--- layout: documentation title: 4512757 - ZWave --- {% include base.html %} # 4512757 Z-Wave thermostat This describes the Z-Wave device *4512757*, manufactured by *Namron* with the thing type UID of ```namron_4512757_00_000```. The device is in the category of *HVAC*, defining Air condition devices, Fans. ![4512757 product image](https://opensmarthouse.org/zwavedatabase/1537/image/) The 4512757 supports routing. This allows the device to communicate using other routing enabled devices as intermediate routers. This device is also able to participate in the routing of data between other devices in the mesh network. ## Overview Z-Wave 16A heating (or cooling) wall thermostat with four regular buttons below the display. Internal, external and floor temperature sensors are supported. ### Inclusion Information Press M-key for 10 seconds to enter settings mode. Press up/down arrow keys to select "NET". Short press M-key, should show "IN". Press M-key for 2 seconds to start inclusion, display will show "i..." **.** ### Exclusion Information Press M-key for 10 seconds to enter settings mode. Press up/down arrow keys to select "NET". Short press M-key, should show "OUT." Press M-key for 2 seconds to start inclusion, display will show "o..." . ### General Usage Information Note that the exclusion mode "OUT" is not perfect. Also, factory reset does not seem to forget a network inclusion. ## Channels The following table summarises the channels available for the 4512757 -: | Channel Name | Channel ID | Channel Type | Category | Item Type | |--------------|------------|--------------|----------|-----------| | Switch | switch_binary | switch_binary | Switch | Switch | | Sensor (temperature) | sensor_temperature | sensor_temperature | Temperature | Number:Temperature | | Electric meter (kWh) | meter_kwh | meter_kwh | Energy | Number | | Electric meter (watts) | meter_watts | meter_watts | Energy | Number | | Electric meter (volts) | meter_voltage | meter_voltage | Energy | Number | | Electric meter (amps) | meter_current | meter_current | Energy | Number | | Thermostat mode | thermostat_mode | thermostat_mode | Temperature | Number | | Operating State | thermostat_state | thermostat_state | Temperature | Number | | Setpoint (heating) | thermostat_setpoint | thermostat_setpoint | Heating | Number:Temperature | | Setpoint (cooling) | thermostat_setpoint | thermostat_setpoint | Heating | Number:Temperature | | Alarm (access) | alarm_access | alarm_access | Door | Switch | | Alarm (power) | alarm_power | alarm_power | Energy | Switch | | Alarm (system) | alarm_system | alarm_system | | Switch | | Clock Time Offset | time_offset | time_offset | Time | Number | ### Switch Switch the power on and off. The ```switch_binary``` channel is of type ```switch_binary``` and supports the ```Switch``` item and is in the ```Switch``` category. ### Sensor (temperature) Indicates the current temperature. The ```sensor_temperature``` channel is of type ```sensor_temperature``` and supports the ```Number:Temperature``` item and is in the ```Temperature``` category. ### Electric meter (kWh) Indicates the energy consumption (kWh). The ```meter_kwh``` channel is of type ```meter_kwh``` and supports the ```Number``` item and is in the ```Energy``` category. This is a read only channel so will only be updated following state changes from the device. ### Electric meter (watts) Indicates the instantaneous power consumption. The ```meter_watts``` channel is of type ```meter_watts``` and supports the ```Number``` item and is in the ```Energy``` category. This is a read only channel so will only be updated following state changes from the device. ### Electric meter (volts) Indicates the instantaneous voltage. The ```meter_voltage``` channel is of type ```meter_voltage``` and supports the ```Number``` item and is in the ```Energy``` category. This is a read only channel so will only be updated following state changes from the device. ### Electric meter (amps) Indicates the instantaneous current consumption. The ```meter_current``` channel is of type ```meter_current``` and supports the ```Number``` item and is in the ```Energy``` category. This is a read only channel so will only be updated following state changes from the device. ### Thermostat mode Sets the thermostat. The ```thermostat_mode``` channel is of type ```thermostat_mode``` and supports the ```Number``` item and is in the ```Temperature``` category. The following state translation is provided for this channel to the ```Number``` item type -: | Value | Label | |-------|-----------| | 0 | Off | | 1 | Heat | | 2 | Cool | | 3 | Auto | | 4 | Aux Heat | | 5 | Resume | | 6 | Fan Only | | 7 | Furnace | | 8 | Dry Air | | 9 | Moist Air | | 10 | Auto Changeover | | 11 | Heat Economy | | 12 | Cool Economy | | 13 | Away | ### Operating State Sets the thermostat operating state. The ```thermostat_state``` channel is of type ```thermostat_state``` and supports the ```Number``` item and is in the ```Temperature``` category. The following state translation is provided for this channel to the ```Number``` item type -: | Value | Label | |-------|-----------| | 0 | Idle | | 1 | Heating | | 2 | Cooling | | 3 | Fan Only | | 4 | Pending Heat | | 5 | Pending Cool | | 6 | Vent / Economiser | ### Setpoint (heating) Sets the thermostat setpoint. The ```thermostat_setpoint``` channel is of type ```thermostat_setpoint``` and supports the ```Number:Temperature``` item and is in the ```Heating``` category. ### Setpoint (cooling) Sets the thermostat setpoint. The ```thermostat_setpoint``` channel is of type ```thermostat_setpoint``` and supports the ```Number:Temperature``` item and is in the ```Heating``` category. ### Alarm (access) Indicates if the access control alarm is triggered. The ```alarm_access``` channel is of type ```alarm_access``` and supports the ```Switch``` item and is in the ```Door``` category. This is a read only channel so will only be updated following state changes from the device. The following state translation is provided for this channel to the ```Switch``` item type -: | Value | Label | |-------|-----------| | OFF | OK | | ON | Alarm | ### Alarm (power) Indicates if a power alarm is triggered. The ```alarm_power``` channel is of type ```alarm_power``` and supports the ```Switch``` item and is in the ```Energy``` category. This is a read only channel so will only be updated following state changes from the device. The following state translation is provided for this channel to the ```Switch``` item type -: | Value | Label | |-------|-----------| | OFF | OK | | ON | Alarm | ### Alarm (system) Indicates if a system alarm is triggered. The ```alarm_system``` channel is of type ```alarm_system``` and supports the ```Switch``` item. This is a read only channel so will only be updated following state changes from the device. The following state translation is provided for this channel to the ```Switch``` item type -: | Value | Label | |-------|-----------| | OFF | OK | | ON | Alarm | ### Clock Time Offset Provides the current time difference for the devices time. The ```time_offset``` channel is of type ```time_offset``` and supports the ```Number``` item and is in the ```Time``` category. ## Device Configuration The following table provides a summary of the 26 configuration parameters available in the 4512757. Detailed information on each parameter can be found in the sections below. | Param | Name | Description | |-------|-------|-------------| | 4 | Eco Mode | Enable ECO mode | | 8 | Window Check | Enable window open detection | | 10 | Frost Enable | Enable frost detection and prevention feature. Note that enabling this mode overrides normal thermostat mode and forces the setpoint to the frost limit, so this mode should usually be left disabled. | | 23 | Temp Unit | Select unit for temperature | | 27 | Temp Correction | Temperature correction/calibration; in 1/10 °C | | 31 | Work Days Set | For week program mode, set which are working days | | 40 | Child Lock | Enable child lock mode where panel buttons are ignored | | 43 | Sensor Mode | Select which sensors to use | | 58 | Run Mode | Select between manual mode or weekly program | | 112 | Adaptation | Enable adaptation mode, self adjusting | | 118 | Regulator | Specify heating schedule time; in minutes, 0 to turn off | | 123 | LCD Backlight Standby | LCD backlight brightness in standby mode; in % | | 124 | LCD Backligh Work | LCD backlight brightness in working mode; in % | | 127 | Regulator Percentage | Regulator percentage; in % | | 134 | Dif Celcius | Regulator temperature hysteresis, Celcius mode; in 1/10 °C (step 5) | | 135 | Dif Fahrenheit | Regulator termperature hysteresis, Fahrenheit mode; in 1/10 °F (step 10) | | 136 | Frost Celsius | Frost limit in Celcius mode; in 1/10 °C (step 10) | | 137 | Frost Fahrenheit | Frost limit in Fahrenheit mode; 1/10 °F (step 20) | | 183 | Drying Time | Drying time; in minutes (step 5), 0 for off | | 185 | Celcius Floor Limit | Floor limit temperature in Celcius mode; in 1/10 °C (step 50) | | 186 | Fahrenheit Floor Limit | Floor limit temperature in Fahrenheit mode; in 1/10 °F (step 10) | | 187 | LCD Display Switch | LCD display switch | | 188 | Automatically Get Network Time | Automatically get network time | | 199 | Week Program Time | Four byte fields, see manual | | 200 | Week Program Celsius | Four byte fields, see manual | | 201 | Week Program Fahrenheit | Four byte fields, see manual | ### Parameter 4: Eco Mode Enable ECO mode The following option values may be configured, in addition to values in the range 0 to 1 -: | Value | Description | |--------|-------------| | 0 | Off | | 1 | On | The manufacturer defined default value is ```0``` (Off). This parameter has the configuration ID ```config_4_4``` and is of type ```INTEGER```. ### Parameter 8: Window Check Enable window open detection The following option values may be configured, in addition to values in the range 0 to 1 -: | Value | Description | |--------|-------------| | 0 | Off | | 1 | On | The manufacturer defined default value is ```1``` (On). This parameter has the configuration ID ```config_8_4``` and is of type ```INTEGER```. ### Parameter 10: Frost Enable Enable frost detection and prevention feature. Note that enabling this mode overrides normal thermostat mode and forces the setpoint to the frost limit, so this mode should usually be left disabled. The following option values may be configured, in addition to values in the range 0 to 1 -: | Value | Description | |--------|-------------| | 0 | Off | | 1 | On | The manufacturer defined default value is ```0``` (Off). This parameter has the configuration ID ```config_10_4``` and is of type ```INTEGER```. ### Parameter 23: Temp Unit Select unit for temperature The following option values may be configured, in addition to values in the range 0 to 1 -: | Value | Description | |--------|-------------| | 0 | °C | | 1 | °F | The manufacturer defined default value is ```0``` (°C). This parameter has the configuration ID ```config_23_0``` and is of type ```INTEGER```. ### Parameter 27: Temp Correction Temperature correction/calibration; in 1/10 °C Values in the range -10 to 10 may be set. The manufacturer defined default value is ```0```. This parameter has the configuration ID ```config_27_4``` and is of type ```INTEGER```. ### Parameter 31: Work Days Set For week program mode, set which are working days This is an advanced parameter and will therefore not show in the user interface without entering advanced mode. The following option values may be configured, in addition to values in the range 0 to 3 -: | Value | Description | |--------|-------------| | 0 | 12345/67 | | 1 | 123456/7 | | 2 | /1234567 | | 3 | 1234567/ | The manufacturer defined default value is ```0``` (12345/67). This parameter has the configuration ID ```config_31_4``` and is of type ```INTEGER```. ### Parameter 40: Child Lock Enable child lock mode where panel buttons are ignored The following option values may be configured, in addition to values in the range 0 to 1 -: | Value | Description | |--------|-------------| | 0 | Off | | 1 | On | The manufacturer defined default value is ```0``` (Off). This parameter has the configuration ID ```config_40_4``` and is of type ```INTEGER```. ### Parameter 43: Sensor Mode Select which sensors to use The following option values may be configured, in addition to values in the range 0 to 6 -: | Value | Description | |--------|-------------| | 0 | Internal sensor | | 1 | Floor sensor | | 2 | Internal sensor with floor temperature limit | | 3 | External sensor | | 4 | External sensor with floor temperature limit | | 5 | Do not use | | 6 | Controller heating percentage | The manufacturer defined default value is ```1``` (Floor sensor). This parameter has the configuration ID ```config_43_4``` and is of type ```INTEGER```. ### Parameter 58: Run Mode Select between manual mode or weekly program The following option values may be configured, in addition to values in the range 0 to 1 -: | Value | Description | |--------|-------------| | 0 | Manual | | 1 | Program | The manufacturer defined default value is ```1``` (Program). This parameter has the configuration ID ```config_58_4``` and is of type ```INTEGER```. ### Parameter 112: Adaptation Enable adaptation mode, self adjusting The following option values may be configured, in addition to values in the range 0 to 1 -: | Value | Description | |--------|-------------| | 0 | Off | | 1 | On | The manufacturer defined default value is ```0``` (Off). This parameter has the configuration ID ```config_112_4``` and is of type ```INTEGER```. ### Parameter 118: Regulator Specify heating schedule time; in minutes, 0 to turn off The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | Off | The manufacturer defined default value is ```30```. This parameter has the configuration ID ```config_118_4``` and is of type ```INTEGER```. ### Parameter 123: LCD Backlight Standby LCD backlight brightness in standby mode; in % Values in the range 10 to 100 may be set. The manufacturer defined default value is ```10```. This parameter has the configuration ID ```config_123_4``` and is of type ```INTEGER```. ### Parameter 124: LCD Backligh Work LCD backlight brightness in working mode; in % Values in the range 10 to 100 may be set. The manufacturer defined default value is ```100```. This parameter has the configuration ID ```config_124_4``` and is of type ```INTEGER```. ### Parameter 127: Regulator Percentage Regulator percentage; in % Values in the range 0 to 100 may be set. The manufacturer defined default value is ```20```. This parameter has the configuration ID ```config_127_4``` and is of type ```INTEGER```. ### Parameter 134: Dif Celcius Regulator temperature hysteresis, Celcius mode; in 1/10 °C (step 5) Values in the range 5 to 100 may be set. The manufacturer defined default value is ```10```. This parameter has the configuration ID ```config_134_4``` and is of type ```INTEGER```. ### Parameter 135: Dif Fahrenheit Regulator termperature hysteresis, Fahrenheit mode; in 1/10 °F (step 10) Values in the range 10 to 180 may be set. The manufacturer defined default value is ```20```. This parameter has the configuration ID ```config_135_4``` and is of type ```INTEGER```. ### Parameter 136: Frost Celsius Frost limit in Celcius mode; in 1/10 °C (step 10) Values in the range 50 to 100 may be set. The manufacturer defined default value is ```50```. This parameter has the configuration ID ```config_136_0``` and is of type ```INTEGER```. ### Parameter 137: Frost Fahrenheit Frost limit in Fahrenheit mode; 1/10 °F (step 20) Values in the range 410 to 510 may be set. The manufacturer defined default value is ```410```. This parameter has the configuration ID ```config_137_4``` and is of type ```INTEGER```. ### Parameter 183: Drying Time Drying time; in minutes (step 5), 0 for off The following option values may be configured -: | Value | Description | |--------|-------------| | 0 | Off | The manufacturer defined default value is ```30```. This parameter has the configuration ID ```config_183_4``` and is of type ```INTEGER```. ### Parameter 185: Celcius Floor Limit Floor limit temperature in Celcius mode; in 1/10 °C (step 50) Values in the range 50 to 600 may be set. The manufacturer defined default value is ```270```. This parameter has the configuration ID ```config_185_4``` and is of type ```INTEGER```. ### Parameter 186: Fahrenheit Floor Limit Floor limit temperature in Fahrenheit mode; in 1/10 °F (step 10) Values in the range 410 to 1400 may be set. The manufacturer defined default value is ```810```. This parameter has the configuration ID ```config_186_4``` and is of type ```INTEGER```. ### Parameter 187: LCD Display Switch LCD display switch The following option values may be configured, in addition to values in the range 0 to 1 -: | Value | Description | |--------|-------------| | 0 | Off | | 1 | On | The manufacturer defined default value is ```1``` (On). This parameter has the configuration ID ```config_187_4``` and is of type ```INTEGER```. ### Parameter 188: Automatically Get Network Time Automatically get network time The following option values may be configured, in addition to values in the range 0 to 1 -: | Value | Description | |--------|-------------| | 0 | Off | | 1 | On | The manufacturer defined default value is ```0``` (Off). This parameter has the configuration ID ```config_188_4``` and is of type ```INTEGER```. ### Parameter 199: Week Program Time Four byte fields, see manual This is an advanced parameter and will therefore not show in the user interface without entering advanced mode. Values in the range 0 to 0 may be set. The manufacturer defined default value is ```0```. This parameter has the configuration ID ```config_199_4``` and is of type ```INTEGER```. ### Parameter 200: Week Program Celsius Four byte fields, see manual This is an advanced parameter and will therefore not show in the user interface without entering advanced mode. Values in the range 0 to 0 may be set. The manufacturer defined default value is ```0```. This parameter has the configuration ID ```config_200_4``` and is of type ```INTEGER```. ### Parameter 201: Week Program Fahrenheit Four byte fields, see manual This is an advanced parameter and will therefore not show in the user interface without entering advanced mode. Values in the range 0 to 0 may be set. The manufacturer defined default value is ```0```. This parameter has the configuration ID ```config_201_4``` and is of type ```INTEGER```. ## Association Groups Association groups allow the device to send unsolicited reports to the controller, or other devices in the network. Using association groups can allow you to eliminate polling, providing instant feedback of a device state change without unnecessary network traffic. The 4512757 supports 1 association group. ### Group 1: Report Available commands: **DEVICE\_RESET\_LOCALLY_NOTIFICATION SENSOR\_MULTILEVEL\_REPORT BINARY\_SWITCH\_REPORT NOTIFICATION_REPORT CONFIGURATION_REPORT THERMOSTAT\_MODE\_REPORT THERMOSTAT\_SETPOINT\_REPORT PROTECTION_REPORT METER_REPORT COMMAND\_CLASS\_INDICATOR ** Association group 1 supports 5 nodes. ## Technical Information ### Endpoints #### Endpoint 0 | Command Class | Comment | |---------------|---------| | COMMAND_CLASS_NO_OPERATION_V1| | | COMMAND_CLASS_BASIC_V1| | | COMMAND_CLASS_SWITCH_BINARY_V1| | | COMMAND_CLASS_SENSOR_MULTILEVEL_V10| | | COMMAND_CLASS_METER_V3| | | COMMAND_CLASS_THERMOSTAT_MODE_V1| | | COMMAND_CLASS_THERMOSTAT_OPERATING_STATE_V1| | | COMMAND_CLASS_THERMOSTAT_SETPOINT_V1| | | COMMAND_CLASS_TRANSPORT_SERVICE_V1| | | COMMAND_CLASS_ASSOCIATION_GRP_INFO_V1| | | COMMAND_CLASS_DEVICE_RESET_LOCALLY_V1| | | COMMAND_CLASS_ZWAVEPLUS_INFO_V1| | | COMMAND_CLASS_SUPERVISION_V1| | | COMMAND_CLASS_CONFIGURATION_V1| | | COMMAND_CLASS_ALARM_V8| | | COMMAND_CLASS_MANUFACTURER_SPECIFIC_V1| | | COMMAND_CLASS_POWERLEVEL_V1| | | COMMAND_CLASS_PROTECTION_V2| | | COMMAND_CLASS_FIRMWARE_UPDATE_MD_V1| | | COMMAND_CLASS_ASSOCIATION_V2| | | COMMAND_CLASS_VERSION_V2| | | COMMAND_CLASS_INDICATOR_V3| | | COMMAND_CLASS_TIME_V1| | | COMMAND_CLASS_TIME_PARAMETERS_V1| | | COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION_V3| | | COMMAND_CLASS_SECURITY_V1| | | COMMAND_CLASS_SECURITY_2_V1| | ### Documentation Links * [User Manual](https://opensmarthouse.org/zwavedatabase/1537/reference/4512757-Manual-18.pdf) * [FDV document](https://opensmarthouse.org/zwavedatabase/1537/reference/4512757-FDV-1.pdf) * [FDV document](https://opensmarthouse.org/zwavedatabase/1537/reference/4512757-FDV-1_1.pdf) --- Did you spot an error in the above definition or want to improve the content? You can [contribute to the database here](https://opensmarthouse.org/zwavedatabase/1537).