | Energy | Number | | Electric meter (kWh) | meter_kwh | Energy | Number | | Electric meter (watts) | meter_watts | Energy | Number | | Reset the total power consumption | meter_reset | Energy | Switch | | Force initial brightness | config_decimal | | Number | | Alarm (heat) | alarm_heat | | Switch | | Alarm (power) | alarm_power | Door | Switch | | Alarm (system) | alarm_system | | Switch | | Dimmer 1 | switch_dimmer1 | DimmableLight | Dimmer | | Sensor (power) 1 | sensor_power1 | Energy | Number | | Electric meter (kWh) 1 | meter_kwh1 | Energy | Number | | Electric meter (watts) 1 | meter_watts1 | Energy | Number | | Alarm (heat) 1 | alarm_heat1 | | Switch | | Alarm (power) 1 | alarm_power1 | Door | Switch | | Alarm (system) 1 | alarm_system1 | | Switch | | Dimmer 2 | switch_dimmer2 | DimmableLight | Dimmer | ### Scene Number Triggers when a scene button is pressed. The ```scene_number``` channel supports the ```Number``` item. ### Sensor (power) Indicates the energy consumption (kWh). The ```sensor_power``` channel supports the ```Number``` item and is in the ```Energy``` category. This is a read only channel so will only be updated following state changes from the device. ### Electric meter (kWh) Indicates the energy consumption (kWh). The ```meter_kwh``` channel supports the ```Number``` item and is in the ```Energy``` category. This is a read only channel so will only be updated following state changes from the device. ### Electric meter (watts) Indicates the instantaneous power consumption. The ```meter_watts``` channel supports the ```Number``` item and is in the ```Energy``` category. This is a read only channel so will only be updated following state changes from the device. ### Reset the total power consumption Reset the meter. The ```meter_reset``` channel supports the ```Switch``` item and is in the ```Energy``` category. ### Force initial brightness Generic class for configuration parameter. The ```config_decimal``` channel supports the ```Number``` item. ### Alarm (heat) Indicates if a heat alarm is triggered. The ```alarm_heat``` channel supports the ```Switch``` item. This is a read only channel so will only be updated following state changes from the device. The following state translation is provided for this channel to the ```Switch``` item type -: | Value | Label | |-------|-----------| | OFF | OK | | ON | Alarm | ### Alarm (power) Indicates if a power alarm is triggered. The ```alarm_power``` channel supports the ```Switch``` item and is in the ```Door``` category. This is a read only channel so will only be updated following state changes from the device. The following state translation is provided for this channel to the ```Switch``` item type -: | Value | Label | |-------|-----------| | OFF | OK | | ON | Alarm | ### Alarm (system) Indicates if a system alarm is triggered. The ```alarm_system``` channel supports the ```Switch``` item. This is a read only channel so will only be updated following state changes from the device. The following state translation is provided for this channel to the ```Switch``` item type -: | Value | Label | |-------|-----------| | OFF | OK | | ON | Alarm | ### Dimmer 1 The brightness channel allows to control the brightness of a light. It is also possible to switch the light on and off. The ```switch_dimmer1``` channel supports the ```Dimmer``` item and is in the ```DimmableLight``` category. ### Sensor (power) 1 Indicates the energy consumption (kWh). The ```sensor_power1``` channel supports the ```Number``` item and is in the ```Energy``` category. This is a read only channel so will only be updated following state changes from the device. ### Electric meter (kWh) 1 Indicates the energy consumption (kWh). The ```meter_kwh1``` channel supports the ```Number``` item and is in the ```Energy``` category. This is a read only channel so will only be updated following state changes from the device. ### Electric meter (watts) 1 Indicates the instantaneous power consumption. The ```meter_watts1``` channel supports the ```Number``` item and is in the ```Energy``` category. This is a read only channel so will only be updated following state changes from the device. ### Alarm (heat) 1 Indicates if a heat alarm is triggered. The ```alarm_heat1``` channel supports the ```Switch``` item. This is a read only channel so will only be updated following state changes from the device. The following state translation is provided for this channel to the ```Switch``` item type -: | Value | Label | |-------|-----------| | OFF | OK | | ON | Alarm | ### Alarm (power) 1 Indicates if a power alarm is triggered. The ```alarm_power1``` channel supports the ```Switch``` item and is in the ```Door``` category. This is a read only channel so will only be updated following state changes from the device. The following state translation is provided for this channel to the ```Switch``` item type -: | Value | Label | |-------|-----------| | OFF | OK | | ON | Alarm | ### Alarm (system) 1 Indicates if a system alarm is triggered. The ```alarm_system1``` channel supports the ```Switch``` item. This is a read only channel so will only be updated following state changes from the device. The following state translation is provided for this channel to the ```Switch``` item type -: | Value | Label | |-------|-----------| | OFF | OK | | ON | Alarm | ### Dimmer 2 The brightness channel allows to control the brightness of a light. It is also possible to switch the light on and off. The ```switch_dimmer2``` channel supports the ```Dimmer``` item and is in the ```DimmableLight``` category. ## Device Configuration The following table provides a summary of the 51 configuration parameters available in the FGD212. Detailed information on each parameter can be found in the sections below. | Param | Name | Description | |-------|-------|-------------| | 1 | Minimum brightness level | The parameter is set automatically during the calibration process. The parameter can be changed manually after the calibration. | | 2 | Maximum brightness level | The parameter is set automatically during the calibration process. The parameter can be changed manually after the calibration. | | 3 | Incandescence level of dimmable compact fluorescent lamps | Virtual value set as a percentage level between parameters MIN (1%) and MAX. (99%). The Dimmer will set to this value after first switch on. It is required for warming up and switching dimmable compact fluorescent lamps and certain types of light sources. | | 4 | Incandescence time of dimmable compact fluorescent lamps | This parameter determines the time required for switching compact fluorescent lamps and certain types of light sources. Setting this parameter to 0 will disable the incandescence functionality. Available settings: 0-255 (0s - 25,5s) | | 5 | Dimming Step at Automatic Control | The parameter defines the percentage of a dimming step at automatic control. 1-99 | | 6 | Dimming Step Timing at Automatic Control | The parameter defines the time of a dimming step at automatic control. Available settings: 0-255 (0s - 2,55s) | | 7 | Dimming Step at Manual Control | The parameter defines the percentage of a dimming step at manual control. 1-99 | | 8 | Dimming Step Timing at Manual Control | The parameter defines the time of a dimming step at manual control. Available settings: 0-255 (0s - 2,55s) | | 9 | Saving state before power failure | Saving state before power failure | | 10 | Timer functionality (auto - off). 0 disables the function | The parameter defines the setting of the timer. Available settings:1-32767 - time to turn off measured in seconds (1s - 9,1h) | | 11 | ALL ON/ALL OFF function | The parameter specifies the available functions. | | 13 | Force auto-calibration | Changing the value of this parameter to 1 will force the calibration process. During the calibration parameter is set to 1 and switched to 0 upon completion. | | 14 | Auto-calibration status (read-only parameter) | This parameter determines operating mode of the Dimmer (automatic/manual settings). | | 15 | Burnt out bulb detection | percentage value of power variation, compared to standard power consumption, measured during the calibration procedure (to be interpreted as load error/burnt out bulb). 1-99, 0 disables the function. | | 16 | Time delay of a burnt out bulb (parameter 15) or overload (parameter 39) detection | Time of delay (in seconds) for power variation detection, interpreted as a LOAD ERROR or OVERLOAD detection (too much power connected to the Dimmer 2). 0 disables the function. | | 19 | Forced switch on brightness level | If the parameter is active, switching on the Dimmer 2 (S1 single click) will always set this brightness level. 0 disables the function. | | 20 | Inputs Button/Switch configuration | Binary inputs type configuration | | 21 | Value sent to associated devices on single click | The value sent to associated devices on single click. | | 22 | Change [On-Off] bi-stable keys | This function allow user to change [On-Off] bi-stable keys (parameter no. 14) (default value 0) | | 23 | Double click option | Double-click set lighting at 100% | | 24 | Command frames sent in 2nd and 3rd association groups (S1 associations) | Parameter determines, which actions will not result in sending frames to association groups. | | 25 | Command frames sent in 4th and 5th association groups (S2associations) | Parameter determines, which actions will not result in sending frames to association groups. | | 26 | The function of 3-way switch | Key no. 2 controls the Dimmer additionally (in 3-way switch mode). Function disabled for parameter 20 set to 2 (roller blind switch). | | 27 | Associations in Z-Wave network security mode | This parameter defines how commands are sent in specified association groups: as secure or non-secure. Parameter is active only in Z-Wave network security mode. It does not apply to 1st Lifeline group. | | 28 | Scene activation functionality | SCENE ID depends on the switch type configuration | | 29 | Switch functionality of S1 and S2 | Switch S1 and S2 buttons | | 30 | Load control mode | The parameter defines the used control mode. | | 31 | Load control mode recognized during auto-calibration | Load control mode recognized during auto-calibration | | 32 | On/Off mode | This mode is necessary while connecting non-dimmable light sources. Enabling parameter 32 automatically ignores brightening/- dimming time settings. | | 33 | Dimmability of the load (read only) | Dimmability of the load (read only) | | 34 | Soft-Start functionality | Time required to warm up the filament of halogen bulb. | | 35 | Auto-calibration after power on | This parameter determines the trigger of auto-calibration procedure, e.g. power on, load error, etc. | | 37 | Behaviour of the Dimmer after overload or surge | | | 38 | Brightness level correction for flickering loads | This parameter specifies the duration of Brightness level correction for flickering loads in seconds. 255 sets the function to "always enabled". 0 disables the function. | | 39 | Power limit - OVERLOAD | Reaching the defined value will result in turning off the load. Parameter 39 is relevant only in a 3-wire connection i or a 2-wire connection for load of cosφ ≥ 0.99. (1 W - 250 W). 0 disables the function. | | 40 | General Purpose Alarm | The parameter specifies the response to an alarm. | | 41 | Water Flooding Alarm | The parameter specifies the response to an alarm. | | 42 | Smoke, CO or CO2 Alarm | The parameter specifies the response to an alarm. | | 43 | Temperature Alarm | The parameter specifies the response to an alarm. | | 44 | Time of alarm state | Alarm state may be cancelled earlier, as a result of pushing the wall-switch keys or sending the Z-Wave command frame. Available settings: 1-32767 (1s - 32767s). | | 45 | OVERLOAD alarm report | (load power consumption too high) | | 46 | LOAD ERROR alarm report | (no load, load failure, burnt out bulb) | | 47 | OVERCURRENT alarm report | (short circuit, burnt out bulb causing overcurrent) | | 48 | SURGE alarm report | (Dimmer output overvoltage) | | 49 | OVERHEAT (critical temperature) and VOLTAGE DROP (low voltage) alarm report | | | 50 | Active power reports | The parameter defines the power level change that will result in a new power report being sent. The value is a percentage of the previous report. 0 disables the function. | | 52 | Periodic active power and energy reports | Parameter 52 defines a time period between consecutive reports. Timer is reset and counted from zero after each report (1 sec - 32767 sec). 0 disables the function. | | 53 | Energy reports | Energy level change which will result in sending a new energy report. Available settings: 1-255 (0,01 - 2,55 kWh). 0 disables the function. | | 54 | Self-measurement | The Dimmer may include active power and energy used by itself in reports sent to the main controller. | | 58 | Method of calculating the active power | This parameter defines how to calculate active power. It is useful in a case of 2-wire connection with light sources other than resistive. Note: Parameter 58 is set to 0 after forced auto-calibration | | 59 | Approximated power at the maximum brightness level | This parameter determines the approximate value of the power that will be reported by the device at its maximum brightness level. Available settings: 0-500 (0-500W). Note: Parameter 59 works only when parameter 58 has a value other than 0. | | | Switch All Mode | Set the mode for the switch when receiving SWITCH ALL commands | ### Parameter 1: Minimum brightness level The parameter is set automatically during the calibration process. The parameter can be changed manually after the calibration. Values in the range 1 to 98 may be set. The manufacturer defined default value is ```1```. This parameter has the configuration ID ```config_1_1``` and is of type ```INTEGER```. ### Parameter 2: Maximum brightness level The parameter is set automatically during the calibration process. The parameter can be changed manually after the calibration. Values in the range 1 to 99 may be set. The manufacturer defined default value is ```99```. This parameter has the configuration ID ```config_2_1``` and is of type ```INTEGER```. ### Parameter 3: Incandescence level of dimmable compact fluorescent lamps Virtual value set as a percentage level between parameters MIN (1%) and MAX. (99%). The Dimmer will set to this value after first switch on. It is required for warming up and switching dimmable compact fluorescent lamps and certain types of light sources. Values in the range 1 to 99 may be set. The manufacturer defined default value is ```1```. This parameter has the configuration ID ```config_3_1``` and is of type ```INTEGER```. ### Parameter 4: Incandescence time of dimmable compact fluorescent lamps This parameter determines the time required for switching compact fluorescent lamps and certain types of light sources. Setting this parameter to 0 will disable the incandescence functionality. Available settings: 0-255 (0s - 25,5s) Values in the range 0 to 255 may be set. The manufacturer defined default value is ```0```. This parameter has the configuration ID ```config_4_2``` and is of type ```INTEGER```. ### Parameter 5: Dimming Step at Automatic Control The parameter defines the percentage of a dimming step at automatic control. 1-99 Values in the range 1 to 99 may be set. The manufacturer defined default value is ```1```. This parameter has the configuration ID ```config_5_1``` and is of type ```INTEGER```. ### Parameter 6: Dimming Step Timing at Automatic Control The parameter defines the time of a dimming step at automatic control. Available settings: 0-255 (0s - 2,55s) Values in the range 0 to 255 may be set. The manufacturer defined default value is ```1```. This parameter has the configuration ID ```config_6_2``` and is of type ```INTEGER```. ### Parameter 7: Dimming Step at Manual Control The parameter defines the percentage of a dimming step at manual control. 1-99 Values in the range 1 to 99 may be set. The manufacturer defined default value is ```1```. This parameter has the configuration ID ```config_7_1``` and is of type ```INTEGER```. ### Parameter 8: Dimming Step Timing at Manual Control The parameter defines the time of a dimming step at manual control. Available settings: 0-255 (0s - 2,55s) Values in the range 0 to 255 may be set. The manufacturer defined default value is ```5```. This parameter has the configuration ID ```config_8_2``` and is of type ```INTEGER```. ### Parameter 9: Saving state before power failure Saving state before power failure The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | State NOT saved at power failure, all outputs are set to OFF upon powe | | 1 | State saved at power failure, all outputs are set to previous state up | The manufacturer defined default value is ```1``` (State saved at power failure, all outputs are set to previous state up). This parameter has the configuration ID ```config_9_1``` and is of type ```INTEGER```. ### Parameter 10: Timer functionality (auto - off). 0 disables the function The parameter defines the setting of the timer. Available settings:1-32767 - time to turn off measured in seconds (1s - 9,1h) Values in the range 0 to 32767 may be set. The manufacturer defined default value is ```0```. This parameter has the configuration ID ```config_10_2``` and is of type ```INTEGER```. ### Parameter 11: ALL ON/ALL OFF function The parameter specifies the available functions. The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | ALL ON not active, ALL OFF not active | | 1 | ALL ON not active, ALL OFF active | | 2 | ALL ON active, ALL OFF not active | | 255 | ALL ON active, ALL OFF active | The manufacturer defined default value is ```255``` (ALL ON active, ALL OFF active). This parameter has the configuration ID ```config_11_2``` and is of type ```INTEGER```. ### Parameter 13: Force auto-calibration Changing the value of this parameter to 1 will force the calibration process. During the calibration parameter is set to 1 and switched to 0 upon completion. The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | readout | | 1 | force auto-calibration of the load without Fibaro Bypass | | 2 | force auto-calibration of the load with Fibaro Bypass | The manufacturer defined default value is ```0``` (readout). This parameter has the configuration ID ```config_13_1``` and is of type ```INTEGER```. ### Parameter 14: Auto-calibration status (read-only parameter) This parameter determines operating mode of the Dimmer (automatic/manual settings). The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | calibration procedure not performed or Dimmer operates on manual setti | | 1 | Dimmer operates on auto-calibration settings | The manufacturer defined default value is ```0``` (calibration procedure not performed or Dimmer operates on manual setti). This parameter has the configuration ID ```config_14_1``` and is of type ```INTEGER```. This is a read only parameter. ### Parameter 15: Burnt out bulb detection percentage value of power variation, compared to standard power consumption, measured during the calibration procedure (to be interpreted as load error/burnt out bulb). 1-99, 0 disables the function. Values in the range 0 to 99 may be set. The manufacturer defined default value is ```30```. This parameter has the configuration ID ```config_15_1``` and is of type ```INTEGER```. ### Parameter 16: Time delay of a burnt out bulb (parameter 15) or overload (parameter 39) detection Time of delay (in seconds) for power variation detection, interpreted as a LOAD ERROR or OVERLOAD detection (too much power connected to the Dimmer 2). 0 disables the function. Values in the range 0 to 255 may be set. The manufacturer defined default value is ```5```. This parameter has the configuration ID ```config_16_2``` and is of type ```INTEGER```. ### Parameter 19: Forced switch on brightness level If the parameter is active, switching on the Dimmer 2 (S1 single click) will always set this brightness level. 0 disables the function. Values in the range 0 to 99 may be set. The manufacturer defined default value is ```0```. This parameter has the configuration ID ```config_19_1``` and is of type ```INTEGER```. ### Parameter 20: Inputs Button/Switch configuration Binary inputs type configuration The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | Mono-stable input (button) | | 1 | Bi-stable input (switch) | | 2 | Roller blind switch (UP / DOWN) | The manufacturer defined default value is ```0``` (Mono-stable input (button)). This parameter has the configuration ID ```config_20_1``` and is of type ```INTEGER```. ### Parameter 21: Value sent to associated devices on single click The value sent to associated devices on single click. The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | 0xFF value is sent, which will set associated devices to their last sa | | 1 | current Dimmer 2 state is sent, which will synchronize brightness leve | The manufacturer defined default value is ```0``` (0xFF value is sent, which will set associated devices to their last sa). This parameter has the configuration ID ```config_21_1``` and is of type ```INTEGER```. ### Parameter 22: Change [On-Off] bi-stable keys This function allow user to change [On-Off] bi-stable keys (parameter no. 14) (default value 0) The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | Device changes status on key status change | | 1 | Device status depends on key status; ON when the key is ON, OFF when t | The manufacturer defined default value is ```0``` (Device changes status on key status change). This parameter has the configuration ID ```config_22_1``` and is of type ```INTEGER```. ### Parameter 23: Double click option Double-click set lighting at 100% The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | Disable double click | | 1 | Enable double click | The manufacturer defined default value is ```1``` (Enable double click). This parameter has the configuration ID ```config_23_1``` and is of type ```INTEGER```. ### Parameter 24: Command frames sent in 2nd and 3rd association groups (S1 associations) Parameter determines, which actions will not result in sending frames to association groups. The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | all actions send to association groups | | 1 | do not send when switching ON (single click) | | 2 | do not send when switching OFF (single click) | | 4 | do not send when changing dimming level (holding and releasing) | | 8 | do not send on double click | | 16 | send 0xFF value on double click | The manufacturer defined default value is ```0``` (all actions send to association groups). This parameter has the configuration ID ```config_24_1``` and is of type ```INTEGER```. ### Parameter 25: Command frames sent in 4th and 5th association groups (S2associations) Parameter determines, which actions will not result in sending frames to association groups. The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | all actions send to association groups | | 1 | do not send when switching ON (single click) | | 2 | do not send when switching OFF (single click) | | 4 | do not send when changing dimming level (holding and releasing) | | 8 | do not send on double click | | 16 | send 0xFF value on double click | The manufacturer defined default value is ```0``` (all actions send to association groups). This parameter has the configuration ID ```config_25_1``` and is of type ```INTEGER```. ### Parameter 26: The function of 3-way switch Key no. 2 controls the Dimmer additionally (in 3-way switch mode). Function disabled for parameter 20 set to 2 (roller blind switch). The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | 3-way switch function for S2 disabled | | 1 | 3-way switch function for S2 enabled | The manufacturer defined default value is ```0``` (3-way switch function for S2 disabled). This parameter has the configuration ID ```config_26_1``` and is of type ```INTEGER```. ### Parameter 27: Associations in Z-Wave network security mode This parameter defines how commands are sent in specified association groups: as secure or non-secure. Parameter is active only in Z-Wave network security mode. It does not apply to 1st Lifeline group. The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | all groups (II-V) sent as non-secure | | 1 | 2nd group sent as secure | | 2 | 3rd group sent as secure | | 4 | 4th group sent as secure | | 8 | 5th group sent as secure | | 15 | all groups (II-V) sent as secure | The manufacturer defined default value is ```15``` (all groups (II-V) sent as secure). This parameter has the configuration ID ```config_27_1``` and is of type ```INTEGER```. ### Parameter 28: Scene activation functionality SCENE ID depends on the switch type configuration The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | Scene functionality deactivated | | 1 | Scene functionality activated | The manufacturer defined default value is ```0``` (Scene functionality deactivated). This parameter has the configuration ID ```config_28_1``` and is of type ```INTEGER```. ### Parameter 29: Switch functionality of S1 and S2 Switch S1 and S2 buttons The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | standard mode | | 1 | S1 operates as S2, S2 operates as S1 | The manufacturer defined default value is ```0``` (standard mode). This parameter has the configuration ID ```config_29_1``` and is of type ```INTEGER```. ### Parameter 30: Load control mode The parameter defines the used control mode. The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | forced leading edge control | | 1 | forced trailing edge control | | 2 | control mode selected automatically (based on auto-calibration) | The manufacturer defined default value is ```2``` (control mode selected automatically (based on auto-calibration)). This parameter has the configuration ID ```config_30_1``` and is of type ```INTEGER```. ### Parameter 31: Load control mode recognized during auto-calibration Load control mode recognized during auto-calibration The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | leading edge control | | 1 | trailing edge control | The manufacturer defined default value is ```0``` (leading edge control). This parameter has the configuration ID ```config_31_1``` and is of type ```INTEGER```. This is a read only parameter. ### Parameter 32: On/Off mode This mode is necessary while connecting non-dimmable light sources. Enabling parameter 32 automatically ignores brightening/- dimming time settings. The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | on/off mode disabled (dimming is possible) | | 1 | on/off mode enabled (dimming is not possible) | | 2 | mode selected automatically | The manufacturer defined default value is ```2``` (mode selected automatically). This parameter has the configuration ID ```config_32_1``` and is of type ```INTEGER```. ### Parameter 33: Dimmability of the load (read only) Dimmability of the load (read only) The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | Load recognized as dimmable | | 1 | Load recognized as non-dimmable | The manufacturer defined default value is ```0``` (Load recognized as dimmable). This parameter has the configuration ID ```config_33_1``` and is of type ```INTEGER```. This is a read only parameter. ### Parameter 34: Soft-Start functionality Time required to warm up the filament of halogen bulb. The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | no soft-start | | 1 | short soft-start (0,1s) | | 2 | long soft-start (0,5s) | The manufacturer defined default value is ```1``` (short soft-start (0,1s)). This parameter has the configuration ID ```config_34_1``` and is of type ```INTEGER```. ### Parameter 35: Auto-calibration after power on This parameter determines the trigger of auto-calibration procedure, e.g. power on, load error, etc. The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | No auto-calibration of the load after power on | | 1 | Auto-calibration performed after first power on | | 2 | Auto-calibration performed after each power on | | 3 | Auto-calibration performed after first power on or after each LOAD ERR | | 4 | Auto-calibration performed after each power on or after each LOAD ERRO | The manufacturer defined default value is ```1``` (Auto-calibration performed after first power on). This parameter has the configuration ID ```config_35_1``` and is of type ```INTEGER```. ### Parameter 37: Behaviour of the Dimmer after overload or surge The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | device permanently disabled until re-enabling by comand or push-button | | 1 | three attempts to turn on the load | The manufacturer defined default value is ```1``` (three attempts to turn on the load). This parameter has the configuration ID ```config_37_1``` and is of type ```INTEGER```. ### Parameter 38: Brightness level correction for flickering loads This parameter specifies the duration of Brightness level correction for flickering loads in seconds. 255 sets the function to "always enabled". 0 disables the function. Correction reduces spontaneous flickering of some capacitive load (e.g. dimmable LEDs) at certain brightness levels in 2-wire installation.  In countries using ripple-control, correction may cause changes in brightness. In this case it is necessary to disable correction or adjust time of correction for flickering loads. Values in the range 0 to 255 may be set. The manufacturer defined default value is ```255```. This parameter has the configuration ID ```config_38_2``` and is of type ```INTEGER```. ### Parameter 39: Power limit - OVERLOAD Reaching the defined value will result in turning off the load. Parameter 39 is relevant only in a 3-wire connection i or a 2-wire connection for load of cosφ ≥ 0.99. (1 W - 250 W). 0 disables the function. Values in the range 0 to 250 may be set. The manufacturer defined default value is ```250```. This parameter has the configuration ID ```config_39_2``` and is of type ```INTEGER```. ### Parameter 40: General Purpose Alarm The parameter specifies the response to an alarm. The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | No reaction | | 1 | Turn on the load | | 2 | Turn off the load | | 3 | Load blinking | The manufacturer defined default value is ```3``` (Load blinking). This parameter has the configuration ID ```config_40_1``` and is of type ```INTEGER```. ### Parameter 41: Water Flooding Alarm The parameter specifies the response to an alarm. The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | No reaction | | 1 | Turn on the load | | 2 | Turn off the load | | 3 | Load blinking | The manufacturer defined default value is ```2``` (Turn off the load). This parameter has the configuration ID ```config_41_1``` and is of type ```INTEGER```. ### Parameter 42: Smoke, CO or CO2 Alarm The parameter specifies the response to an alarm. The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | No reaction | | 1 | Turn on the load | | 2 | Turn off the load | | 3 | Load blinking | The manufacturer defined default value is ```3``` (Load blinking). This parameter has the configuration ID ```config_42_1``` and is of type ```INTEGER```. ### Parameter 43: Temperature Alarm The parameter specifies the response to an alarm. The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | No reaction | | 1 | Turn on the load | | 2 | Turn off the load | | 3 | Load blinking | The manufacturer defined default value is ```1``` (Turn on the load). This parameter has the configuration ID ```config_43_1``` and is of type ```INTEGER```. ### Parameter 44: Time of alarm state Alarm state may be cancelled earlier, as a result of pushing the wall-switch keys or sending the Z-Wave command frame. Available settings: 1-32767 (1s - 32767s). Values in the range 1 to 32767 may be set. The manufacturer defined default value is ```600```. This parameter has the configuration ID ```config_44_2``` and is of type ```INTEGER```. ### Parameter 45: OVERLOAD alarm report (load power consumption too high) The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | No reaction | | 1 | Send an alarm frame | The manufacturer defined default value is ```1``` (Send an alarm frame). This parameter has the configuration ID ```config_45_1``` and is of type ```INTEGER```. ### Parameter 46: LOAD ERROR alarm report (no load, load failure, burnt out bulb) The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | No reaction | | 1 | Send an alarm frame | The manufacturer defined default value is ```1``` (Send an alarm frame). This parameter has the configuration ID ```config_46_1``` and is of type ```INTEGER```. ### Parameter 47: OVERCURRENT alarm report (short circuit, burnt out bulb causing overcurrent) The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | No reaction | | 1 | Send an alarm frame | The manufacturer defined default value is ```1``` (Send an alarm frame). This parameter has the configuration ID ```config_47_1``` and is of type ```INTEGER```. ### Parameter 48: SURGE alarm report (Dimmer output overvoltage) The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | No reaction | | 1 | Send an alarm frame | The manufacturer defined default value is ```1``` (Send an alarm frame). This parameter has the configuration ID ```config_48_1``` and is of type ```INTEGER```. ### Parameter 49: OVERHEAT (critical temperature) and VOLTAGE DROP (low voltage) alarm report The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | No reaction | | 1 | Send an alarm frame | The manufacturer defined default value is ```1``` (Send an alarm frame). This parameter has the configuration ID ```config_49_1``` and is of type ```INTEGER```. ### Parameter 50: Active power reports The parameter defines the power level change that will result in a new power report being sent. The value is a percentage of the previous report. 0 disables the function. Values in the range 0 to 100 may be set. The manufacturer defined default value is ```10```. This parameter has the configuration ID ```config_50_1``` and is of type ```INTEGER```. ### Parameter 52: Periodic active power and energy reports Parameter 52 defines a time period between consecutive reports. Timer is reset and counted from zero after each report (1 sec - 32767 sec). 0 disables the function. Values in the range 0 to 32767 may be set. The manufacturer defined default value is ```3600```. This parameter has the configuration ID ```config_52_2``` and is of type ```INTEGER```. ### Parameter 53: Energy reports Energy level change which will result in sending a new energy report. Available settings: 1-255 (0,01 - 2,55 kWh). 0 disables the function. Values in the range 1 to 255 may be set. The manufacturer defined default value is ```10```. This parameter has the configuration ID ```config_53_2``` and is of type ```INTEGER```. ### Parameter 54: Self-measurement The Dimmer may include active power and energy used by itself in reports sent to the main controller. The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | Self-measurement inactive | | 1 | Self-measurement active | The manufacturer defined default value is ```0``` (Self-measurement inactive). This parameter has the configuration ID ```config_54_1``` and is of type ```INTEGER```. ### Parameter 58: Method of calculating the active power This parameter defines how to calculate active power. It is useful in a case of 2-wire connection with light sources other than resistive. Note: Parameter 58 is set to 0 after forced auto-calibration The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | measurement based on the standard algorithm | | 1 | approximation based on the calibration data | | 2 | approximation based on the control angle | The manufacturer defined default value is ```0``` (measurement based on the standard algorithm). This parameter has the configuration ID ```config_58_1``` and is of type ```INTEGER```. ### Parameter 59: Approximated power at the maximum brightness level This parameter determines the approximate value of the power that will be reported by the device at its maximum brightness level. Available settings: 0-500 (0-500W). Note: Parameter 59 works only when parameter 58 has a value other than 0. Values in the range 0 to 500 may be set. The manufacturer defined default value is ```0```. This parameter has the configuration ID ```config_59_2``` and is of type ```INTEGER```. ### Switch All Mode Set the mode for the switch when receiving SWITCH ALL commands. The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | Exclude from All On and All Off groups | | 1 | Include in All On group | | 2 | Include in All Off group | | 255 | Include in All On and All Off groups | This parameter has the configuration ID ```switchall_mode``` and is of type ```INTEGER```. ## Association Groups Association groups allow the device to send unsolicited reports to the controller, or other devices in the network. Using association groups can allow you to eliminate polling, providing instant feedback of a device state change without unnecessary network traffic. The FGD212 supports 5 association groups. ### Group 1: Lifeline The Lifeline association group reports device status to a hub and is not designed to control other devices directly. When using the Lineline group with a hub, in most cases, only the lifeline group will need to be configured and normally the hub will perform this automatically during the device initialisation. Association group 1 supports 1 node. ### Group 2: Sends BASIC SET command class frame according to the state of the devi Association group 2 supports 10 nodes. ### Group 3: Sends BASIC SET command class frame according to the state of the devi Association group 3 supports 10 nodes. ### Group 4: Sends BASIC SET command class frame according to the state of the devi Association group 4 supports 10 nodes. ### Group 5: Sends BASIC SET command class frame according to the state of the devi Association group 5 supports 10 nodes. ## Technical Information ### Endpoints #### Endpoint 0 | Command Class | Comment | |---------------|---------| | COMMAND_CLASS_NO_OPERATION_V1| | | COMMAND_CLASS_BASIC_V1| | | COMMAND_CLASS_APPLICATION_STATUS_V1| | | COMMAND_CLASS_SWITCH_MULTILEVEL_V3| Linked to BASIC| | COMMAND_CLASS_SWITCH_ALL_V1| | | COMMAND_CLASS_SCENE_ACTIVATION_V1| | | COMMAND_CLASS_SENSOR_MULTILEVEL_V4| | | COMMAND_CLASS_METER_V3| | | COMMAND_CLASS_CRC_16_ENCAP_V1| | | COMMAND_CLASS_DEVICE_RESET_LOCALLY_V1| | | COMMAND_CLASS_ZWAVEPLUS_INFO_V1| | | COMMAND_CLASS_MULTI_CHANNEL_V2| | | COMMAND_CLASS_CONFIGURATION_V1| | | COMMAND_CLASS_ALARM_V5| | | COMMAND_CLASS_MANUFACTURER_SPECIFIC_V1| | | COMMAND_CLASS_POWERLEVEL_V1| | | COMMAND_CLASS_PROTECTION_V2| | | COMMAND_CLASS_FIRMWARE_UPDATE_MD_V1| | | COMMAND_CLASS_ASSOCIATION_V2| | | COMMAND_CLASS_VERSION_V2| | | COMMAND_CLASS_SECURITY_V1| | #### Endpoint 1 | Command Class | Comment | |---------------|---------| | COMMAND_CLASS_BASIC_V1| | | COMMAND_CLASS_SWITCH_MULTILEVEL_V3| Linked to BASIC| | COMMAND_CLASS_SENSOR_MULTILEVEL_V4| | | COMMAND_CLASS_METER_V3| | | COMMAND_CLASS_ZWAVEPLUS_INFO_V1| | | COMMAND_CLASS_ALARM_V5| | | COMMAND_CLASS_ASSOCIATION_V2| | | COMMAND_CLASS_VERSION_V2| | #### Endpoint 2 | Command Class | Comment | |---------------|---------| | COMMAND_CLASS_BASIC_V1| | | COMMAND_CLASS_SWITCH_MULTILEVEL_V3| Linked to BASIC| | COMMAND_CLASS_ZWAVEPLUS_INFO_V1| | | COMMAND_CLASS_ASSOCIATION_V2| | | COMMAND_CLASS_VERSION_V2| | ### Documentation Links * [Operating manual](https://www.cd-jackson.com/zwave_device_uploads/787/Fibaro-Dimmer-2-FGD212-v3-5.pdf) --- Did you spot an error in the above definition or want to improve the content? You can [contribute to the database here](http://www.cd-jackson.com/index.php/zwave/zwave-device-database/zwave-device-list/devicesummary/787).